Pressure-Temperature Charts

Saturation P-T data for common refrigerants

R-22

Pure
GWP: 1,810
ODP: 0.055
Safety Class: A1

HCFC refrigerant being phased out. Has ozone depletion potential. Common in legacy AC systems.

Quick P-T Lookup

kgf/cm²

* Results are interpolated from the P-T table data

Pressure Units: psig = Gauge pressure (relative to atmosphere) kPa / bar / kgf/cm² = Absolute pressure

°C °F kgf/cm²
-50 -58 0.3
-45 -49 0.4
-40 -40 0.6
-35 -31 0.8
-30 -22 1.1
-25 -13 1.4
-20 -4 1.8
-15 5 2.3
-10 14 2.8
-5 23 3.4
0 32 4.0
5 41 4.8
10 50 5.7
15 59 6.6
20 68 7.7
25 77 8.9
30 86 10.2
35 95 11.7
40 104 13.3
45 113 15.1
50 122 17.0
55 131 19.1
60 140 21.4
65 149 23.9
70 158 26.6
75 167 29.5
80 176 32.6
85 185 36.0
90 194 39.7