Pressure-Temperature Charts
Saturation P-T data for common refrigerants
Select Refrigerant
Low GWP (HFO)
Pressure Unit
R-22
Pure
GWP:
1,810
ODP:
0.055
Safety Class:
A1
HCFC refrigerant being phased out. Has ozone depletion potential. Common in legacy AC systems.
Quick P-T Lookup
psig
* Results are interpolated from the P-T table data
Pressure Units: psig = Gauge pressure (relative to atmosphere) kPa / bar / kgf/cm² = Absolute pressure
| °C | °F | psig |
|---|---|---|
| -50 | -58 | -10.5 |
| -45 | -49 | -7.4 |
| -40 | -40 | -3.8 |
| -35 | -31 | 0.5 |
| -30 | -22 | 5.5 |
| -25 | -13 | 11.3 |
| -20 | -4 | 17.9 |
| -15 | 5 | 25.4 |
| -10 | 14 | 33.9 |
| -5 | 23 | 43.4 |
| 0 | 32 | 54.0 |
| 5 | 41 | 65.9 |
| 10 | 50 | 79.1 |
| 15 | 59 | 93.6 |
| 20 | 68 | 109.7 |
| 25 | 77 | 127.4 |
| 30 | 86 | 146.8 |
| 35 | 95 | 168.0 |
| 40 | 104 | 191.1 |
| 45 | 113 | 216.2 |
| 50 | 122 | 243.4 |
| 55 | 131 | 272.8 |
| 60 | 140 | 304.6 |
| 65 | 149 | 338.9 |
| 70 | 158 | 375.9 |
| 75 | 167 | 415.6 |
| 80 | 176 | 458.3 |
| 85 | 185 | 504.2 |
| 90 | 194 | 553.3 |