Pressure-Temperature Charts
Saturation P-T data for common refrigerants
Select Refrigerant
Low GWP (HFO)
Pressure Unit
R-22
Pure
GWP:
1,810
ODP:
0.055
Safety Class:
A1
HCFC refrigerant being phased out. Has ozone depletion potential. Common in legacy AC systems.
Quick P-T Lookup
kPa
* Results are interpolated from the P-T table data
Pressure Units: psig = Gauge pressure (relative to atmosphere) kPa / bar / kgf/cm² = Absolute pressure
| °C | °F | kPa |
|---|---|---|
| -50 | -58 | 29.0 |
| -45 | -49 | 43.0 |
| -40 | -40 | 60.0 |
| -35 | -31 | 82.0 |
| -30 | -22 | 109.0 |
| -25 | -13 | 140.0 |
| -20 | -4 | 178.0 |
| -15 | 5 | 221.0 |
| -10 | 14 | 271.0 |
| -5 | 23 | 329.0 |
| 0 | 32 | 395.0 |
| 5 | 41 | 470.0 |
| 10 | 50 | 555.0 |
| 15 | 59 | 649.0 |
| 20 | 68 | 755.0 |
| 25 | 77 | 872.0 |
| 30 | 86 | 1,002.0 |
| 35 | 95 | 1,145.0 |
| 40 | 104 | 1,303.0 |
| 45 | 113 | 1,476.0 |
| 50 | 122 | 1,665.0 |
| 55 | 131 | 1,871.0 |
| 60 | 140 | 2,095.0 |
| 65 | 149 | 2,339.0 |
| 70 | 158 | 2,603.0 |
| 75 | 167 | 2,889.0 |
| 80 | 176 | 3,198.0 |
| 85 | 185 | 3,532.0 |
| 90 | 194 | 3,892.0 |