Pressure-Temperature Charts
Saturation P-T data for common refrigerants
Select Refrigerant
Low GWP (HFO)
Pressure Unit
R-290
Pure
GWP:
3
ODP:
0
Safety Class:
A3
Natural refrigerant with ultra-low GWP. Used in small commercial refrigeration and domestic applications (charge limits apply per IEC 60335-2-89).
A3 HIGHLY FLAMMABLE - Safety Warning
- ASHRAE 34 Classification: A3 - Non-toxic but HIGHLY FLAMMABLE
- Maximum charge limits: 150g (sealed systems) per IEC 60335-2-89
- Use only explosion-proof equipment and tools
- Work in well-ventilated areas - gas is heavier than air
- No open flames, sparks, or hot surfaces during service
- Use hydrocarbon-rated recovery equipment and leak detectors
- Install gas detection equipment per local codes
Flammability Range:
LEL 2.1% - UEL 9.5% in air
Quick P-T Lookup
kPa
* Results are interpolated from the P-T table data
Pressure Units: psig = Gauge pressure (relative to atmosphere) kPa / bar / kgf/cm² = Absolute pressure
| °C | °F | kPa |
|---|---|---|
| -50 | -58 | 38.0 |
| -45 | -49 | 54.0 |
| -40 | -40 | 74.0 |
| -35 | -31 | 98.0 |
| -30 | -22 | 128.0 |
| -25 | -13 | 163.0 |
| -20 | -4 | 205.0 |
| -15 | 5 | 254.0 |
| -10 | 14 | 310.0 |
| -5 | 23 | 374.0 |
| 0 | 32 | 447.0 |
| 5 | 41 | 528.0 |
| 10 | 50 | 620.0 |
| 15 | 59 | 722.0 |
| 20 | 68 | 834.0 |
| 25 | 77 | 958.0 |
| 30 | 86 | 1,094.0 |
| 35 | 95 | 1,243.0 |
| 40 | 104 | 1,407.0 |
| 45 | 113 | 1,585.0 |
| 50 | 122 | 1,779.0 |
| 55 | 131 | 1,990.0 |
| 60 | 140 | 2,218.0 |
| 65 | 149 | 2,465.0 |
| 70 | 158 | 2,732.0 |
| 75 | 167 | 3,019.0 |
| 80 | 176 | 3,328.0 |
| 85 | 185 | 3,659.0 |
| 90 | 194 | 4,015.0 |