Pressure-Temperature Charts
Saturation P-T data for common refrigerants
Select Refrigerant
Low GWP (HFO)
Pressure Unit
R-134a
Pure
GWP:
1,430
ODP:
0
Safety Class:
A1
Common automotive and commercial refrigerant. Being phased out in automotive (EU) for R-1234yf due to GWP.
Quick P-T Lookup
psig
* Results are interpolated from the P-T table data
Pressure Units: psig = Gauge pressure (relative to atmosphere) kPa / bar / kgf/cm² = Absolute pressure
| °C | °F | psig |
|---|---|---|
| -40 | -40 | -7.2 |
| -35 | -31 | -4.1 |
| -30 | -22 | -0.5 |
| -26 | -15 | 2.4 |
| -25 | -13 | 3.2 |
| -20 | -4 | 7.4 |
| -15 | 5 | 12.0 |
| -10 | 14 | 17.1 |
| -5 | 23 | 22.8 |
| 0 | 32 | 29.1 |
| 5 | 41 | 36.0 |
| 10 | 50 | 43.6 |
| 15 | 59 | 52.0 |
| 20 | 68 | 61.3 |
| 25 | 77 | 71.4 |
| 30 | 86 | 82.5 |
| 35 | 95 | 94.7 |
| 40 | 104 | 108.0 |
| 45 | 113 | 122.6 |
| 50 | 122 | 138.5 |
| 55 | 131 | 155.9 |
| 60 | 140 | 174.8 |
| 65 | 149 | 195.4 |
| 70 | 158 | 217.8 |
| 75 | 167 | 242.2 |
| 80 | 176 | 268.6 |
| 85 | 185 | 297.3 |
| 90 | 194 | 328.4 |
| 95 | 203 | 362.2 |