Pressure-Temperature Charts

Saturation P-T data for common refrigerants

R-449A

Zeotropic
GWP: 1,397
ODP: 0
Safety Class: A1
Temperature Glide: 6°C

Retrofit replacement for R-404A/R-507A. Lower discharge temp than R-404A. Requires POE oil. Use dew point for superheat, bubble point for subcooling.

Quick P-T Lookup

kgf/cm²

* Results are interpolated from the P-T table data

Z

Zeotropic Blend

This refrigerant has a temperature glide of 6°C - use the correct saturation point!

Temperature Glide Visualization

Dew Point
100% Vapor
For Superheat
6°C Glide
Higher Temp Lower Temp
Bubble Point
100% Liquid
For Subcooling

DEW Suction Side / Superheat

  • Superheat = Suction Temp - Dew Point Temp
  • • Use at evaporator outlet
  • • Low pressure gauge reading
  • • Temperature where last liquid evaporates

BUBBLE Liquid Side / Subcooling

  • Subcooling = Bubble Point Temp - Liquid Temp
  • • Use at condenser outlet
  • • High pressure gauge reading
  • • Temperature where first bubble forms

Important: Using the wrong saturation point will give incorrect superheat/subcooling readings. For R-449A with 6°C glide, this error can significantly affect diagnosis and charging.

Dew Point (Vapor)

Used for suction line / evaporator

°C °F kgf/cm²
-50 -58 0.9
-45 -49 1.3
-40 -40 1.8
-35 -31 2.3
-30 -22 2.9
-25 -13 3.6
-20 -4 4.4
-17.8 0 4.8
-15 5 5.3
-10 14 6.3
-5 23 7.4
0 32 8.6
5 41 10.0
10 50 11.5
15 59 13.2
20 68 15.0
25 77 17.0
30 86 19.1
35 95 21.4
40 104 24.0
45 113 26.7
50 122 29.6
55 131 32.8
60 140 36.2

Bubble Point (Liquid)

Used for liquid line / condenser

°C °F kgf/cm²
-50 -58 1.3
-45 -49 1.8
-40 -40 2.3
-35 -31 2.9
-30 -22 3.6
-25 -13 4.4
-20 -4 5.3
-17.8 0 5.8
-15 5 6.3
-10 14 7.4
-5 23 8.7
0 32 10.0
5 41 11.6
10 50 13.2
15 59 15.0
20 68 17.0
25 77 19.2
30 86 21.5
35 95 24.1
40 104 26.8
45 113 29.8
50 122 33.0
55 131 36.5
60 140 40.2

Pressure Units: psig = Gauge pressure (relative to atmosphere) kPa / bar / kgf/cm² = Absolute pressure