Pressure-Temperature Charts
Saturation P-T data for common refrigerants
Select Refrigerant
Low GWP (HFO)
Pressure Unit
R-513A
Azeotropic
GWP:
631
ODP:
0
Safety Class:
A1
Near drop-in replacement for R-134a. Compatible with existing R-134a systems with POE oil. Zero temperature glide (azeotropic).
Quick P-T Lookup
kgf/cm²
* Results are interpolated from the P-T table data
Pressure Units: psig = Gauge pressure (relative to atmosphere) kPa / bar / kgf/cm² = Absolute pressure
| °C | °F | kgf/cm² |
|---|---|---|
| -50 | -58 | 0.4 |
| -45 | -49 | 0.6 |
| -40 | -40 | 0.5 |
| -35 | -31 | 0.8 |
| -30 | -22 | 1.0 |
| -25 | -13 | 1.4 |
| -20 | -4 | 1.7 |
| -15 | 5 | 2.2 |
| -10 | 14 | 2.6 |
| -5 | 23 | 3.1 |
| 0 | 32 | 3.7 |
| 5 | 41 | 4.3 |
| 10 | 50 | 5.1 |
| 15 | 59 | 5.8 |
| 20 | 68 | 6.7 |
| 25 | 77 | 7.6 |
| 30 | 86 | 8.6 |
| 35 | 95 | 9.7 |
| 40 | 104 | 10.9 |
| 45 | 113 | 12.2 |
| 50 | 122 | 13.6 |
| 55 | 131 | 15.1 |
| 60 | 140 | 16.7 |
| 65 | 149 | 18.5 |
| 70 | 158 | 20.4 |
| 75 | 167 | 22.3 |
| 80 | 176 | 24.5 |