Pressure-Temperature Charts
Saturation P-T data for common refrigerants
Select Refrigerant
Low GWP (HFO)
Pressure Unit
R-410A
Near-azeotropic
GWP:
2,088
ODP:
0
Quick P-T Lookup
kgf/cm²
* Results are interpolated from the P-T table data
Pressure Units: psig = Gauge pressure (relative to atmosphere) kPa / bar / kgf/cm² = Absolute pressure
| °C | °F | kgf/cm² |
|---|---|---|
| -50 | -58 | 0.8 |
| -45 | -49 | 1.1 |
| -40 | -40 | 1.6 |
| -35 | -31 | 2.0 |
| -30 | -22 | 2.6 |
| -25 | -13 | 3.2 |
| -20 | -4 | 3.9 |
| -15 | 5 | 4.8 |
| -10 | 14 | 5.7 |
| -5 | 23 | 6.7 |
| 0 | 32 | 7.9 |
| 5 | 41 | 9.2 |
| 10 | 50 | 10.6 |
| 15 | 59 | 12.2 |
| 20 | 68 | 13.9 |
| 25 | 77 | 15.8 |
| 30 | 86 | 17.9 |
| 35 | 95 | 20.1 |
| 40 | 104 | 22.6 |
| 45 | 113 | 25.2 |
| 50 | 122 | 28.1 |
| 55 | 131 | 31.1 |
| 60 | 140 | 34.5 |
| 65 | 149 | 38.0 |
| 70 | 158 | 41.9 |
| 75 | 167 | 46.0 |
| 80 | 176 | 50.4 |