M
Midea Error Codes
Inverter Mini-Splits & Air Conditioners ยท China
Prefixes: E=System/Sensor, F=Sensor/Protection, P=Protection, H=Status
E-Series (System/Sensor Errors)
| Code | Description | Possible Cause | Action |
|---|---|---|---|
| E0 | EEPROM parameter error | Indoor EEPROM data corrupted | Reset power; replace PCB if persists |
| E1 | Indoor/outdoor communication error | Signal wiring disconnected | Check communication wiring between units |
| E2 | Zero crossing error | Power supply frequency abnormal | Check power supply quality |
| E3 | Indoor fan speed error | Fan motor speed out of control | Check fan motor and drive circuit |
| E4 | Room temperature sensor fault | T1 sensor open or short | Check room temperature sensor |
| E5 | Evaporator temperature sensor fault | T2 sensor open or short | Check evaporator coil sensor |
| E6 | Outdoor temperature sensor fault | T3 sensor open or short | Check outdoor coil sensor |
| E8 | Duplex communication error | Address conflict on communication bus | Reset unit addresses |
| E9 | Expansion valve fault | EEV driver or valve failure | Check EEV coil and wiring |
| EC | Refrigerant leak detection | Leak sensor activated | Leak test, repair, and recharge system |
F-Series (Sensor/Protection Codes)
| Code | Description | Possible Cause | Action |
|---|---|---|---|
| F0 | Outdoor EEPROM error | Outdoor unit EEPROM fault | Reset power; replace outdoor PCB if needed |
| F1 | Outdoor ambient sensor fault | T4 thermistor failure | Check outdoor ambient sensor |
| F2 | Condenser coil sensor fault | Condenser thermistor failure | Check condenser sensor |
| F3 | Discharge temperature sensor fault | T5 thermistor failure | Check compressor discharge sensor |
| F4 | Suction temperature sensor fault | Suction line thermistor failure | Check suction line sensor |
P-Series (Protection Codes)
| Code | Description | Possible Cause | Action |
|---|---|---|---|
| P0 | IPM module protection | Inverter module overcurrent | Check IPM module and compressor |
| P1 | Over/under voltage protection | Supply voltage out of range | Check power supply voltage |
| P2 | Compressor top temperature protection | Compressor overheating | Check superheat, charge, airflow |
| P3 | High current protection | System drawing excess current | Check compressor and wiring |
| P4 | Inverter drive error | Drive board fault | Check inverter board and compressor wiring |
| P5 | DC fan motor fault | Outdoor fan feedback error | Check DC fan motor and wiring |
| P6 | Heat sink temperature high | Inverter heat sink overheating | Check outdoor unit ventilation |
No matching error codes found
Try a different search term or browse the categories above.
Midea Troubleshooting Tips
Before Calling for Service
- Turn off unit, wait 5 minutes, then restart - some errors auto-reset
- Check and clean air filters - many errors caused by restricted airflow
- Verify power supply voltage is within specification
- Check circuit breaker and disconnect switch
- Note the exact error code and when it occurs for technician