Fujitsu Error Codes
Halcyon, Airstage, and Mini-Split Systems
Quick Reference: Error Display Methods
Indoor Unit Display
E#:## format shows on unit display or remote controller
LED Flash Patterns
Count flashes of Operation, Timer, and Economy lights
Outdoor LED1/LED2
Two-digit codes via LED flash sequences
E-Series Errors
| Code | Description | Possible Cause | Solution |
|---|---|---|---|
| E0:00 | Communication error (remote/indoor) | Remote controller communication fault | Check remote wiring and connections |
| E1:00 | Indoor/outdoor communication error | Signal wire fault between units | Check S1/S2/S3 wiring, polarity |
| E2:00 | Return air thermistor error | Room temperature sensor open/short | Check thermistor resistance, replace if faulty |
| E3:00 | Indoor coil thermistor error | Coil temperature sensor fault | Check thermistor, verify connection |
| E4:00 | Indoor coil thermistor 2 error | Secondary coil sensor fault | Check and replace thermistor |
| E5:00 | Drain sensor / float switch error | Drain pump or float switch activated | Clean drain line, check float switch |
| E6:00 | Outdoor unit error detected | General outdoor unit fault | Check outdoor unit error codes |
| E7:00 | Indoor fan motor error | Fan motor locked or feedback error | Check motor windings, PCB, capacitor |
| E8:00 | Indoor unit current overload | Indoor PCB drawing excess current | Check wiring, reset power |
| E9:00 | Electronic expansion valve error | EEV not responding to commands | Check EEV coil, wiring, controller |
| EE:EE | EEPROM error | Indoor PCB memory fault | Replace indoor unit PCB |
Outdoor Unit Errors
| Code | Description | Possible Cause | Solution |
|---|---|---|---|
| 00 | Serial communication error | Outdoor PCB comm fault | Check outdoor unit wiring |
| 01 | Inverter board communication error | Inverter-to-main PCB fault | Check inverter board connections |
| 03 | Discharge thermistor error | Compressor discharge sensor fault | Check and replace thermistor |
| 04 | Outdoor coil thermistor error | Condenser temp sensor fault | Check and replace thermistor |
| 05 | Suction gas thermistor error | Suction line sensor fault | Check and replace thermistor |
| 06 | Outdoor ambient thermistor error | Outdoor air temp sensor fault | Check and replace thermistor |
| 07 | Outdoor coil thermistor 2 error | Secondary coil sensor fault | Check and replace thermistor |
| 08 | Compressor inlet thermistor error | Compressor inlet sensor fault | Check and replace thermistor |
| 09 | CT sensor error | Current transformer fault | Check CT sensor, inverter board |
| 10 | Inverter fin thermistor error | Heat sink temp sensor fault | Check thermistor, inverter board |
| 11 | Power transistor thermistor error | IPM temp sensor fault | Check thermistor, inverter board |
Protection Errors
| Code | Description | Possible Cause | Solution |
|---|---|---|---|
| 12 | High pressure protection | High discharge pressure | Clean condenser, check fan, verify charge |
| 14 | Suction pressure low | Low refrigerant or restriction | Leak test, check charge, inspect TXV |
| 16 | ACT over temperature | Reactor overheating | Check ventilation, reactor condition |
| 17 | Discharge temperature high | Compressor overheating | Check charge, airflow, compressor |
| 19 | Condenser temperature high | Poor heat rejection | Clean condenser, check fan operation |
| 20 | Compressor protection | Compressor overcurrent/thermal | Check compressor, inverter, charge |
| 21 | IPM protection (overcurrent) | Inverter power module fault | Check inverter board, compressor |
| 22 | AC overcurrent | High AC current draw | Check power supply, wiring |
| 23 | DC low voltage | Low DC bus voltage | Check power supply, capacitors |
| 24 | DC high voltage | High DC bus voltage | Check power supply, inverter |
| 25 | ACT current error | Reactor current abnormal | Check reactor, inverter board |
| 27 | Pressure sensor error | Pressure transducer fault | Check pressure sensor, wiring |
| 28 | Compressor position error | Rotor position feedback fault | Check compressor, inverter board |
| 29 | Compressor start failure | Compressor won't start | Check compressor, wiring, inverter |
| 30 | Compressor speed error | Compressor speed out of range | Check inverter board, compressor |
System Errors
| Code | Description | Possible Cause | Solution |
|---|---|---|---|
| 31 | Outdoor fan motor error | Fan motor lock or speed error | Check motor, blade obstruction |
| 32 | Outdoor fan motor 2 error | Secondary fan motor fault | Check motor, wiring |
| 33 | Solenoid valve error | Solenoid valve not operating | Check valve coil, wiring |
| 34 | Reversing valve error | 4-way valve not shifting | Check solenoid coil, verify valve movement |
| 35 | Inverter board error | Inverter PCB malfunction | Replace inverter board |
| 36 | Main PCB error | Outdoor control board fault | Replace outdoor PCB |
| 39 | Power supply phase error | Phase missing or reversed | Check 3-phase power supply |
LED Flash Codes (Indoor Unit)
| Code | Description | Possible Cause | Solution |
|---|---|---|---|
| Operation Light: 1 Flash | Indoor room thermistor error | Room temperature sensor fault | Check and replace thermistor |
| Operation Light: 2 Flashes | Indoor coil thermistor error | Coil temperature sensor fault | Check and replace thermistor |
| Operation Light: 3 Flashes | Transmission error | Indoor-outdoor communication fault | Check signal wiring |
| Operation Light: 4 Flashes | Drain pump error | Drain pump or float switch | Clean drain, check pump |
| Operation Light: 5 Flashes | Outdoor unit abnormality | Outdoor unit fault detected | Check outdoor unit error code |
| Operation Light: 6 Flashes | Indoor fan motor error | Fan motor not running correctly | Check motor, capacitor |
| Operation Light: 7 Flashes | EEPROM error | Indoor PCB memory fault | Replace indoor PCB |
| Operation Light: 8 Flashes | Freeze/overheat protection | Coil temp abnormal | Check airflow, filter, charge |
| Timer Light: Flashing | High pressure protection | High head pressure | Check condenser, fan, charge |
| Economy Light: Flashing | Power supply voltage error | Voltage abnormal | Check power supply voltage |
LED Flash Codes (Outdoor Unit)
| Code | Description | Possible Cause | Solution |
|---|---|---|---|
| LED1: 1 Flash | High pressure switch open | High discharge pressure | Check condenser, refrigerant charge |
| LED1: 2 Flashes | Inverter error | Inverter protection activated | Check inverter board, reset power |
| LED1: 3 Flashes | Indoor/outdoor transmission error | Communication fault | Check signal wiring connections |
| LED1: 4 Flashes | Outdoor thermistor error | Temperature sensor fault | Check and replace thermistor |
| LED1: 5 Flashes | CT/DC voltage error | Current or voltage sensor fault | Check sensors, inverter board |
| LED2: 1 Flash | High discharge temperature | Compressor overheating | Check charge, suction superheat |
| LED2: 2 Flashes | Outdoor fan motor error | Fan motor fault | Check motor, PCB |
| LED2: 3 Flashes | Low pressure protection | Low refrigerant | Leak test, recharge system |
| LED2: 4 Flashes | Compressor error | Compressor protection activated | Check compressor, inverter |
No matching error codes found
Try a different search term or browse the categories above.
Fujitsu Troubleshooting Tips
Reading Error Codes
- Wired Remote: Error displays directly on screen
- Wireless Remote: Press and hold TIMER button for 3 seconds
- Indoor LEDs: Count flash patterns carefully
- Outdoor LEDs: LED1 = tens digit, LED2 = ones digit
Most Common Issues
- E1:00: Communication error - check S1/S2/S3 wiring
- Error 12: High pressure - clean condenser, check charge
- Error 20/21: Inverter protection - check compressor
- E5:00: Drain issue - clean drain line and pump
Clearing Error Codes
- Turn off unit at circuit breaker for 30 seconds
- Turn power back on
- If error persists, the underlying issue must be resolved
- Some protection errors (like high pressure) require cooldown period