H
Hitachi Error Codes
Inverter Mini-Splits & Air Conditioners ยท Japan
Prefixes: E=System/Sensor, F=Sensor/Protection, P=Protection, H=Status
Other Codes
| Code | Description | Possible Cause | Action |
|---|---|---|---|
| 02 | High pressure protection | High pressure cut activated | Check refrigerant charge, condenser, fan operation |
| 03 | Indoor/outdoor communication error | Disconnected wires, loose terminals, incorrect wiring | Check communication wiring between units |
| 04 | Outdoor PCB to fan controller error | Blown fuse, loose connectors, broken wires | Check outdoor fan controller circuit |
| 06 | Phase detection failure | Phase sequence error or missing phase | Check 3-phase power supply, correct phase sequence |
| 0A | Outdoor to outdoor communication error | Damaged wiring, incorrect connections (multi-split) | Check wiring between outdoor units |
| 0B | Main unit address error | Multiple units set as main unit | Check address settings, set only one main |
| 0C | Sub unit address error | Address setting conflict | Correct address settings on sub units |
| 11 | Indoor inlet air thermistor error | Thermistor open/short circuit | Check/replace inlet air thermistor |
| 12 | Indoor outlet air thermistor error | Thermistor failure | Check/replace outlet air thermistor |
| 13 | Indoor freeze protection thermistor error | Evaporator thermistor fault | Check/replace evaporator thermistor |
| 14 | Indoor gas piping thermistor error | Gas pipe sensor failure | Check/replace gas pipe thermistor |
| 21 | Outdoor high pressure sensor error | Pressure transducer fault | Check/replace high pressure sensor |
| 22 | Outdoor low pressure sensor error | Pressure transducer fault | Check/replace low pressure sensor |
| 23 | Outdoor discharge gas thermistor error | Discharge temperature sensor fault | Check/replace discharge thermistor |
| 24 | Outdoor heat exchanger thermistor error | Condenser thermistor fault | Check/replace condenser thermistor |
| 25 | Outdoor suction gas thermistor error | Suction temperature sensor fault | Check/replace suction thermistor |
| 29 | Outdoor air thermistor error | Ambient temperature sensor fault | Check/replace outdoor air thermistor |
| 31 | Capacity setting mismatch | Indoor/outdoor capacity code incorrect | Verify capacity code settings match |
| 35 | Indoor unit number duplicated | Multiple units with same address | Assign unique addresses to each unit |
| 36 | Incompatible unit combination | Mismatched indoor/outdoor units | Verify unit compatibility |
| 39 | Constant compressor overcurrent | Running current abnormal | Check compressor, current sensor, power supply |
| 43 | Low pressure protection | Low suction pressure | Check refrigerant charge, filter, expansion valve |
| 44 | High pressure protection (repeat) | Repeated high pressure trips | Check condenser, refrigerant charge, ambient conditions |
| 45 | Discharge temperature protection | Compressor discharge overheat | Check superheat, refrigerant charge, airflow |
| 46 | Inverter compressor overcurrent | Inverter compressor drawing excess current | Check compressor, voltage, refrigerant |
| 47 | Valve locking protection | Service valve closed or restricted | Open service valves, check for restriction |
| 48 | Electrical overload | System drawing excessive power | Check power supply, reduce load |
| 53 | Inverter PCB failure | Inverter board malfunction | Replace inverter PCB |
| 54 | Inverter overheating | IPM module overheat | Check ventilation around outdoor unit |
| 55 | Fan motor error | Outdoor fan motor failure | Check fan motor, replace if necessary |
E-Series (System/Sensor Errors)
| Code | Description | Possible Cause | Action |
|---|---|---|---|
| E0 | Water pump error | Condensate pump failure | Check drain pump operation |
| E1 | Compressor thermal protection | Compressor internal protection | Check refrigerant charge, superheat |
| E3 | High pressure protection | High discharge pressure | Check condenser, fan, refrigerant |
| E5 | Inverter compressor error | Compressor startup failure | Check compressor, inverter, wiring |
| E9 | Indoor fan motor error | Indoor fan locked rotor | Check fan motor, obstructions |
| EE | Compressor protection alarm | Repeated compressor trips (3x in 6 hours) | Professional service required, check compressor |
No matching error codes found
Try a different search term or browse the categories above.
Hitachi Troubleshooting Tips
Before Calling for Service
- Turn off unit, wait 5 minutes, then restart - some errors auto-reset
- Check and clean air filters - many errors caused by restricted airflow
- Verify power supply voltage is within specification
- Check circuit breaker and disconnect switch
- Note the exact error code and when it occurs for technician