Pressure-Temperature Charts
Saturation P-T data for common refrigerants
Select Refrigerant
Low GWP (HFO)
Pressure Unit
R-600a
Pure
GWP:
3
ODP:
0
Safety Class:
A3
Natural refrigerant common in domestic refrigerators. Lower working pressure than R-290. Charge limits apply per IEC 60335-2-89.
A3 HIGHLY FLAMMABLE - Safety Warning
- ASHRAE 34 Classification: A3 - Non-toxic but HIGHLY FLAMMABLE
- Maximum charge limits: 150g (sealed systems) per IEC 60335-2-89
- Use only explosion-proof equipment and tools
- Work in well-ventilated areas - gas is heavier than air
- No open flames, sparks, or hot surfaces during service
- Use hydrocarbon-rated recovery equipment and leak detectors
- Most domestic refrigerators contain 50-100g charge
Flammability Range:
LEL 1.8% - UEL 8.4% in air
Quick P-T Lookup
bar
* Results are interpolated from the P-T table data
Pressure Units: psig = Gauge pressure (relative to atmosphere) kPa / bar / kgf/cm² = Absolute pressure
| °C | °F | bar |
|---|---|---|
| -50 | -58 | 0.1 |
| -45 | -49 | 0.2 |
| -40 | -40 | 0.3 |
| -35 | -31 | 0.4 |
| -30 | -22 | 0.5 |
| -25 | -13 | 0.6 |
| -20 | -4 | 0.8 |
| -15 | 5 | 1.0 |
| -12 | 10 | 1.2 |
| -10 | 14 | 1.2 |
| -5 | 23 | 1.5 |
| 0 | 32 | 1.9 |
| 5 | 41 | 2.3 |
| 10 | 50 | 2.8 |
| 15 | 59 | 3.3 |
| 20 | 68 | 4.0 |
| 25 | 77 | 4.7 |
| 30 | 86 | 5.5 |
| 35 | 95 | 6.4 |
| 40 | 104 | 7.4 |
| 45 | 113 | 8.5 |
| 50 | 122 | 9.7 |
| 55 | 131 | 11.1 |
| 60 | 140 | 12.6 |
| 65 | 149 | 14.3 |
| 70 | 158 | 16.1 |
| 75 | 167 | 18.0 |
| 80 | 176 | 20.2 |
| 85 | 185 | 22.5 |
| 90 | 194 | 25.0 |
| 95 | 203 | 27.8 |
| 100 | 212 | 30.7 |