Pressure-Temperature Charts

Saturation P-T data for common refrigerants

R-407C

Zeotropic
GWP: 1,774
ODP: 0
Temperature Glide: 7°C

Quick P-T Lookup

bar

* Results are interpolated from the P-T table data

Z

Zeotropic Blend

This refrigerant has a temperature glide of 7°C - use the correct saturation point!

Temperature Glide Visualization

Dew Point
100% Vapor
For Superheat
7°C Glide
Higher Temp Lower Temp
Bubble Point
100% Liquid
For Subcooling

DEW Suction Side / Superheat

  • Superheat = Suction Temp - Dew Point Temp
  • • Use at evaporator outlet
  • • Low pressure gauge reading
  • • Temperature where last liquid evaporates

BUBBLE Liquid Side / Subcooling

  • Subcooling = Bubble Point Temp - Liquid Temp
  • • Use at condenser outlet
  • • High pressure gauge reading
  • • Temperature where first bubble forms

Important: Using the wrong saturation point will give incorrect superheat/subcooling readings. For R-407C with 7°C glide, this error can significantly affect diagnosis and charging.

Dew Point (Vapor)

Used for suction line / evaporator

°C °F bar
-40 -40 1.3
-35 -31 1.7
-30 -22 2.2
-25 -13 2.8
-20 -4 3.4
-15 5 4.2
-10 14 5.0
-5 23 6.0
0 32 7.0
5 41 8.2
10 50 9.5
15 59 11.0
20 68 12.6
25 77 14.3
30 86 16.2
35 95 18.2
40 104 20.5
45 113 22.9
50 122 25.5
55 131 28.3
60 140 31.3

Bubble Point (Liquid)

Used for liquid line / condenser

°C °F bar
-40 -40 0.8
-35 -31 1.2
-30 -22 1.6
-25 -13 2.1
-20 -4 2.7
-15 5 3.3
-10 14 4.1
-5 23 4.9
0 32 5.8
5 41 6.8
10 50 8.0
15 59 9.3
20 68 10.7
25 77 12.2
30 86 13.9
35 95 15.7
40 104 17.7
45 113 19.8
50 122 22.2
55 131 24.7
60 140 27.4

Pressure Units: psig = Gauge pressure (relative to atmosphere) kPa / bar / kgf/cm² = Absolute pressure