Emerson/Alco

XCM-330

XCM Series • Refrigeration Controller

XCM-330

Quick Info

Type Refrigeration
Application Rack System
Probe Inputs 8
Relay Outputs 16
Communication RS485 Modbus RTU / Ethernet / BACnet
Panel Size 288x288 mm

Output Functions

R1 Comp stages
R2 Condenser fans
R3 Alarms

Compressor pack manager for up to 30 compressors

Technical Specifications

Display & Interface

Display Type LCD
Display Digits Graphic
Buttons 8
LED Indicators Run, Alarm, Comm, Network

Power Supply

Voltage 230V AC
Voltage Range 100-240V AC
Frequency 50/60Hz
Power Consumption 15VA

Sensor Inputs

Probe Inputs 8
Probe Type NTC / 4-20mA
Temp Range -50 to 150 / 0-50 bar°C
Accuracy ±0.3°C

Relay Outputs

Relay Outputs 16
Relay Rating 5A/250VAC

Physical

Panel Size 288x288 mm
Depth 100 mm
IP Rating IP54 (front)
Weight 2500 g

Operating Conditions

Operating Temp -10 to 55°C
Storage Temp -25 to 65°C

Wiring Terminals

Terminal Function Type Wire Color
1-2 Power 230VAC Input
brown/blue
AI1-AI8 Analog inputs Input
various
DI1-DI16 Digital inputs Input
various
RS1 RS485 Port 1 Comm
orange/yellow
RS2 RS485 Port 2 Comm
orange/yellow
ETH Ethernet RJ45 Comm
N/A
DO1-DO16 Relay outputs Output
various
AO1-AO4 Analog outputs Output
various

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SP Suction Press SP 0 to 30 4 bar Suction pressure setpoint
dP Stage Diff 0.1 to 3 0.5 bar Compressor staging differential
ST Stage Time 30 to 600 120 sec Minimum stage time
NC Comp Count 1 to 30 8 Number of compressors
NF Fan Count 1 to 16 6 Number of condenser fans
HP HP Setpoint 10 to 35 18 bar Condensing pressure target
HH HP Cutout 15 to 40 28 bar High pressure safety
LL LP Cutout -1 to 5 0 bar Low pressure safety

Error Codes

HP High pressure

Solution: Check condenser and fans

LP Low pressure

Solution: Check refrigerant charge

OP Oil pressure

Solution: Check oil level

OL Compressor overload

Solution: Check motor protection

PH Phase fault

Solution: Check power supply

SC Short cycle

Solution: Check staging settings

COM Communication error

Solution: Check network wiring

Frequently Asked Questions

Alternative Models (Cross Reference)

Dixell XC650D Carel pCO sistema Danfoss AK-PC 781

Manufacturer Information

Brand: Emerson/Alco

Country: USA

Parent: Copeland (Emerson Climate Technologies)

Visit Manufacturer Website