Emerson/Alco

EC3-X32

EC3 Series • Refrigeration Controller

EC3-X32

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 3
Relay Outputs 4
Communication RS485 Modbus RTU
Panel Size 32x74 mm

Output Functions

R1 Compressor
R2 Defrost
R3 Fan
R4 Alarm

Universal electronic controller for refrigeration with EEV capability

Technical Specifications

Display & Interface

Display Type LED
Display Digits 3
Buttons 4
LED Indicators Compressor, Defrost, Fan, Alarm

Power Supply

Voltage 230V AC
Voltage Range 100-240V AC
Frequency 50/60Hz
Power Consumption 5VA

Sensor Inputs

Probe Inputs 3
Probe Type NTC / PTC / PT1000
Temp Range -50 to 150°C
Accuracy ±0.5°C

Relay Outputs

Relay Outputs 4
Relay Rating 8A/250VAC (Comp 16A)

Physical

Panel Size 32x74 mm
Depth 68 mm
IP Rating IP65 (front)
Weight 115 g

Operating Conditions

Operating Temp -10 to 55°C
Storage Temp -25 to 65°C

Wiring Terminals

Terminal Function Type Wire Color
1 Power L Input
brown
2 Power N Input
blue
3-4 Probe 1 (Room) Input
yellow/white
5-6 Probe 2 (Evap) Input
green/white
7-8 Probe 3 (Aux) Input
orange/white
9 RS485 A+ Comm
orange
10 RS485 B- Comm
yellow
11-12 Compressor Output
black
13-14 Defrost Output
red
15-16 Fan Output
blue
17-18 Alarm Output
gray

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SP Setpoint -50 to 99 -18 °C Temperature setpoint
dF Differential 0.1 to 20 2 °C Switching differential
dT Defrost Type 0=Off,1=Elec,2=Gas,3=Timer 1 Defrost method
dI Defrost Interval 0 to 99 8 hr Defrost interval
dL Defrost Duration 0 to 240 30 min Max defrost time
dE Defrost End -50 to 50 8 °C End defrost temperature
Fd Fan Delay 0 to 30 3 min Fan delay after defrost
Ad Address 1 to 247 1 Modbus address

Error Codes

E1 Probe 1 fault

Solution: Check room probe wiring

E2 Probe 2 fault

Solution: Check evaporator probe

E3 Probe 3 fault

Solution: Check auxiliary probe

dF Defrost active

Solution: Normal operation

HA High temp alarm

Solution: Check refrigeration system

LA Low temp alarm

Solution: Check setpoint

Frequently Asked Questions

Alternative Models (Cross Reference)

Dixell XR60CX Eliwell EWCM Carel IR33+

Manufacturer Information

Brand: Emerson/Alco

Country: USA

Parent: Copeland (Emerson Climate Technologies)

Visit Manufacturer Website