Evco
EVK213N7
EVK Series • Refrigeration Controller
Quick Info
Type
Refrigeration
Application
Cold Room
Probe Inputs
2
Relay Outputs
3
Panel Size
32x74 mm
Output Functions
R1
Compressor
R2
Defrost
R3
Fan
Three relay controller with compressor, defrost and fan outputs
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 3 |
| Buttons | 4 |
| LED Indicators | Compressor, Defrost, Fan, Alarm |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 115-230V AC |
| Frequency | 50/60Hz |
| Power Consumption | 4VA |
Sensor Inputs
| Probe Inputs | 2 |
| Probe Type | NTC |
| Temp Range | -50 to 105°C |
| Accuracy | ±0.5°C |
Relay Outputs
| Relay Outputs | 3 |
| Relay Rating | 8A/250VAC |
Physical
| Panel Size | 32x74 mm |
| Depth | 65 mm |
| IP Rating | IP65 (front) |
| Weight | 100 g |
Operating Conditions
| Operating Temp | -5 to 50°C |
| Storage Temp | -20 to 60°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| 1 | Power L | Input |
brown
|
| 2 | Power N | Input |
blue
|
| 3-4 | Probe 1 | Input |
yellow/white
|
| 5-6 | Probe 2 | Input |
green/white
|
| 7-8 | Compressor | Output |
black
|
| 9-10 | Defrost | Output |
red
|
| 11-12 | Fan | Output |
blue
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SP | Setpoint | -50 to 50 | -18 °C | Temperature setpoint |
| dF | Differential | 0.1 to 20 | 2 °C | Switching differential |
| dt | Defrost Type | 0=Off,1=Elec,2=Gas | 1 | Defrost method |
| dI | Defrost Interval | 0 to 48 | 8 hr | Defrost interval |
| dL | Defrost Duration | 0 to 120 | 30 min | Max defrost time |
| Fd | Fan Delay | 0 to 15 | 3 min | Fan delay after defrost |
| Fc | Fan Control | 0=Cont,1=wComp | 1 | Fan operation mode |
Error Codes
E1
Probe 1 fault
Solution: Check room probe
E2
Probe 2 fault
Solution: Check evaporator probe
HA
High alarm
Solution: Check system
LA
Low alarm
Solution: Check setpoint
Frequently Asked Questions
0=Continuous running, 1=Runs only with compressor
Alternative Models (Cross Reference)
Dixell XR40CX
Eliwell ID 974
LAE AD2-5C34W
Manufacturer Information
Brand: Evco
Country: Italy