Output Functions
Electronic expansion valve and VSD compressor controller
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 4 |
| Buttons | 4 |
| LED Indicators | Comp, EEV, Alarm, Comm |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 100-240V AC |
| Frequency | 50/60Hz |
| Power Consumption | 8VA |
Sensor Inputs
| Probe Inputs | 4 |
| Probe Type | NTC / 4-20mA |
| Temp Range | -50 to 150 / 0-50 bar°C |
| Accuracy | ±0.3°C |
Relay Outputs
| Relay Outputs | 2 |
| Relay Rating | 8A/250VAC |
Physical
| Panel Size | 96x96 mm |
| Depth | 90 mm |
| IP Rating | IP54 (front) |
| Weight | 310 g |
Operating Conditions
| Operating Temp | -10 to 55°C |
| Storage Temp | -25 to 65°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| 1-2 | Power 230VAC | Input |
brown/blue
|
| 3-4 | Room Temp NTC | Input |
yellow/white
|
| 5-6 | Suction Temp NTC | Input |
green/white
|
| 7-8 | Suction Press 4-20mA | Input |
red/black
|
| 9-10 | Discharge Press 4-20mA | Input |
orange/black
|
| 11-12 | RS485 | Comm |
orange/yellow
|
| 13-14 | Defrost Relay | Output |
red
|
| 15-16 | Alarm Relay | Output |
gray
|
| 17-18 | EEV 0-10V | Output |
blue/black
|
| 19-20 | VSD Speed 0-10V | Output |
green/black
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SP | Setpoint | -50 to 50 | -18 °C | Temperature setpoint |
| SH | Superheat SP | 2 to 20 | 8 K | Target superheat |
| Kp | EEV P-gain | 0.1 to 10 | 2 | Proportional gain |
| Ki | EEV I-time | 10 to 600 | 120 sec | Integral time |
| Cs | Comp Min Speed | 20 to 60 | 30 % | Minimum VSD speed |
| CM | Comp Max Speed | 60 to 100 | 100 % | Maximum VSD speed |
| Cp | Comp P-gain | 0.1 to 10 | 1.5 | Capacity control P-gain |
Error Codes
Solution: Check NTC probe
Solution: Check suction probe
Solution: Check pressure transducer
Solution: Check pressure transducer
Solution: Check condenser
Solution: Check refrigerant
Solution: Check EEV operation
Frequently Asked Questions
EEV adjusts to maintain target superheat for optimal efficiency and compressor protection
Compressor speed modulates based on cooling demand for energy savings
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Evco
Country: Italy