Full Gauge

TIC-17RGTi

TIC-17 Series • Refrigeration Controller

TIC-17RGTi

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 3
Relay Outputs 4
Communication RS485
Panel Size 32x74 mm

Output Functions

R1 Compressor
R2 Defrost
R3 Fan
R4 Alarm/Aux

Smart controller with touch buttons and real-time clock

Technical Specifications

Display & Interface

Display Type LED
Display Digits 4
Buttons Touch
LED Indicators Compressor, Defrost, Fan, Alarm, Clock

Power Supply

Voltage 115/230V AC
Voltage Range 85-264V AC
Frequency 50/60Hz
Power Consumption 5VA

Sensor Inputs

Probe Inputs 3
Probe Type NTC 10K
Temp Range -50 to 105°C
Accuracy ±0.5°C

Relay Outputs

Relay Outputs 4
Relay Rating 10A/250VAC

Physical

Panel Size 32x74 mm
Depth 70 mm
IP Rating IP65 (front)
Weight 120 g

Operating Conditions

Operating Temp -10 to 50°C
Storage Temp -20 to 60°C

Wiring Terminals

Terminal Function Type Wire Color
L Power L Input
brown
N Power N Input
blue
S1 Probe 1 (Room) Input
red/white
S2 Probe 2 (Evap) Input
red/white
S3 Probe 3 (Cond) Input
red/white
DI1 Digital Input 1 Input
gray
DI2 Digital Input 2 Input
gray
R1 Relay 1 (Comp) Output
black
R2 Relay 2 (Def) Output
orange
R3 Relay 3 (Fan) Output
green
R4 Relay 4 (Alarm) Output
yellow
A+ RS485 A+ Comm
yellow
B- RS485 B- Comm
green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
Set Setpoint -50 to 105 0 °C Temperature setpoint
Hys Hysteresis 0.1 to 30 2 °C Differential
dF Defrost Type 0=Off, 1=Elec, 2=Gas, 3=Smart 3 Defrost method
dt Defrost Duration 0 to 255 30 min Max duration
dT1 Defrost Time 1 00:00-23:59 06:00 HH:MM Scheduled defrost 1
dT2 Defrost Time 2 00:00-23:59 14:00 HH:MM Scheduled defrost 2
dT3 Defrost Time 3 00:00-23:59 22:00 HH:MM Scheduled defrost 3
Sdn Night Setback 0 to 10 2 °C Night mode offset
NS Night Start 00:00-23:59 22:00 HH:MM Night mode start
NE Night End 00:00-23:59 06:00 HH:MM Night mode end
Add Modbus Address 1 to 247 1 Network address

Error Codes

E1 Room probe fault

Solution: Check probe 1

E2 Evap probe fault

Solution: Check probe 2

E3 Condenser probe fault

Solution: Check probe 3

Ebt RTC battery low

Solution: Replace CR2032 battery

Hi High temperature

Solution: Check system

Lo Low temperature

Solution: Check setpoint

Frequently Asked Questions

Alternative Models (Cross Reference)