Full Gauge
TC-900Ri
TC-900 Series • Refrigeration Controller
Quick Info
Type
Refrigeration
Application
Display Case
Probe Inputs
1
Relay Outputs
1
Communication
RS485
Panel Size
28.5x71 mm
Output Functions
R1
Compressor
Basic controller with RS485 Modbus communication for centralized monitoring
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 3 |
| Buttons | 3 |
| LED Indicators | Output, Communication |
Power Supply
| Voltage | 115/230V AC |
| Voltage Range | 85-264V AC |
| Frequency | 50/60Hz |
| Power Consumption | 2.5VA |
Sensor Inputs
| Probe Inputs | 1 |
| Probe Type | NTC 10K |
| Temp Range | -50 to 105°C |
| Accuracy | ±0.5°C |
Relay Outputs
| Relay Outputs | 1 |
| Relay Rating | 10A/250VAC |
Physical
| Panel Size | 28.5x71 mm |
| Depth | 51 mm |
| IP Rating | IP65 (front) |
| Weight | 70 g |
Operating Conditions
| Operating Temp | -10 to 50°C |
| Storage Temp | -20 to 60°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| S1 | Sensor + | Input |
red
|
| S2 | Sensor - | Input |
white
|
| NO | Relay NO | Output |
black
|
| C | Relay COM | Output |
black
|
| A+ | RS485 A+ | Comm |
yellow
|
| B- | RS485 B- | Comm |
green
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| Set | Setpoint | -50 to 105 | 5 °C | Temperature setpoint |
| Hys | Hysteresis | 0.1 to 30 | 2 °C | Switching differential |
| Ls | Low Limit | -50 to Set | -40 °C | Minimum setpoint |
| Us | High Limit | Set to 105 | 99 °C | Maximum setpoint |
| Ofs | Offset | -10 to 10 | 0 °C | Probe calibration |
| Cd | Comp Delay | 0 to 30 | 0 min | Compressor restart delay |
| Add | Modbus Address | 1 to 247 | 1 | Network address |
| bAu | Baud Rate | 0=9600, 1=19200 | 0 | Communication speed |
Error Codes
E1
Sensor open
Solution: Check sensor wiring
E2
Sensor short
Solution: Replace sensor
EC
Communication error
Solution: Check RS485 wiring
Frequently Asked Questions
Access parameters, find Add parameter and set unique address 1-247
Up to 32 devices on single RS485 bus
Alternative Models (Cross Reference)
Eliwell EWCM 4180
Dixell XR20CX RS485
Manufacturer Information
Brand: Full Gauge
Country: Brazil