Full Gauge

TC-940Ri

TC-940 Series • Refrigeration Controller

TC-940Ri

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 2
Relay Outputs 3
Communication RS485 (optional)
Panel Size 32x74 mm

Output Functions

R1 Compressor
R2 Defrost
R3 Fan

Refrigeration controller with defrost management

Technical Specifications

Display & Interface

Display Type LED
Display Digits 3
Buttons 4
LED Indicators Compressor, Defrost, Fan, Alarm

Power Supply

Voltage 115/230V AC
Voltage Range 85-264V AC
Frequency 50/60Hz
Power Consumption 4VA

Sensor Inputs

Probe Inputs 2
Probe Type NTC 10K
Temp Range -50 to 105°C
Accuracy ±0.5°C

Relay Outputs

Relay Outputs 3
Relay Rating 10A/250VAC

Physical

Panel Size 32x74 mm
Depth 59 mm
IP Rating IP65 (front)
Weight 95 g

Operating Conditions

Operating Temp -10 to 50°C
Storage Temp -20 to 60°C

Wiring Terminals

Terminal Function Type Wire Color
L Power L Input
brown
N Power N Input
blue
S1+ Probe 1 + Input
red
S1- Probe 1 - Input
white
S2+ Probe 2 + Input
red
S2- Probe 2 - Input
white
DI Digital Input Input
gray
GND DI Common Input
gray
R1 Relay 1 (Comp) Output
black
C1 Relay 1 COM Output
black
R2 Relay 2 (Def) Output
orange
C2 Relay 2 COM Output
orange
R3 Relay 3 (Fan) Output
green
C3 Relay 3 COM Output
green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
Set Setpoint -50 to 105 0 °C Temperature setpoint
Hys Hysteresis 0.1 to 30 2 °C Differential
Ls Low Limit -50 to Set -30 °C Min setpoint
Us High Limit Set to 105 50 °C Max setpoint
Of1 Probe 1 Offset -10 to 10 0 °C Room probe cal
Of2 Probe 2 Offset -10 to 10 0 °C Evap probe cal
Cd Comp Delay 0 to 30 0 min Startup delay
Co Min Off Time 0 to 30 3 min Minimum off
dF Defrost Type 0=Off, 1=Elec, 2=Gas 1 Defrost method
dt Defrost Duration 0 to 255 30 min Max duration
dI Defrost Interval 0 to 24 8 hr Time between
St Defrost End Temp 0 to 50 8 °C Termination temp
dd Drip Time 0 to 30 2 min Drain time
Fd Fan Delay 0 to 30 0 min Fan restart delay
Fc Fan Cutout 0=No, 1=Yes 1 Stop fan in defrost
AL Low Alarm -50 to Set -10 °C Low alarm setpoint
AH High Alarm Set to 105 15 °C High alarm setpoint
Ad Alarm Delay 0 to 255 60 min Alarm delay

Error Codes

E1 Room probe fault

Solution: Check probe 1

E2 Evap probe fault

Solution: Check probe 2

Hi High temperature

Solution: Check system

Lo Low temperature

Solution: Check setpoint

dF Defrost active

Solution: Normal operation

Frequently Asked Questions

Alternative Models (Cross Reference)

Eliwell EW Plus 974 Dixell XR60CX Danfoss EKC 202

Manufacturer Information

Brand: Full Gauge

Country: Brazil

Visit Manufacturer Website