Full Gauge

TC-941Ri Plus

TC-940 Series • Refrigeration Controller

TC-941Ri Plus

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 3
Relay Outputs 4
Communication RS485
Panel Size 32x74 mm

Output Functions

R1 Compressor
R2 Defrost
R3 Fan
R4 Auxiliary/Alarm

Advanced cold room controller with 4 relay outputs and buzzer

Technical Specifications

Display & Interface

Display Type LED
Display Digits 3
Buttons 4
LED Indicators Compressor, Defrost, Fan, Aux, Alarm

Power Supply

Voltage 115/230V AC
Voltage Range 85-264V AC
Frequency 50/60Hz
Power Consumption 5VA

Sensor Inputs

Probe Inputs 3
Probe Type NTC 10K
Temp Range -50 to 105°C
Accuracy ±0.5°C

Relay Outputs

Relay Outputs 4
Relay Rating 10A/250VAC

Physical

Panel Size 32x74 mm
Depth 65 mm
IP Rating IP65 (front)
Weight 110 g

Operating Conditions

Operating Temp -10 to 50°C
Storage Temp -20 to 60°C

Wiring Terminals

Terminal Function Type Wire Color
L Power L Input
brown
N Power N Input
blue
S1 Probe 1 (Room) Input
red/white
S2 Probe 2 (Evap) Input
red/white
S3 Probe 3 (Aux) Input
red/white
R1 Relay 1 (Comp) Output
black
R2 Relay 2 (Def) Output
orange
R3 Relay 3 (Fan) Output
green
R4 Relay 4 (Aux) Output
yellow
A+ RS485 A+ Comm
yellow
B- RS485 B- Comm
green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
Set Setpoint -50 to 105 0 °C Temperature setpoint
Hys Hysteresis 0.1 to 30 2 °C Differential
Of1 Probe 1 Offset -10 to 10 0 °C Room probe cal
Of2 Probe 2 Offset -10 to 10 0 °C Evap probe cal
Of3 Probe 3 Offset -10 to 10 0 °C Aux probe cal
dF Defrost Type 0=Off, 1=Elec, 2=Gas 1 Defrost method
dt Defrost Duration 0 to 255 30 min Max duration
dI Defrost Interval 0 to 24 8 hr Time between
St Defrost End Temp 0 to 50 8 °C Termination temp
O4F Output 4 Function 0=Aux, 1=Alarm, 2=Light 1 Relay 4 mode
Add Modbus Address 1 to 247 1 Network address

Error Codes

E1 Room probe fault

Solution: Check probe 1

E2 Evap probe fault

Solution: Check probe 2

E3 Aux probe fault

Solution: Check probe 3

Hi High temperature

Solution: Check system

Lo Low temperature

Solution: Check setpoint

Frequently Asked Questions

Alternative Models (Cross Reference)

Eliwell ID Next 978 Dixell XR70CX Danfoss EKC 204A1

Manufacturer Information

Brand: Full Gauge

Country: Brazil

Visit Manufacturer Website