Full Gauge
TC-900Ri clock
TC Series • Refrigeration Controller
Quick Info
Type
Refrigeration
Application
Display Case
Probe Inputs
1
Relay Outputs
1
Communication
RS485 Modbus RTU
Panel Size
34x76 mm
Output Functions
R1
Compressor
Single relay with RS485 and real-time clock for scheduled defrost
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 3 |
| Buttons | 4 |
| LED Indicators | Compressor, Clock |
Power Supply
| Voltage | 115-230V AC |
| Voltage Range | 90-264V AC |
| Frequency | 50/60Hz |
| Power Consumption | 3VA |
Sensor Inputs
| Probe Inputs | 1 |
| Probe Type | NTC 10K |
| Temp Range | -50 to 105°C |
| Accuracy | ±0.5°C |
Relay Outputs
| Relay Outputs | 1 |
| Relay Rating | 16A/250VAC |
Physical
| Panel Size | 34x76 mm |
| Depth | 68 mm |
| IP Rating | IP65 (front) |
| Weight | 85 g |
Operating Conditions
| Operating Temp | -10 to 50°C |
| Storage Temp | -20 to 60°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| S | NTC Probe | Input |
red/white
|
| NO | Relay NO | Output |
black
|
| C | Relay COM | Output |
black
|
| NC | Relay NC | Output |
black
|
| A | RS485 A+ | Comm |
yellow
|
| B | RS485 B- | Comm |
green
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| Set | Setpoint | -50 to 105 | 5 °C | Temperature setpoint |
| Hys | Hysteresis | 0.1 to 30 | 2 °C | Differential |
| Ofs | Probe Offset | -10 to 10 | 0 °C | Calibration |
| Out | Output Mode | 0=Cool, 1=Heat | 0 | Control action |
| Odr | Comp Delay | 0 to 10 | 3 min | Restart delay |
| dt1 | Defrost Time 1 | 00:00 to 23:59 | 06:00 | First defrost |
| dt2 | Defrost Time 2 | 00:00 to 23:59 | 14:00 | Second defrost |
| dt3 | Defrost Time 3 | 00:00 to 23:59 | 22:00 | Third defrost |
| Add | RS485 Address | 1 to 247 | 1 | Modbus address |
Error Codes
E1
Probe fault
Solution: Check NTC probe
Err
Clock error
Solution: Reset time and date
Frequently Asked Questions
Clock version has RTC for scheduled defrost times
Yes, internal backup battery maintains time
Alternative Models (Cross Reference)
TC-900Ri
Eliwell EW Plus 902
Dixell XR02CX
Manufacturer Information
Brand: Full Gauge
Country: Brazil