Full Gauge
Plus II 4150
Plus II Series • Refrigeration Controller
Quick Info
Type
Refrigeration
Application
Display Case
Probe Inputs
1
Relay Outputs
2
Panel Size
28.5x71 mm
Output Functions
R1
Stage 1
R2
Stage 2
Economy dual-stage controller for basic applications
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 3 |
| Buttons | 3 |
| LED Indicators | Output 1, Output 2 |
Power Supply
| Voltage | 115/230V AC |
| Voltage Range | 85-264V AC |
| Frequency | 50/60Hz |
| Power Consumption | 3VA |
Sensor Inputs
| Probe Inputs | 1 |
| Probe Type | NTC 10K |
| Temp Range | -50 to 105°C |
| Accuracy | ±0.5°C |
Relay Outputs
| Relay Outputs | 2 |
| Relay Rating | 10A/250VAC |
Physical
| Panel Size | 28.5x71 mm |
| Depth | 51 mm |
| IP Rating | IP65 (front) |
| Weight | 70 g |
Operating Conditions
| Operating Temp | -10 to 50°C |
| Storage Temp | -20 to 60°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| S1 | Sensor + | Input |
red
|
| S2 | Sensor - | Input |
white
|
| R1 | Relay 1 NO | Output |
black
|
| C1 | Relay 1 COM | Output |
black
|
| R2 | Relay 2 NO | Output |
orange
|
| C2 | Relay 2 COM | Output |
orange
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SP1 | Setpoint 1 | -50 to 105 | 5 °C | Stage 1 setpoint |
| Hy1 | Hysteresis 1 | 0.1 to 30 | 2 °C | Stage 1 differential |
| SP2 | Setpoint 2 | -50 to 105 | 10 °C | Stage 2 setpoint |
| Hy2 | Hysteresis 2 | 0.1 to 30 | 2 °C | Stage 2 differential |
| Ofs | Offset | -10 to 10 | 0 °C | Probe calibration |
| Cd | Comp Delay | 0 to 30 | 3 min | Minimum off time |
| Hc1 | Mode 1 | 0=Cool, 1=Heat | 0 | Stage 1 mode |
| Hc2 | Mode 2 | 0=Cool, 1=Heat | 0 | Stage 2 mode |
Error Codes
E1
Sensor open
Solution: Check sensor wiring
E2
Sensor short
Solution: Replace sensor
Frequently Asked Questions
Two independent relays with separate setpoints for staged cooling/heating
Yes, each output has its own setpoint and differential
Alternative Models (Cross Reference)
Dixell XR10CX
Carel PJEZS
Manufacturer Information
Brand: Full Gauge
Country: Brazil