PENTA III
PENTA Series • Refrigeration Controller
Quick Info
Output Functions
Five-output controller for complex refrigeration systems
Technical Specifications
Display & Interface
| Display Type | LCD |
| Display Digits | 4 |
| Buttons | 6 |
| LED Indicators | Comp, Def, Fan, Aux1, Aux2, Alarm |
Power Supply
| Voltage | 115-230V AC |
| Voltage Range | 90-264V AC |
| Frequency | 50/60Hz |
| Power Consumption | 8VA |
Sensor Inputs
| Probe Inputs | 4 |
| Probe Type | NTC 10K / PT100 / 4-20mA |
| Temp Range | -50 to 200°C |
| Accuracy | ±0.2°C |
Relay Outputs
| Relay Outputs | 5 |
| Relay Rating | 16A/250VAC (x2), 8A (x3) |
Physical
| Panel Size | 96x48 mm |
| Depth | 90 mm |
| IP Rating | IP65 (front) |
| Weight | 220 g |
Operating Conditions
| Operating Temp | -10 to 50°C |
| Storage Temp | -20 to 60°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| S1 | Room Probe | Input |
red/white
|
| S2 | Evap Probe | Input |
red/white
|
| S3 | Cond Probe | Input |
red/white
|
| S4 | Aux Probe | Input |
red/white
|
| DI1 | Door Switch | Input |
gray
|
| DI2 | HP/LP Switch | Input |
gray
|
| R1 | Compressor | Output |
black
|
| R2 | Defrost | Output |
orange
|
| R3 | Fan | Output |
green
|
| R4 | Aux 1 | Output |
white
|
| R5 | Aux 2 | Output |
yellow
|
| A/B | RS485 | Comm |
yellow/green
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| Set | Setpoint | -50 to 200 | -20 °C | Temperature setpoint |
| Hys | Hysteresis | 0.1 to 30 | 2 °C | Differential |
| Pb | Probe Type | 0=NTC, 1=PT100, 2=4-20mA | 0 | Sensor type |
| dF | Defrost Type | 0-4 | 1 | 0=Off, 1=Elec, 2=Gas, 3=Hot gas, 4=Scheduled |
| dt | Defrost Duration | 0 to 180 | 60 min | Max duration |
| dI | Defrost Interval | 0 to 48 | 6 hr | Time between |
| St | Defrost End Temp | 0 to 50 | 12 °C | Termination temp |
| Ax1 | Aux 1 Function | 0-6 | 0 | 0=Alarm, 1=Light, 2=2nd comp, 3=Heater, 4=Pump, 5=Solenoid, 6=Spare |
| Ax2 | Aux 2 Function | 0-6 | 1 | Aux 2 assignment |
| HAL | High Alarm | Set to 200 | -5 °C | High temp alarm |
| LAL | Low Alarm | -50 to Set | -35 °C | Low temp alarm |
Error Codes
Solution: Check S1
Solution: Check S2
Solution: Check S3
Solution: Check S4
Solution: Check refrigeration
Solution: Check setpoint
Solution: Check DI2 input
Solution: Close door
Frequently Asked Questions
Five relays with configurable aux functions
Yes, set Pb=1 for 3-wire PT100
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Full Gauge
Country: Brazil