Full Gauge

MT-543Ri Plus

MT Series • Refrigeration Controller

MT-543Ri Plus

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 3
Relay Outputs 5
Communication RS485 Modbus RTU
Panel Size 75x33 mm

Output Functions

R1 Compressor
R2 Defrost
R3 Fan
R4 Auxiliary
R5 Alarm

Three probe controller with auxiliary output and RS485

Technical Specifications

Display & Interface

Display Type LED
Display Digits 4
Buttons 5
LED Indicators Comp, Defrost, Fan, Aux, Alarm

Power Supply

Voltage 115-230V AC
Voltage Range 90-264V AC
Frequency 50/60Hz
Power Consumption 5VA

Sensor Inputs

Probe Inputs 3
Probe Type NTC 10K
Temp Range -50 to 105°C
Accuracy ±0.3°C

Relay Outputs

Relay Outputs 5
Relay Rating 16A/250VAC (comp), 8A (others)

Physical

Panel Size 75x33 mm
Depth 77 mm
IP Rating IP65 (front)
Weight 135 g

Operating Conditions

Operating Temp -10 to 50°C
Storage Temp -20 to 60°C

Wiring Terminals

Terminal Function Type Wire Color
L Power L Input
brown
N Power N Input
blue
S1 Probe 1 (Room) Input
red/white
S2 Probe 2 (Evap) Input
red/white
S3 Probe 3 (Aux) Input
red/white
DI Door Switch Input
gray
R1 Compressor Output
black
R2 Defrost Output
orange
R3 Fan Output
green
R4 Auxiliary Output
white
R5 Alarm Output
red
A/B RS485 Comm
yellow/green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
Set Setpoint -50 to 105 -20 °C Temperature setpoint
Hys Hysteresis 0.1 to 30 2 °C Differential
Of1 Probe 1 Offset -10 to 10 0 °C Room probe cal
Of2 Probe 2 Offset -10 to 10 0 °C Evap probe cal
Of3 Probe 3 Offset -10 to 10 0 °C Aux probe cal
dF Defrost Type 0=Off, 1=Elec, 2=Gas 1 Defrost method
dt Defrost Duration 0 to 99 45 min Max duration
dI Defrost Interval 0 to 48 6 hr Time between
St Defrost End Temp 0 to 30 10 °C Termination temp
Aux Aux Function 0-4 0 0=Light, 1=Heater, 2=2nd comp, 3=Alarm, 4=Door
Add RS485 Address 1 to 247 1 Modbus address

Error Codes

E1 Room probe fault

Solution: Check probe 1

E2 Evap probe fault

Solution: Check probe 2

E3 Aux probe fault

Solution: Check probe 3

Hi High temp alarm

Solution: Check refrigeration

Lo Low temp alarm

Solution: Check setpoint

Frequently Asked Questions

Alternative Models (Cross Reference)

MT-530Ri Eliwell ID Plus 974 Dixell XR60CX

Manufacturer Information

Brand: Full Gauge

Country: Brazil

Visit Manufacturer Website