MT-530Ri
MT-530 Series • Refrigeration Controller
Quick Info
Output Functions
Professional cold room controller with RS485 Modbus communication
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 3 |
| Buttons | 4 |
| LED Indicators | Compressor, Defrost, Fan, Alarm, Comm |
Power Supply
| Voltage | 115/230V AC |
| Voltage Range | 85-264V AC |
| Frequency | 50/60Hz |
| Power Consumption | 4.5VA |
Sensor Inputs
| Probe Inputs | 2 |
| Probe Type | NTC 10K |
| Temp Range | -50 to 105°C |
| Accuracy | ±0.5°C |
Relay Outputs
| Relay Outputs | 3 |
| Relay Rating | 10A/250VAC |
Physical
| Panel Size | 32x74 mm |
| Depth | 65 mm |
| IP Rating | IP65 (front) |
| Weight | 105 g |
Operating Conditions
| Operating Temp | -10 to 50°C |
| Storage Temp | -20 to 60°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| S1 | Probe 1 (Room) | Input |
red/white
|
| S2 | Probe 2 (Evap) | Input |
red/white
|
| DI1 | Digital Input 1 | Input |
gray
|
| DI2 | Digital Input 2 | Input |
gray
|
| GND | DI Common | Input |
gray
|
| R1 | Relay 1 (Comp) | Output |
black
|
| R2 | Relay 2 (Def) | Output |
orange
|
| R3 | Relay 3 (Fan) | Output |
green
|
| A+ | RS485 A+ | Comm |
yellow
|
| B- | RS485 B- | Comm |
green
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| Set | Setpoint | -50 to 105 | 0 °C | Temperature setpoint |
| Hys | Hysteresis | 0.1 to 30 | 2 °C | Differential |
| dF | Defrost Type | 0=Off, 1=Elec, 2=Gas | 1 | Defrost method |
| dt | Defrost Duration | 0 to 255 | 30 min | Max duration |
| dI | Defrost Interval | 0 to 24 | 8 hr | Time between |
| DI1 | DI1 Function | 0=Off, 1=Door, 2=Alarm | 1 | Digital input 1 |
| DI2 | DI2 Function | 0=Off, 1=Defrost, 2=Alarm | 1 | Digital input 2 |
| Add | Modbus Address | 1 to 247 | 1 | Network address |
| bAu | Baud Rate | 0=9600, 1=19200 | 0 | Communication speed |
Error Codes
Solution: Check probe 1
Solution: Check probe 2
Solution: Check RS485 wiring
Solution: Close cold room door
Frequently Asked Questions
Yes, set DI2=1, closing contact starts defrost cycle
Use RS485 A+/B- terminals with Modbus RTU protocol
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Full Gauge
Country: Brazil