XH260L
XH Series • HVAC Controller
Quick Info
Output Functions
Fan coil unit controller with heating/cooling and fan speed control
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 3 |
| Buttons | 4 |
| LED Indicators | Heat, Cool, Fan Lo, Fan Med, Fan Hi |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 100-240V AC |
| Frequency | 50/60Hz |
| Power Consumption | 5VA |
Sensor Inputs
| Probe Inputs | 2 |
| Probe Type | NTC |
| Temp Range | -20 to 60°C |
| Accuracy | ±0.5°C |
Relay Outputs
| Relay Outputs | 5 |
| Relay Rating | 5A/250VAC |
Physical
| Panel Size | 71x29 mm |
| Depth | 60 mm |
| IP Rating | IP40 |
| Weight | 120 g |
Operating Conditions
| Operating Temp | 0 to 50°C |
| Storage Temp | -20 to 60°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| Pb1 | Room Probe | Input |
red/white
|
| Pb2 | Supply Air Probe | Input |
red/white
|
| DI | Window Contact | Input |
gray
|
| Y1 | Heat Valve | Output |
red
|
| Y2 | Cool Valve | Output |
blue
|
| G1 | Fan Low | Output |
green
|
| G2 | Fan Medium | Output |
green
|
| G3 | Fan High | Output |
green
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SEt | Setpoint | 10 to 35 | 22 °C | Room setpoint |
| Hy | Deadband | 0.5 to 5 | 1 °C | Neutral zone |
| LS | Low Limit | 5 to SET | 16 °C | Min setpoint |
| US | High Limit | SET to 40 | 28 °C | Max setpoint |
| Fn | Fan Mode | 0=Auto, 1=Manual | 0 | Fan control mode |
| FS | Fan Speed | 1=Lo, 2=Med, 3=Hi | 2 | Manual fan speed |
| Md | Operating Mode | 0=Off, 1=Heat, 2=Cool, 3=Auto | 3 | System mode |
| CHg | Changeover | 0=Manual, 1=Auto | 1 | Heat/cool switching |
Error Codes
Solution: Check room probe
Solution: Check supply air probe
Solution: Close window to resume
Frequently Asked Questions
Set Fn=1 for manual, then use FS to select speed
Hy sets the neutral zone where neither heating nor cooling operates
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Dixell
Country: Italy
Parent: Emerson Climate Technologies