EKC 319A
EKC Series • Refrigeration Controller
Quick Info
Output Functions
Multi-output controller with RS485 Modbus communication
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 3 |
| Buttons | 5 |
| LED Indicators | Comp, Defrost, Fan, Alarm |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 100-240V AC |
| Frequency | 50/60Hz |
| Power Consumption | 5VA |
Sensor Inputs
| Probe Inputs | 2 |
| Probe Type | NTC / PTC / PT1000 |
| Temp Range | -50 to 150°C |
| Accuracy | ±0.3°C |
Relay Outputs
| Relay Outputs | 4 |
| Relay Rating | 12A/250VAC (comp), 8A (others) |
Physical
| Panel Size | 72x72 mm |
| Depth | 65 mm |
| IP Rating | IP65 (front) |
| Weight | 150 g |
Operating Conditions
| Operating Temp | -10 to 55°C |
| Storage Temp | -25 to 70°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| S1+/S1- | Air Probe | Input |
red/white
|
| S2+/S2- | Evap Probe | Input |
red/white
|
| DI | Door Switch | Input |
gray
|
| K1 | Compressor | Output |
black
|
| K2 | Defrost | Output |
black
|
| K3 | Fan | Output |
black
|
| K4 | Alarm | Output |
red
|
| A/B | RS485 | Comm |
yellow/green
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| r01 | Setpoint | -50 to 150 | -20 °C | Temperature setpoint |
| r02 | Differential | 0.1 to 20 | 2 °C | Switching band |
| d01 | Defrost Type | 0-3 | 1 | 0=Off, 1=Electric, 2=Gas, 3=Off-cycle |
| d02 | Defrost Interval | 0 to 48 | 6 h | Hours between defrosts |
| d03 | Defrost Time | 1 to 180 | 45 min | Max defrost duration |
| d04 | Defrost Stop Temp | -50 to 50 | 10 °C | End defrost temp |
| F01 | Fan Mode | 0-3 | 1 | 0=Off, 1=On, 2=With comp, 3=Cont w/defrost stop |
| F04 | Fan Delay | 0 to 30 | 2 min | Restart delay after defrost |
| c01 | Modbus Address | 1 to 247 | 1 | RS485 address |
| c02 | Baud Rate | 0-4 | 2 | 0=1200, 1=2400, 2=9600, 3=19200, 4=38400 |
Error Codes
Solution: Check S1 wiring
Solution: Check S2 wiring
Solution: Check system
Solution: Check setpoint
Solution: Check heater
Frequently Asked Questions
Use RS485 Modbus RTU, address via c01
Yes, configure probe type in o02
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Danfoss
Country: Denmark