Danfoss

EKC 302

EKC Series • Refrigeration Controller

EKC 302

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 3
Relay Outputs 5
Communication RS485 Modbus
Panel Size 71.5x28.5 mm

Output Functions

R1 Compressor 1
R2 Compressor 2
R3 Defrost
R4 Fan
R5 Alarm

Advanced controller for multiple evaporator systems

Technical Specifications

Display & Interface

Display Type LED
Display Digits 4
Buttons 4
LED Indicators Comp 1, Comp 2, Defrost, Fan, Alarm

Power Supply

Voltage 230V AC
Voltage Range 100-240V AC
Frequency 50/60Hz
Power Consumption 6VA

Sensor Inputs

Probe Inputs 3
Probe Type NTC/PTC/PT1000
Temp Range -60 to 150°C
Accuracy ±0.3°C

Relay Outputs

Relay Outputs 5
Relay Rating 8A/250VAC

Physical

Panel Size 71.5x28.5 mm
Depth 65 mm
IP Rating IP65 (front)
Weight 140 g

Operating Conditions

Operating Temp -25 to 55°C
Storage Temp -40 to 70°C

Wiring Terminals

Terminal Function Type Wire Color
L Power L Input
brown
N Power N Input
blue
S1 Room Sensor Input
red/white
S2 Evap Sensor Input
red/white
S3 Aux Sensor Input
red/white
DI1 Digital Input 1 Input
gray
DI2 Digital Input 2 Input
gray
K1 Relay 1 (Comp 1) Output
black
K2 Relay 2 (Comp 2) Output
black
K3 Relay 3 (Defrost) Output
orange
K4 Relay 4 (Fan) Output
green
K5 Relay 5 (Alarm) Output
red
A RS485 A Comm
blue
B RS485 B Comm
yellow

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
r01 Setpoint -60 to 150 0 °C Main setpoint
r02 Differential 0.1 to 20 2 °C Stage 1 diff
r03 Stage 2 Diff 0.1 to 20 4 °C Stage 2 differential
c01 Comp Delay 0 to 30 0 min Startup delay
c02 Min Off 0 to 30 3 min Minimum off time
c03 Stage Delay 0 to 30 5 min Delay between stages
c04 Rotation 0=No, 1=Yes 1 Compressor rotation
d01 Defrost Type 0-3 1 Defrost method
d02 Defrost End 0 to 25 8 °C Termination temp
d03 Max Defrost 0 to 180 30 min Maximum duration
d04 Defrost Interval 0 to 48 8 hr Time between

Error Codes

E1 Room sensor fault

Solution: Check S1 sensor

E2 Evap sensor fault

Solution: Check S2 sensor

E3 Aux sensor fault

Solution: Check S3 sensor

AL Temperature alarm

Solution: Check system

HP High pressure

Solution: Check condenser

LP Low pressure

Solution: Check charge

Frequently Asked Questions

Alternative Models (Cross Reference)

Eliwell EWDR 984 Dixell XC660D

Manufacturer Information

Brand: Danfoss

Country: Denmark

Visit Manufacturer Website