Danfoss

AK-CC 350A

AK-CC Series • Refrigeration Controller

AK-CC 350A

Quick Info

Type Refrigeration
Application Condensing Unit
Probe Inputs 3
Relay Outputs 5
Communication RS485 Modbus
Panel Size 96x96 mm

Output Functions

R1 Compressor
R2 Fan 1
R3 Fan 2
R4 Crankcase Heater
R5 Alarm

Controller for outdoor condensing units

Technical Specifications

Display & Interface

Display Type LCD
Display Digits 4
Buttons 4
LED Indicators Comp, Fan, Crankcase, Alarm

Power Supply

Voltage 230V AC
Voltage Range 100-240V AC
Frequency 50/60Hz
Power Consumption 8VA

Sensor Inputs

Probe Inputs 3
Probe Type NTC/PT1000/Pressure
Temp Range -60 to 150°C
Accuracy ±0.3°C

Relay Outputs

Relay Outputs 5
Relay Rating 16A/250VAC (K1), 8A/250VAC (K2-K5)

Physical

Panel Size 96x96 mm
Depth 70 mm
IP Rating IP65 (front)
Weight 280 g

Operating Conditions

Operating Temp -40 to 60°C
Storage Temp -50 to 80°C

Wiring Terminals

Terminal Function Type Wire Color
L Power L Input
brown
N Power N Input
blue
PE Earth Input
green/yellow
Po Suction Pressure Input
red/blue
Pc Discharge Pressure Input
red/blue
S1 Ambient Temp Input
red/white
K1 Compressor Output
black
K2 Fan 1 Output
green
K3 Fan 2 Output
green
K4 Crankcase Output
orange
K5 Alarm Output
red
AO 0-10V Fan Speed Output
yellow

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
r01 Pc Setpoint 5 to 35 18 bar Condensing pressure setpoint
r02 Differential 0 to 5 2 bar Fan switching differential
r10 LP Cutout 0 to 10 1 bar Low pressure cutout
r11 HP Cutout 15 to 40 28 bar High pressure cutout
c01 Comp Min Off 0 to 30 3 min Minimum off time
c02 Crankcase Time 0 to 240 30 min Crankcase preheat time
F01 Fan Mode 0=Continuous, 1=Modulated 1 Fan control mode
F02 Fan Min Speed 0 to 100 30 % Minimum fan speed

Error Codes

E1 Ambient sensor fault

Solution: Check S1 sensor

E5 Po sensor fault

Solution: Check suction pressure sensor

E6 Pc sensor fault

Solution: Check discharge pressure sensor

HP High pressure cutout

Solution: Check condenser and clean coils

LP Low pressure cutout

Solution: Check charge and for leaks

OL Compressor overload

Solution: Check motor and electrical

Frequently Asked Questions

Alternative Models (Cross Reference)

Bitzer OLC Pack Copeland E2 CU

Manufacturer Information

Brand: Danfoss

Country: Denmark

Visit Manufacturer Website