IR33W7HR20
IR33+ Series • Refrigeration Controller
Quick Info
Output Functions
Advanced universal controller with extended features and connectivity
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 4 |
| Buttons | 4 |
| LED Indicators | Compressor, Defrost, Fan, Alarm, Aux |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 115-230V AC |
| Frequency | 50/60Hz |
| Power Consumption | 6VA |
Sensor Inputs
| Probe Inputs | 4 |
| Probe Type | NTC / PT1000 |
| Temp Range | -50 to 150°C |
| Accuracy | ±0.3°C |
Relay Outputs
| Relay Outputs | 4 |
| Relay Rating | 8A/250VAC |
Physical
| Panel Size | 71x29 mm |
| Depth | 65 mm |
| IP Rating | IP65 (front) |
| Weight | 130 g |
Operating Conditions
| Operating Temp | -10 to 60°C |
| Storage Temp | -20 to 70°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| B1 | Probe 1 (Room) | Input |
red/white
|
| B2 | Probe 2 (Evap) | Input |
red/white
|
| B3 | Probe 3 (Discharge) | Input |
red/white
|
| B4 | Probe 4 (Aux) | Input |
red/white
|
| DI1 | Digital Input 1 | Input |
gray
|
| DI2 | Digital Input 2 | Input |
gray
|
| NO1 | Relay 1 (Comp) | Output |
black
|
| NO2 | Relay 2 (Def) | Output |
orange
|
| NO3 | Relay 3 (Fan) | Output |
green
|
| NO4 | Relay 4 (Aux) | Output |
yellow
|
| A | RS485 A (+) | Comm |
blue
|
| B | RS485 B (-) | Comm |
yellow
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| St | Setpoint | -50 to 150 | 5 °C | Main setpoint |
| S2 | Night Setpoint | -50 to 150 | 3 °C | Energy saving setpoint |
| rd | Differential | 0.1 to 20 | 2 °C | Control differential |
| c4 | Comp ON Delay | 0 to 255 | 0 min | Startup delay |
| c5 | Min Comp OFF | 0 to 255 | 3 min | Minimum off |
| d0 | Defrost Type | 0-3 | 1 | Defrost method |
| d1 | Defrost End | 0 to 50 | 8 °C | Termination temp |
| d2 | Max Defrost | 1 to 255 | 30 min | Maximum duration |
| d3 | Defrost Interval | 0 to 48 | 8 hr | Time between |
| Ad | Modbus Address | 1 to 247 | 1 | Device address |
Error Codes
Solution: Check B1 probe
Solution: Check B2 probe
Solution: Check B3 probe
Solution: Check B4 probe
Solution: Check refrigeration system
Solution: Check setpoint/defrost
Solution: Normal operation
Frequently Asked Questions
HACCP is always active. Use /Hc menu to view logged events
Set Ad for address, bA for baud rate in communication menu
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Carel
Country: Italy