Carel

IR33S0ER00

IR33 Series • Refrigeration Controller

IR33S0ER00

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 2
Relay Outputs 3
Communication RS485 (optional)
Panel Size 32x74 mm

Output Functions

R1 Compressor
R2 Defrost
R3 Fan

Universal controller for static and ventilated refrigeration units

Technical Specifications

Display & Interface

Display Type LED
Display Digits 3
Buttons 4
LED Indicators Compressor, Defrost, Fan, Alarm

Power Supply

Voltage 230V AC
Voltage Range 115-230V AC
Frequency 50/60Hz
Power Consumption 5VA

Sensor Inputs

Probe Inputs 2
Probe Type NTC
Temp Range -50 to 90°C
Accuracy ±0.5°C

Relay Outputs

Relay Outputs 3
Relay Rating 8A/250VAC (16A inrush)

Physical

Panel Size 32x74 mm
Depth 60 mm
IP Rating IP65 (front)
Weight 100 g

Operating Conditions

Operating Temp -10 to 60°C
Storage Temp -20 to 70°C

Wiring Terminals

Terminal Function Type Wire Color
1 Power L Input
brown
2 Power N Input
blue
5 Probe 1 (Room) Input
red
6 Probe Common Input
white
7 Probe 2 (Defrost) Input
red
10 Digital Input Input
gray
11 DI Common Input
gray
12 Relay 1 NO (Comp) Output
black
13 Relay 1 COM Output
black
14 Relay 2 NO (Defrost) Output
orange
15 Relay 2 COM Output
orange
16 Relay 3 NO (Fan) Output
green
17 Relay 3 COM Output
green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
St Setpoint -50 to 90 5 °C Temperature setpoint
rd Differential 0.1 to 20 2 °C Switching differential
r1 Setpoint Low Limit -50 to St -50 °C Minimum setpoint
r2 Setpoint High Limit St to 90 50 °C Maximum setpoint
c0 Probe 1 Offset -10 to 10 0 °C Room probe calibration
c1 Probe 2 Offset -10 to 10 0 °C Defrost probe calibration
c4 Comp ON Delay 0 to 15 0 min Startup delay
c5 Min Comp OFF 0 to 15 3 min Minimum off time
c6 Min Comp ON 0 to 15 0 min Minimum on time
d0 Defrost Type 0=None, 1=Elec, 2=Gas 1 Defrost heating method
d1 Defrost End Temp 0 to 50 8 °C Termination temperature
d2 Max Defrost Time 1 to 255 30 min Maximum duration
d3 Defrost Interval 0 to 24 8 hr Time between defrosts
d4 Drip Time 0 to 15 2 min Drain time after defrost
d5 Fan Delay 0 to 15 0 min Fan restart delay

Error Codes

E1 Room probe fault

Solution: Check probe 1 wiring, resistance should be ~10kΩ at 25°C

E2 Defrost probe fault

Solution: Check probe 2 wiring

HA High temperature alarm

Solution: Check refrigeration system capacity

LA Low temperature alarm

Solution: Check setpoint and defrost settings

dF Defrost in progress

Solution: Normal operation, wait for completion

dr Drip time in progress

Solution: Normal operation after defrost

Frequently Asked Questions

Alternative Models (Cross Reference)

Eliwell EW Plus 974 Dixell XR60CX Danfoss EKC 202

Manufacturer Information

Brand: Carel

Country: Italy

Visit Manufacturer Website