Type Refrigeration
Application Universal
Probe Inputs 3
Relay Outputs 4
Communication RS485 Modbus / NFC
Panel Size 71x29 mm

Output Functions

R1 Compressor
R2 Defrost
R3 Fan
R4 Alarm/Aux

Enhanced universal refrigeration controller with NFC programming

Technical Specifications

Display & Interface

Display Type LED
Display Digits 4
Buttons 4
LED Indicators Comp, Defrost, Fan, Alarm, NFC

Power Supply

Voltage 230V AC
Voltage Range 100-240V AC
Frequency 50/60Hz
Power Consumption 4VA

Sensor Inputs

Probe Inputs 3
Probe Type NTC 10K / PTC / PT1000
Temp Range -50 to 150°C
Accuracy ±0.3°C

Relay Outputs

Relay Outputs 4
Relay Rating 8A/250VAC (SPDT)

Physical

Panel Size 71x29 mm
Depth 62 mm
IP Rating IP65 (front)
Weight 95 g

Operating Conditions

Operating Temp -10 to 60°C
Storage Temp -25 to 70°C

Wiring Terminals

Terminal Function Type Wire Color
G Earth Input
green/yellow
1 Power L Input
brown
2 Power N Input
blue
B1 Probe 1 (Room) Input
red/white
B2 Probe 2 (Evap) Input
red/white
B3 Probe 3 (Aux) Input
red/white
DI1 Digital Input Input
gray
NO1 Relay 1 (Comp) Output
black
NO2 Relay 2 (Defrost) Output
black
NO3 Relay 3 (Fan) Output
black
NO4 Relay 4 (Aux) Output
black
+/- RS485 Comm
yellow/green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SP Setpoint -50 to 150 5 °C Temperature setpoint
rd Differential 0.1 to 25.5 2 °C Control band
c0 Compressor Delay 0 to 15 3 min Restart delay
c1 Min On Time 0 to 15 0 min Minimum runtime
d0 Defrost Type 0-4 1 0=Off, 1=Electric, 2=Gas, 3=Off-cycle, 4=EEV
d1 Defrost End -50 to 50 8 °C Termination temp
d3 Defrost Interval 0 to 99 8 h Hours between defrosts
d4 Max Defrost 1 to 180 30 min Maximum duration
F0 Fan Mode 0-3 1 0=Off, 1=On, 2=With comp, 3=Continuous
F2 Fan Delay 0 to 15 2 min Post-defrost delay
Pn Probe Type 0-4 0 0=NTC, 1=PTC, 2=PT100, 3=PT500, 4=PT1000

Error Codes

E1 Probe 1 error

Solution: Check room sensor

E2 Probe 2 error

Solution: Check evap sensor

E3 Probe 3 error

Solution: Check aux sensor

Hi High temp alarm

Solution: Check refrigeration

Lo Low temp alarm

Solution: Check setpoint

dEF Defrost timeout

Solution: Check heater

Frequently Asked Questions

Alternative Models (Cross Reference)

IR33S0ER00 Dixell XR30CX Danfoss EKC 202

Manufacturer Information

Brand: Carel

Country: Italy

Visit Manufacturer Website