VRF Piping Design Calculator

Calculate refrigerant pipe sizes and equivalent lengths for VRF/VRV systems

Important: Always Refer to Manufacturer Guidelines

This calculator provides general guidance only. VRF/VRV piping requirements vary by manufacturer (Daikin, Mitsubishi, LG, Samsung, etc.). Always use the specific manufacturer's design software and installation manuals for final design and sizing.

System Configuration

kW

Main Line (ODU to First Branch)

m
m

Branch Configuration

m
m
IDU # Type Capacity (kW) Branch Length (m) Liquid Line Gas Line

Calculation Results

Main Liquid Line
-
OD (mm)
Main Gas Line
-
OD (mm)
Total Equivalent Length
-
m
Additional Charge
-
kg

System Limits Check

Total Pipe Length: -
Max Limit: -
Capacity Ratio: -
Oil Return: -

Branch Selector / Refnet Sizing

VRF Piping Guidelines

Typical Pipe Sizes by Capacity

Capacity Range Liquid Line (OD) Gas Line (OD) Notes
2.2 - 5.6 kWφ6.35 (1/4")φ12.7 (1/2")Single IDU branch
7.1 - 11.2 kWφ9.52 (3/8")φ15.88 (5/8")Medium capacity
14.0 - 22.4 kWφ9.52 (3/8")φ19.05 (3/4")Sub-header
28 - 45 kWφ12.7 (1/2")φ22.2 (7/8")Main header
50 - 84 kWφ15.88 (5/8")φ28.58 (1-1/8")Large system
100+ kWφ19.05 (3/4")φ34.9 (1-3/8")Multiple ODU

Typical System Limits

  • • Max total pipe length: 165-1000m (varies by model)
  • • Max height difference (ODU-IDU): 50-90m
  • • Max height difference (IDU-IDU): 15-30m
  • • Max single pipe run: 120-165m
  • • Equivalent length per elbow: 0.5m
  • • Capacity ratio: 50-130% (typical)

Additional Charge Calculation

  • • φ6.35 (1/4"): 10 g/m
  • • φ9.52 (3/8"): 30 g/m
  • • φ12.7 (1/2"): 60 g/m
  • • φ15.88 (5/8"): 90 g/m
  • • φ19.05 (3/4"): 140 g/m
  • • φ22.2 (7/8"): 200 g/m