Voltage Drop Calculator

Calculate wire size for long electrical runs

Circuit Parameters

Use RLA or full load amps from nameplate

Distance from panel to equipment

Copper Wire Resistance (ohms/1000ft @ 75°C)

AWG mm² Ω/1000ft Ampacity
142.53.1415A
1241.9820A
1061.2430A
8100.77840A
6160.49155A
4250.30870A
2350.19495A
1/0550.122125A

NEC Voltage Drop Guidelines

3% Recommendation (NEC 210.19(A))

Branch circuits should have voltage drop ≤3% for satisfactory equipment operation.

5% Maximum (NEC 215.2(A)(1))

Combined feeder and branch circuit voltage drop should not exceed 5%.

Motor Applications

Motors are sensitive to voltage. Most require ±10% of nameplate voltage. Lower voltage = higher current = overheating.

Important Notes

  • • This calculator assumes resistive load. Motor loads may require additional considerations for power factor.
  • • Always verify wire size meets minimum ampacity requirements (NEC Table 310.16).
  • • Temperature derating may be required for high ambient or bundled conductors.
  • • Consult local electrical codes - they may have additional requirements.
  • • For HVAC equipment, also check MCA (Minimum Circuit Ampacity) on nameplate.