Chilled Water Pump Head Calculator

Calculate pump head and system friction loss

System Configuration

Flow Parameters

°C

Piping System

m

Equipment Pressure Drop

kPa
kPa
kPa
kPa

Static Head (Open Systems Only)

Calculation Results

Total Pump Head
-
kPa (- m H₂O)
Design Flow
-
L/min (- GPM)
Pump Power (Est.)
-
kW (η = 70%)
Pipe Velocity
-
m/s

Head Loss Breakdown

Pipe Friction: -
Fitting Loss: -
Equipment Loss: -
Static Head: -

Pipe Sizing Check

Design Guidelines

Recommended Pipe Velocities

Pipe Size Max Velocity (m/s)
25-50mm (1"-2")1.2 - 1.5
65-100mm (2.5"-4")1.5 - 2.0
125-200mm (5"-8")2.0 - 2.5
250mm+ (10"+)2.5 - 3.0

Typical Equipment Pressure Drop

Equipment Pressure Drop (kPa)
Chiller Evaporator35 - 70
AHU Cooling Coil20 - 50
FCU Coil15 - 35
Strainer (Clean)7 - 15
2-Way Control Valve20 - 50

Design Notes

  • • Add 10-20% safety margin to calculated pump head
  • • For glycol systems, increase head by 10-25% depending on concentration
  • • Consider future expansion when sizing pumps
  • • VFD (Variable Frequency Drive) pumps recommended for variable flow systems
  • • Always verify with actual equipment data sheets