Chilled Water Pump Head Calculator
Calculate pump head and system friction loss
System Configuration
Flow Parameters
°C
Piping System
m
Equipment Pressure Drop
kPa
kPa
kPa
kPa
Static Head (Open Systems Only)
m
Calculation Results
Total Pump Head
-
kPa (- m H₂O)
Design Flow
-
L/min (- GPM)
Pump Power (Est.)
-
kW (η = 70%)
Pipe Velocity
-
m/s
Head Loss Breakdown
Pipe Friction:
-
Fitting Loss:
-
Equipment Loss:
-
Static Head:
-
Pipe Sizing Check
Design Guidelines
Recommended Pipe Velocities
| Pipe Size | Max Velocity (m/s) |
|---|---|
| 25-50mm (1"-2") | 1.2 - 1.5 |
| 65-100mm (2.5"-4") | 1.5 - 2.0 |
| 125-200mm (5"-8") | 2.0 - 2.5 |
| 250mm+ (10"+) | 2.5 - 3.0 |
Typical Equipment Pressure Drop
| Equipment | Pressure Drop (kPa) |
|---|---|
| Chiller Evaporator | 35 - 70 |
| AHU Cooling Coil | 20 - 50 |
| FCU Coil | 15 - 35 |
| Strainer (Clean) | 7 - 15 |
| 2-Way Control Valve | 20 - 50 |
Design Notes
- • Add 10-20% safety margin to calculated pump head
- • For glycol systems, increase head by 10-25% depending on concentration
- • Consider future expansion when sizing pumps
- • VFD (Variable Frequency Drive) pumps recommended for variable flow systems
- • Always verify with actual equipment data sheets