AHU/FCU Selection Calculator

Calculate Air Handling Unit and Fan Coil Unit sizing requirements

Space Requirements

Design Conditions

°C
%
°C
%

AHU Configuration

Calculation Results

Required Airflow
-
m³/h (- CFM)
Coil Capacity
-
kW (Total)
CHW Flow Rate
-
L/min
Fan Power
-
kW

Airflow Analysis

Fresh Air: -
Return Air: -
Supply Air Velocity: -
Air Changes (ACH): -

Coil Specifications

Sensible Heat: -
Latent Heat: -
SHR: -
Coil Face Velocity: -

Equipment Selection

Design Reference

Typical Air Change Rates (ACH)

Space Type ACH
Office6-10
Conference Room10-15
Classroom6-10
Restaurant10-15
Hospital Ward6-12
Clean Room (ISO 7)30-60

Typical Pressure Drops

Component Pressure Drop (Pa)
Pre-filter (G4)50-80
Medium Filter (F7)100-150
HEPA (H13)250-350
Cooling Coil (6-row)150-250
Heat Recovery150-300
Ductwork (typical)200-500

FCU Selection Tips

  • • Select FCU at medium speed for design capacity
  • • High speed provides ~15% more capacity
  • • Consider noise level (NC rating) for space type
  • • 4-way cassette: 600×600mm or 900×900mm ceiling grid
  • • Concealed units need return air path

AHU Selection Tips

  • • Face velocity: 2.0-2.5 m/s (typical)
  • • EC fans offer 30-50% energy savings
  • • Consider maintenance access space
  • • Add 10-15% safety factor to airflow
  • • VFD required for VAV systems