Inverter AC Error Codes

Fault code database for VRF and mini-split systems

Found 214 error codes

Daikin

Japan • 30 error codes

View all Daikin codes →
Code Description Cause Action
A0 External protection device activated External protection relay triggered Check external protection device, reset if safe
A1 Indoor PCB defect Indoor unit control board failure Replace indoor PCB
A3 Drain level abnormal Condensate drain blocked or float switch activated Clean drain line, check float switch
A5 Heat exchanger freeze-up Evaporator coil freezing Check airflow, refrigerant charge, expansion valve
A6 Fan motor abnormal Indoor fan motor locked or abnormal Check fan motor, capacitor, wiring
A7 Swing motor abnormal Louver/swing motor failure Check swing motor and drive circuit
C4 Heat exchanger sensor fault Indoor coil thermistor open/short Check thermistor resistance, replace if out of spec
C9 Room temperature sensor fault Room temperature thermistor failure Check sensor connection and resistance
E0 External protection device Outdoor external protection activated Check external protection circuit
E1 Outdoor PCB fault Outdoor control board failure Replace outdoor PCB
E3 High pressure switch activated High discharge pressure Check condenser, fan, refrigerant charge, ambient
E4 Low pressure switch activated Low suction pressure Check refrigerant charge, expansion valve, airflow
E5 Inverter compressor overload Compressor motor overcurrent Check compressor, power supply, refrigerant
E6 Standard compressor overload Fixed speed compressor overcurrent Check compressor, capacitor, power supply
E7 Fan motor overcurrent Outdoor fan drawing excess current Check fan motor, blade, bearings
E9 Electronic expansion valve fault EEV driver or valve failure Check EEV wiring, driver, replace valve if needed
F3 Discharge pipe temperature high Compressor discharge overheating Check superheat, refrigerant charge, airflow
F6 High pressure abnormal Pressure sensor detecting high pressure Check refrigerant charge, condenser, ambient
H6 Position sensor fault Compressor position sensor failure Check sensor wiring, replace compressor if internal
H8 CT sensor fault Current transformer failure Check CT sensor and wiring
H9 Outdoor air sensor fault Outdoor ambient thermistor failure Check thermistor resistance and connection
J3 Discharge pipe sensor fault Discharge temperature thermistor failure Replace discharge temperature sensor
J6 Heat exchanger sensor fault Outdoor coil thermistor failure Check thermistor, replace if needed
L3 Electrical box temperature high Control box overheating Check ventilation, clean control box
L4 Heat sink temperature high Inverter heat sink overheating Check airflow around outdoor unit
L5 Compressor overcurrent Instantaneous overcurrent trip Check compressor, wiring, voltage
P4 Inverter heat sink sensor fault Heat sink thermistor failure Replace heat sink temperature sensor
U0 Low refrigerant System undercharged Check for leaks, recharge system
U2 Abnormal power supply voltage Low or high voltage detected Check power supply voltage, connections
U4 Communication error Indoor-outdoor communication failure Check communication wiring, connectors

Mitsubishi Electric

Japan • 29 error codes

View all Mitsubishi Electric codes →
Code Description Cause Action
E0 Remote controller signal error Communication issue with remote Check remote controller and receiver
E1 Remote controller PCB error Remote control board fault Replace remote controller
E3 Communication error No communication between units Check wiring between indoor and outdoor
E6 Indoor/outdoor communication error Serial communication failure Check S21/S22 communication lines
E7 Indoor fan motor error Fan motor failure Check fan motor, hall sensor, connections
E9 Indoor/outdoor communication error Communication timeout Check wiring polarity and connections
Eb Indoor PCB error Indoor control board failure Replace indoor PCB
F1 Room thermistor open/short Room temperature sensor fault Check/replace room thermistor
F2 Indoor coil thermistor fault Evaporator sensor open/short Check/replace coil thermistor
P1 Power supply peak detection Input voltage variation Check power supply stability
P2 Current sensor error CT sensor failure Check CT sensor and wiring
P4 Drain sensor error Float switch activated Clean condensate drain
P5 Drain pump error Condensate pump failure Check drain pump operation
P6 Freeze/overheat protection Coil temperature abnormal Check airflow, refrigerant charge
P8 Pipe thermistor error Liquid pipe sensor fault Check pipe thermistor
P9 Outdoor unit protection Outdoor unit fault Check outdoor unit error codes
U1 High pressure switch High pressure protection Check condenser, refrigerant, airflow
U2 Low pressure switch Low pressure protection Check refrigerant charge, filter
U3 Short cycle Compressor short cycling Check timer settings, pressure
U4 Discharge pipe temp high Compressor overheat Check refrigerant, airflow
U5 Heat sink overheat Inverter overheating Check outdoor unit airflow
U6 Compressor overcurrent Compressor drawing excess current Check compressor, voltage, refrigerant
U7 Low superheat Possible liquid flooding Check expansion valve, charge
U8 Outdoor fan error Outdoor fan motor fault Check fan motor, capacitor
U9 Power voltage error Input voltage out of range Check power supply voltage
UA Compressor overcurrent (CT) Current transformer detected overcurrent Check compressor, wiring
Ub Outdoor coil thermistor error Condenser sensor fault Check/replace outdoor coil thermistor
Ud Discharge thermistor error Discharge sensor open/short Check/replace discharge thermistor
UF Compressor overcurrent (peak) Instantaneous overcurrent Check compressor, wiring, voltage

LG

South Korea • 24 error codes

View all LG codes →
Code Description Cause Action
CH01 Indoor room temp sensor error Thermistor open/short Check/replace room thermistor
CH02 Indoor inlet temp sensor error Evaporator inlet sensor fault Check sensor connection and resistance
CH03 Indoor outlet temp sensor error Evaporator outlet sensor fault Check/replace outlet thermistor
CH05 Communication error Wired remote communication fail Check communication wiring
CH06 Indoor outlet temp sensor error Sensor fault Check outlet pipe sensor
CH07 Indoor BLDC motor error Fan motor failure Check BLDC motor, hall sensor
CH10 Indoor BLDC motor error Motor locked rotor Check for obstructions, replace motor
CH21 Outdoor DC link voltage error DC bus voltage abnormal Check power supply, inverter board
CH22 Outdoor current detection error CT sensor fault Check CT sensor
CH23 Outdoor DC link low voltage Low DC bus voltage Check power supply voltage
CH26 Outdoor fan BLDC error Outdoor fan motor fault Check fan motor operation
CH27 Outdoor PSC motor error PSC fan motor fault Check fan motor, capacitor
CH32 Outdoor discharge temp high Compressor overheat Check refrigerant, airflow
CH33 Outdoor discharge temp sensor error Discharge thermistor fault Check/replace sensor
CH34 High pressure sensor error Pressure transducer fault Check pressure sensor
CH35 Low pressure sensor error Pressure transducer fault Check pressure sensor
CH38 Outdoor compressor temp sensor error Compressor thermistor fault Check sensor on compressor shell
CH40 Outdoor CT sensor error Current transformer fault Check CT sensor and wiring
CH44 Outdoor air temp sensor error Ambient thermistor fault Check/replace outdoor thermistor
CH45 Outdoor condenser temp sensor error Condenser thermistor fault Check/replace coil thermistor
CH53 Communication error between PCBs Internal communication fault Check outdoor PCB connections
CH61 Outdoor condenser temp high High condensing temperature Clean condenser, check fan
CH62 Inverter module temp high IPM overheating Check airflow around outdoor unit
CH67 Outdoor fan motor lock Fan motor locked Check for obstructions, replace motor

Samsung

South Korea • 19 error codes

View all Samsung codes →
Code Description Cause Action
E101 Communication error Indoor-outdoor communication fail Check communication wiring
E121 Indoor room sensor error Room thermistor fault Check/replace room sensor
E122 Indoor coil sensor error Evaporator thermistor fault Check/replace coil sensor
E154 Indoor fan error Fan motor failure Check fan motor, connections
E162 Indoor EEPROM error Memory chip fault Replace indoor PCB
E201 Communication error Outdoor communication fault Check wiring polarity
E221 Outdoor TH1 sensor error Outdoor coil sensor fault Check/replace TH1
E231 Abnormal high pressure High pressure detected Check refrigerant, condenser
E237 Inverter overcurrent IPM overcurrent trip Check compressor, wiring
E251 Outdoor EEPROM error Memory chip fault Replace outdoor PCB
E416 Compressor discharge temp high Compressor overheat Check refrigerant, superheat
E440 Low pressure switch open Low pressure protection Check refrigerant charge
E441 High pressure switch open High pressure protection Check condenser, charge
E461 Compressor startup failure Compressor failed to start Check compressor, voltage, wiring
E464 Compressor overcurrent Excessive compressor current Check compressor, refrigerant
E465 DC link voltage error DC bus voltage abnormal Check power supply
E466 Outdoor fan error Fan motor fault Check fan motor operation
E468 CT sensor error Current sensor fault Check CT sensor
E554 Inverter module temp high IPM overheating Improve ventilation

Gree

China • 20 error codes

View all Gree codes →
Code Description Cause Action
E1 High pressure protection High discharge pressure Check condenser, fan, refrigerant
E2 Indoor freeze protection Evaporator freezing Check airflow, charge, expansion valve
E3 Low pressure protection Low suction pressure Check refrigerant charge, filter
E4 Compressor discharge temp high Compressor overheating Check superheat, refrigerant
E5 Overcurrent protection Compressor overcurrent Check compressor, voltage
E6 Communication error Indoor-outdoor communication fail Check wiring connections
E7 Mode conflict Multi-split mode mismatch Set all units to same mode
E8 Overload protection System overload Check load, reduce demand
E9 Full water protection Condensate tank full Empty condensate tank
F0 Refrigerant shortage Low refrigerant Check for leaks, recharge
F1 Indoor ambient sensor error Room thermistor fault Check/replace sensor
F2 Indoor coil sensor error Evaporator thermistor fault Check/replace sensor
F3 Outdoor ambient sensor error Outdoor thermistor fault Check/replace sensor
F4 Outdoor coil sensor error Condenser thermistor fault Check/replace sensor
F5 Discharge temp sensor error Discharge thermistor fault Check/replace sensor
F6 Overcharge protection System overcharged Recover excess refrigerant
H1 Defrost mode Heat pump defrosting (normal) Wait for defrost to complete
H3 Compressor overload Compressor thermal protection Check compressor, charge
H5 IPM protection Inverter module fault Check inverter board
H6 Fan motor feedback error Indoor fan motor fault Check fan motor, connections

Panasonic

Japan • 24 error codes

View all Panasonic codes →
Code Description Cause Action
H00 No abnormality Normal operation No action required
H11 Communication error Indoor-outdoor communication fail Check communication wiring
H12 Indoor unit capacity error Capacity mismatch Check system configuration
H14 Indoor air sensor error Room thermistor fault Check/replace room sensor
H15 Indoor compressor sensor error Sensor fault Check indoor sensors
H16 Indoor current sensor error CT sensor fault Check CT sensor
H19 Indoor fan motor error Fan motor locked Check fan motor operation
H23 Indoor gas pipe sensor error Thermistor fault Check/replace gas pipe sensor
H25 Indoor filter cleaning error Auto-clean function error Clean filter, check mechanism
H27 Outdoor air sensor error Ambient thermistor fault Check/replace outdoor sensor
H28 Outdoor coil sensor error Condenser thermistor fault Check/replace coil sensor
H30 Outdoor discharge sensor error Discharge thermistor fault Check/replace discharge sensor
H33 Connection mistake Wiring connection error Check indoor/outdoor wiring
H38 Indoor/outdoor mismatch Unit mismatch Verify compatible units
H98 Indoor high pressure protection Indoor unit pressure high Check airflow, filter
H99 Indoor freeze protection Evaporator freezing Check airflow, charge
F11 4-way valve error Reversing valve malfunction Check 4-way valve coil, operation
F17 Indoor freeze protection Freezing detected Defrost, check airflow
F90 Outdoor inverter error Inverter circuit fault Check inverter board
F91 Refrigerant cycle error Refrigerant system fault Check charge, valves, piping
F93 Compressor rotor position error Position sensor fault Check compressor, inverter
F95 Outdoor cooling error Condenser performance issue Clean condenser, check fan
F96 IPM overheat Inverter module overheating Check ventilation, heat sink
F97 Compressor overheat Compressor overheating Check refrigerant, superheat

Hitachi

Japan • 36 error codes

View all Hitachi codes →
Code Description Cause Action
02 High pressure protection High pressure cut activated Check refrigerant charge, condenser, fan operation
03 Indoor/outdoor communication error Disconnected wires, loose terminals, incorrect wiring Check communication wiring between units
04 Outdoor PCB to fan controller error Blown fuse, loose connectors, broken wires Check outdoor fan controller circuit
06 Phase detection failure Phase sequence error or missing phase Check 3-phase power supply, correct phase sequence
0A Outdoor to outdoor communication error Damaged wiring, incorrect connections (multi-split) Check wiring between outdoor units
0B Main unit address error Multiple units set as main unit Check address settings, set only one main
0C Sub unit address error Address setting conflict Correct address settings on sub units
11 Indoor inlet air thermistor error Thermistor open/short circuit Check/replace inlet air thermistor
12 Indoor outlet air thermistor error Thermistor failure Check/replace outlet air thermistor
13 Indoor freeze protection thermistor error Evaporator thermistor fault Check/replace evaporator thermistor
14 Indoor gas piping thermistor error Gas pipe sensor failure Check/replace gas pipe thermistor
21 Outdoor high pressure sensor error Pressure transducer fault Check/replace high pressure sensor
22 Outdoor low pressure sensor error Pressure transducer fault Check/replace low pressure sensor
23 Outdoor discharge gas thermistor error Discharge temperature sensor fault Check/replace discharge thermistor
24 Outdoor heat exchanger thermistor error Condenser thermistor fault Check/replace condenser thermistor
25 Outdoor suction gas thermistor error Suction temperature sensor fault Check/replace suction thermistor
29 Outdoor air thermistor error Ambient temperature sensor fault Check/replace outdoor air thermistor
31 Capacity setting mismatch Indoor/outdoor capacity code incorrect Verify capacity code settings match
35 Indoor unit number duplicated Multiple units with same address Assign unique addresses to each unit
36 Incompatible unit combination Mismatched indoor/outdoor units Verify unit compatibility
39 Constant compressor overcurrent Running current abnormal Check compressor, current sensor, power supply
43 Low pressure protection Low suction pressure Check refrigerant charge, filter, expansion valve
44 High pressure protection (repeat) Repeated high pressure trips Check condenser, refrigerant charge, ambient conditions
45 Discharge temperature protection Compressor discharge overheat Check superheat, refrigerant charge, airflow
46 Inverter compressor overcurrent Inverter compressor drawing excess current Check compressor, voltage, refrigerant
47 Valve locking protection Service valve closed or restricted Open service valves, check for restriction
48 Electrical overload System drawing excessive power Check power supply, reduce load
53 Inverter PCB failure Inverter board malfunction Replace inverter PCB
54 Inverter overheating IPM module overheat Check ventilation around outdoor unit
55 Fan motor error Outdoor fan motor failure Check fan motor, replace if necessary
E0 Water pump error Condensate pump failure Check drain pump operation
E1 Compressor thermal protection Compressor internal protection Check refrigerant charge, superheat
E3 High pressure protection High discharge pressure Check condenser, fan, refrigerant
E5 Inverter compressor error Compressor startup failure Check compressor, inverter, wiring
E9 Indoor fan motor error Indoor fan locked rotor Check fan motor, obstructions
EE Compressor protection alarm Repeated compressor trips (3x in 6 hours) Professional service required, check compressor

Mitsubishi Heavy Industries

Japan • 32 error codes

View all Mitsubishi Heavy Industries codes →
Code Description Cause Action
E01 Remote controller communication error Wired remote controller wiring failure Check remote controller wiring connections
E02 Duplicate indoor unit address Multiple units have same address Assign unique address to each indoor unit
E03 Indoor/outdoor communication error Communication not established Check wiring between indoor and outdoor units
E05 Indoor/outdoor transmission abnormal Serial communication failure Check communication line polarity and connections
E06 Indoor heat exchanger thermistor error Evaporator sensor fault Check/replace evaporator thermistor
E07 Indoor return air thermistor error Room temperature sensor fault Check/replace return air thermistor
E08 Heating overload protection Overheat during heating mode Check airflow, thermistor operation
E09 Drain float switch activated Condensate drain blocked Clean drain line, check float switch
E10 Too many indoor units connected Over 17 indoor units on system Reduce number of connected units
E16 Indoor fan motor error Fan motor failure or locked rotor Check fan motor, capacitor, wiring
E28 Remote controller thermistor error Remote controller sensor fault Replace remote controller
E32 Phase wiring open or reversed 3-phase connection error Check phase wiring, correct phase sequence
E33 Inverter current abnormal Compressor current out of range Check compressor, inverter board
E34 L3-phase wiring open Missing phase connection Check 3-phase power supply connections
E35 Heat exchanger temperature high Condenser overheat Clean condenser, check fan operation
E36 Discharge temperature abnormal Compressor discharge overheat Check superheat, refrigerant charge
E37 Outdoor heat exchanger thermistor error Condenser thermistor fault Check/replace condenser thermistor
E38 Outdoor air thermistor error Ambient temperature sensor fault Check/replace outdoor air thermistor
E39 Discharge pipe thermistor error Discharge temperature sensor fault Check/replace discharge thermistor
E40 High pressure protection High pressure switch activated Check condenser, fan, refrigerant charge
E42 Compressor overcurrent Compressor drawing excess current Check compressor, power supply, refrigerant
E43 Low pressure protection Low pressure switch activated Check refrigerant charge, filter, expansion valve
E47 Inverter overvoltage DC bus voltage too high Check power supply voltage, inverter board
E48 DC fan motor abnormal Outdoor DC fan motor fault Check fan motor, hall sensor, wiring
E52 Control circuit abnormal Outdoor PCB fault Check/replace outdoor control board
E56 Power transistor thermistor error IPM temperature sensor fault Check IPM thermistor, replace if needed
E57 Insufficient refrigerant Low refrigerant charge detected Check for leaks, recharge system
E59 Compressor startup error Compressor failed to start Check compressor, inverter, wiring
E60 Compressor position detection error Rotor position sensor fault Check compressor, inverter board
E63 Emergency stop activated Emergency stop input received Check emergency stop circuit, reset
E64 High pressure protection (sensor) High pressure transducer trip Check condenser, refrigerant, ambient
E68 Current sensor abnormal CT sensor fault Check current transformer sensor

Troubleshooting Tips

  • Record the exact error code - Some brands use letters, numbers, or both
  • Check for multiple errors - Some systems store error history in service mode
  • Note when the error occurs - Startup, during operation, or after running
  • Check both indoor and outdoor units - Errors may be displayed on either unit
  • Reset after repair - Clear error codes after fixing the issue
  • Some codes are informational - Not all codes indicate a fault (e.g., defrost mode)