Inverter AC Error Codes

Fault code database for VRF and mini-split systems

Found 502 error codes

Daikin

Japan • 30 error codes

View all Daikin codes →
Code Description Cause Action
A0 External protection device activated External protection relay triggered Check external protection device, reset if safe
A1 Indoor PCB defect Indoor unit control board failure Replace indoor PCB
A3 Drain level abnormal Condensate drain blocked or float switch activated Clean drain line, check float switch
A5 Heat exchanger freeze-up Evaporator coil freezing Check airflow, refrigerant charge, expansion valve
A6 Fan motor abnormal Indoor fan motor locked or abnormal Check fan motor, capacitor, wiring
A7 Swing motor abnormal Louver/swing motor failure Check swing motor and drive circuit
C4 Heat exchanger sensor fault Indoor coil thermistor open/short Check thermistor resistance, replace if out of spec
C9 Room temperature sensor fault Room temperature thermistor failure Check sensor connection and resistance
E0 External protection device Outdoor external protection activated Check external protection circuit
E1 Outdoor PCB fault Outdoor control board failure Replace outdoor PCB
E3 High pressure switch activated High discharge pressure Check condenser, fan, refrigerant charge, ambient
E4 Low pressure switch activated Low suction pressure Check refrigerant charge, expansion valve, airflow
E5 Inverter compressor overload Compressor motor overcurrent Check compressor, power supply, refrigerant
E6 Standard compressor overload Fixed speed compressor overcurrent Check compressor, capacitor, power supply
E7 Fan motor overcurrent Outdoor fan drawing excess current Check fan motor, blade, bearings
E9 Electronic expansion valve fault EEV driver or valve failure Check EEV wiring, driver, replace valve if needed
F3 Discharge pipe temperature high Compressor discharge overheating Check superheat, refrigerant charge, airflow
F6 High pressure abnormal Pressure sensor detecting high pressure Check refrigerant charge, condenser, ambient
H6 Position sensor fault Compressor position sensor failure Check sensor wiring, replace compressor if internal
H8 CT sensor fault Current transformer failure Check CT sensor and wiring
H9 Outdoor air sensor fault Outdoor ambient thermistor failure Check thermistor resistance and connection
J3 Discharge pipe sensor fault Discharge temperature thermistor failure Replace discharge temperature sensor
J6 Heat exchanger sensor fault Outdoor coil thermistor failure Check thermistor, replace if needed
L3 Electrical box temperature high Control box overheating Check ventilation, clean control box
L4 Heat sink temperature high Inverter heat sink overheating Check airflow around outdoor unit
L5 Compressor overcurrent Instantaneous overcurrent trip Check compressor, wiring, voltage
P4 Inverter heat sink sensor fault Heat sink thermistor failure Replace heat sink temperature sensor
U0 Low refrigerant System undercharged Check for leaks, recharge system
U2 Abnormal power supply voltage Low or high voltage detected Check power supply voltage, connections
U4 Communication error Indoor-outdoor communication failure Check communication wiring, connectors

Mitsubishi Electric

Japan • 29 error codes

View all Mitsubishi Electric codes →
Code Description Cause Action
E0 Remote controller signal error Communication issue with remote Check remote controller and receiver
E1 Remote controller PCB error Remote control board fault Replace remote controller
E3 Communication error No communication between units Check wiring between indoor and outdoor
E6 Indoor/outdoor communication error Serial communication failure Check S21/S22 communication lines
E7 Indoor fan motor error Fan motor failure Check fan motor, hall sensor, connections
E9 Indoor/outdoor communication error Communication timeout Check wiring polarity and connections
Eb Indoor PCB error Indoor control board failure Replace indoor PCB
F1 Room thermistor open/short Room temperature sensor fault Check/replace room thermistor
F2 Indoor coil thermistor fault Evaporator sensor open/short Check/replace coil thermistor
P1 Power supply peak detection Input voltage variation Check power supply stability
P2 Current sensor error CT sensor failure Check CT sensor and wiring
P4 Drain sensor error Float switch activated Clean condensate drain
P5 Drain pump error Condensate pump failure Check drain pump operation
P6 Freeze/overheat protection Coil temperature abnormal Check airflow, refrigerant charge
P8 Pipe thermistor error Liquid pipe sensor fault Check pipe thermistor
P9 Outdoor unit protection Outdoor unit fault Check outdoor unit error codes
U1 High pressure switch High pressure protection Check condenser, refrigerant, airflow
U2 Low pressure switch Low pressure protection Check refrigerant charge, filter
U3 Short cycle Compressor short cycling Check timer settings, pressure
U4 Discharge pipe temp high Compressor overheat Check refrigerant, airflow
U5 Heat sink overheat Inverter overheating Check outdoor unit airflow
U6 Compressor overcurrent Compressor drawing excess current Check compressor, voltage, refrigerant
U7 Low superheat Possible liquid flooding Check expansion valve, charge
U8 Outdoor fan error Outdoor fan motor fault Check fan motor, capacitor
U9 Power voltage error Input voltage out of range Check power supply voltage
UA Compressor overcurrent (CT) Current transformer detected overcurrent Check compressor, wiring
Ub Outdoor coil thermistor error Condenser sensor fault Check/replace outdoor coil thermistor
Ud Discharge thermistor error Discharge sensor open/short Check/replace discharge thermistor
UF Compressor overcurrent (peak) Instantaneous overcurrent Check compressor, wiring, voltage

LG

South Korea • 24 error codes

View all LG codes →
Code Description Cause Action
CH01 Indoor room temp sensor error Thermistor open/short Check/replace room thermistor
CH02 Indoor inlet temp sensor error Evaporator inlet sensor fault Check sensor connection and resistance
CH03 Indoor outlet temp sensor error Evaporator outlet sensor fault Check/replace outlet thermistor
CH05 Communication error Wired remote communication fail Check communication wiring
CH06 Indoor outlet temp sensor error Sensor fault Check outlet pipe sensor
CH07 Indoor BLDC motor error Fan motor failure Check BLDC motor, hall sensor
CH10 Indoor BLDC motor error Motor locked rotor Check for obstructions, replace motor
CH21 Outdoor DC link voltage error DC bus voltage abnormal Check power supply, inverter board
CH22 Outdoor current detection error CT sensor fault Check CT sensor
CH23 Outdoor DC link low voltage Low DC bus voltage Check power supply voltage
CH26 Outdoor fan BLDC error Outdoor fan motor fault Check fan motor operation
CH27 Outdoor PSC motor error PSC fan motor fault Check fan motor, capacitor
CH32 Outdoor discharge temp high Compressor overheat Check refrigerant, airflow
CH33 Outdoor discharge temp sensor error Discharge thermistor fault Check/replace sensor
CH34 High pressure sensor error Pressure transducer fault Check pressure sensor
CH35 Low pressure sensor error Pressure transducer fault Check pressure sensor
CH38 Outdoor compressor temp sensor error Compressor thermistor fault Check sensor on compressor shell
CH40 Outdoor CT sensor error Current transformer fault Check CT sensor and wiring
CH44 Outdoor air temp sensor error Ambient thermistor fault Check/replace outdoor thermistor
CH45 Outdoor condenser temp sensor error Condenser thermistor fault Check/replace coil thermistor
CH53 Communication error between PCBs Internal communication fault Check outdoor PCB connections
CH61 Outdoor condenser temp high High condensing temperature Clean condenser, check fan
CH62 Inverter module temp high IPM overheating Check airflow around outdoor unit
CH67 Outdoor fan motor lock Fan motor locked Check for obstructions, replace motor

Samsung

South Korea • 19 error codes

View all Samsung codes →
Code Description Cause Action
E101 Communication error Indoor-outdoor communication fail Check communication wiring
E121 Indoor room sensor error Room thermistor fault Check/replace room sensor
E122 Indoor coil sensor error Evaporator thermistor fault Check/replace coil sensor
E154 Indoor fan error Fan motor failure Check fan motor, connections
E162 Indoor EEPROM error Memory chip fault Replace indoor PCB
E201 Communication error Outdoor communication fault Check wiring polarity
E221 Outdoor TH1 sensor error Outdoor coil sensor fault Check/replace TH1
E231 Abnormal high pressure High pressure detected Check refrigerant, condenser
E237 Inverter overcurrent IPM overcurrent trip Check compressor, wiring
E251 Outdoor EEPROM error Memory chip fault Replace outdoor PCB
E416 Compressor discharge temp high Compressor overheat Check refrigerant, superheat
E440 Low pressure switch open Low pressure protection Check refrigerant charge
E441 High pressure switch open High pressure protection Check condenser, charge
E461 Compressor startup failure Compressor failed to start Check compressor, voltage, wiring
E464 Compressor overcurrent Excessive compressor current Check compressor, refrigerant
E465 DC link voltage error DC bus voltage abnormal Check power supply
E466 Outdoor fan error Fan motor fault Check fan motor operation
E468 CT sensor error Current sensor fault Check CT sensor
E554 Inverter module temp high IPM overheating Improve ventilation

Gree

China • 20 error codes

View all Gree codes →
Code Description Cause Action
E1 High pressure protection High discharge pressure Check condenser, fan, refrigerant
E2 Indoor freeze protection Evaporator freezing Check airflow, charge, expansion valve
E3 Low pressure protection Low suction pressure Check refrigerant charge, filter
E4 Compressor discharge temp high Compressor overheating Check superheat, refrigerant
E5 Overcurrent protection Compressor overcurrent Check compressor, voltage
E6 Communication error Indoor-outdoor communication fail Check wiring connections
E7 Mode conflict Multi-split mode mismatch Set all units to same mode
E8 Overload protection System overload Check load, reduce demand
E9 Full water protection Condensate tank full Empty condensate tank
F0 Refrigerant shortage Low refrigerant Check for leaks, recharge
F1 Indoor ambient sensor error Room thermistor fault Check/replace sensor
F2 Indoor coil sensor error Evaporator thermistor fault Check/replace sensor
F3 Outdoor ambient sensor error Outdoor thermistor fault Check/replace sensor
F4 Outdoor coil sensor error Condenser thermistor fault Check/replace sensor
F5 Discharge temp sensor error Discharge thermistor fault Check/replace sensor
F6 Overcharge protection System overcharged Recover excess refrigerant
H1 Defrost mode Heat pump defrosting (normal) Wait for defrost to complete
H3 Compressor overload Compressor thermal protection Check compressor, charge
H5 IPM protection Inverter module fault Check inverter board
H6 Fan motor feedback error Indoor fan motor fault Check fan motor, connections

Panasonic

Japan • 24 error codes

View all Panasonic codes →
Code Description Cause Action
H00 No abnormality Normal operation No action required
H11 Communication error Indoor-outdoor communication fail Check communication wiring
H12 Indoor unit capacity error Capacity mismatch Check system configuration
H14 Indoor air sensor error Room thermistor fault Check/replace room sensor
H15 Indoor compressor sensor error Sensor fault Check indoor sensors
H16 Indoor current sensor error CT sensor fault Check CT sensor
H19 Indoor fan motor error Fan motor locked Check fan motor operation
H23 Indoor gas pipe sensor error Thermistor fault Check/replace gas pipe sensor
H25 Indoor filter cleaning error Auto-clean function error Clean filter, check mechanism
H27 Outdoor air sensor error Ambient thermistor fault Check/replace outdoor sensor
H28 Outdoor coil sensor error Condenser thermistor fault Check/replace coil sensor
H30 Outdoor discharge sensor error Discharge thermistor fault Check/replace discharge sensor
H33 Connection mistake Wiring connection error Check indoor/outdoor wiring
H38 Indoor/outdoor mismatch Unit mismatch Verify compatible units
H98 Indoor high pressure protection Indoor unit pressure high Check airflow, filter
H99 Indoor freeze protection Evaporator freezing Check airflow, charge
F11 4-way valve error Reversing valve malfunction Check 4-way valve coil, operation
F17 Indoor freeze protection Freezing detected Defrost, check airflow
F90 Outdoor inverter error Inverter circuit fault Check inverter board
F91 Refrigerant cycle error Refrigerant system fault Check charge, valves, piping
F93 Compressor rotor position error Position sensor fault Check compressor, inverter
F95 Outdoor cooling error Condenser performance issue Clean condenser, check fan
F96 IPM overheat Inverter module overheating Check ventilation, heat sink
F97 Compressor overheat Compressor overheating Check refrigerant, superheat

Hitachi

Japan • 36 error codes

View all Hitachi codes →
Code Description Cause Action
02 High pressure protection High pressure cut activated Check refrigerant charge, condenser, fan operation
03 Indoor/outdoor communication error Disconnected wires, loose terminals, incorrect wiring Check communication wiring between units
04 Outdoor PCB to fan controller error Blown fuse, loose connectors, broken wires Check outdoor fan controller circuit
06 Phase detection failure Phase sequence error or missing phase Check 3-phase power supply, correct phase sequence
0A Outdoor to outdoor communication error Damaged wiring, incorrect connections (multi-split) Check wiring between outdoor units
0B Main unit address error Multiple units set as main unit Check address settings, set only one main
0C Sub unit address error Address setting conflict Correct address settings on sub units
11 Indoor inlet air thermistor error Thermistor open/short circuit Check/replace inlet air thermistor
12 Indoor outlet air thermistor error Thermistor failure Check/replace outlet air thermistor
13 Indoor freeze protection thermistor error Evaporator thermistor fault Check/replace evaporator thermistor
14 Indoor gas piping thermistor error Gas pipe sensor failure Check/replace gas pipe thermistor
21 Outdoor high pressure sensor error Pressure transducer fault Check/replace high pressure sensor
22 Outdoor low pressure sensor error Pressure transducer fault Check/replace low pressure sensor
23 Outdoor discharge gas thermistor error Discharge temperature sensor fault Check/replace discharge thermistor
24 Outdoor heat exchanger thermistor error Condenser thermistor fault Check/replace condenser thermistor
25 Outdoor suction gas thermistor error Suction temperature sensor fault Check/replace suction thermistor
29 Outdoor air thermistor error Ambient temperature sensor fault Check/replace outdoor air thermistor
31 Capacity setting mismatch Indoor/outdoor capacity code incorrect Verify capacity code settings match
35 Indoor unit number duplicated Multiple units with same address Assign unique addresses to each unit
36 Incompatible unit combination Mismatched indoor/outdoor units Verify unit compatibility
39 Constant compressor overcurrent Running current abnormal Check compressor, current sensor, power supply
43 Low pressure protection Low suction pressure Check refrigerant charge, filter, expansion valve
44 High pressure protection (repeat) Repeated high pressure trips Check condenser, refrigerant charge, ambient conditions
45 Discharge temperature protection Compressor discharge overheat Check superheat, refrigerant charge, airflow
46 Inverter compressor overcurrent Inverter compressor drawing excess current Check compressor, voltage, refrigerant
47 Valve locking protection Service valve closed or restricted Open service valves, check for restriction
48 Electrical overload System drawing excessive power Check power supply, reduce load
53 Inverter PCB failure Inverter board malfunction Replace inverter PCB
54 Inverter overheating IPM module overheat Check ventilation around outdoor unit
55 Fan motor error Outdoor fan motor failure Check fan motor, replace if necessary
E0 Water pump error Condensate pump failure Check drain pump operation
E1 Compressor thermal protection Compressor internal protection Check refrigerant charge, superheat
E3 High pressure protection High discharge pressure Check condenser, fan, refrigerant
E5 Inverter compressor error Compressor startup failure Check compressor, inverter, wiring
E9 Indoor fan motor error Indoor fan locked rotor Check fan motor, obstructions
EE Compressor protection alarm Repeated compressor trips (3x in 6 hours) Professional service required, check compressor

Mitsubishi Heavy Industries

Japan • 32 error codes

View all Mitsubishi Heavy Industries codes →
Code Description Cause Action
E01 Remote controller communication error Wired remote controller wiring failure Check remote controller wiring connections
E02 Duplicate indoor unit address Multiple units have same address Assign unique address to each indoor unit
E03 Indoor/outdoor communication error Communication not established Check wiring between indoor and outdoor units
E05 Indoor/outdoor transmission abnormal Serial communication failure Check communication line polarity and connections
E06 Indoor heat exchanger thermistor error Evaporator sensor fault Check/replace evaporator thermistor
E07 Indoor return air thermistor error Room temperature sensor fault Check/replace return air thermistor
E08 Heating overload protection Overheat during heating mode Check airflow, thermistor operation
E09 Drain float switch activated Condensate drain blocked Clean drain line, check float switch
E10 Too many indoor units connected Over 17 indoor units on system Reduce number of connected units
E16 Indoor fan motor error Fan motor failure or locked rotor Check fan motor, capacitor, wiring
E28 Remote controller thermistor error Remote controller sensor fault Replace remote controller
E32 Phase wiring open or reversed 3-phase connection error Check phase wiring, correct phase sequence
E33 Inverter current abnormal Compressor current out of range Check compressor, inverter board
E34 L3-phase wiring open Missing phase connection Check 3-phase power supply connections
E35 Heat exchanger temperature high Condenser overheat Clean condenser, check fan operation
E36 Discharge temperature abnormal Compressor discharge overheat Check superheat, refrigerant charge
E37 Outdoor heat exchanger thermistor error Condenser thermistor fault Check/replace condenser thermistor
E38 Outdoor air thermistor error Ambient temperature sensor fault Check/replace outdoor air thermistor
E39 Discharge pipe thermistor error Discharge temperature sensor fault Check/replace discharge thermistor
E40 High pressure protection High pressure switch activated Check condenser, fan, refrigerant charge
E42 Compressor overcurrent Compressor drawing excess current Check compressor, power supply, refrigerant
E43 Low pressure protection Low pressure switch activated Check refrigerant charge, filter, expansion valve
E47 Inverter overvoltage DC bus voltage too high Check power supply voltage, inverter board
E48 DC fan motor abnormal Outdoor DC fan motor fault Check fan motor, hall sensor, wiring
E52 Control circuit abnormal Outdoor PCB fault Check/replace outdoor control board
E56 Power transistor thermistor error IPM temperature sensor fault Check IPM thermistor, replace if needed
E57 Insufficient refrigerant Low refrigerant charge detected Check for leaks, recharge system
E59 Compressor startup error Compressor failed to start Check compressor, inverter, wiring
E60 Compressor position detection error Rotor position sensor fault Check compressor, inverter board
E63 Emergency stop activated Emergency stop input received Check emergency stop circuit, reset
E64 High pressure protection (sensor) High pressure transducer trip Check condenser, refrigerant, ambient
E68 Current sensor abnormal CT sensor fault Check current transformer sensor

Carrier

USA • 23 error codes

View all Carrier codes →
Code Description Cause Action
E0 EEPROM parameter error Indoor unit EEPROM data corrupted Reset power; if persists, replace indoor PCB
E1 Indoor/outdoor communication error Communication line fault between units Check signal wiring, connectors, and PCB
E2 Zero crossing detection error Power supply frequency abnormal Check power supply voltage and frequency
E3 Indoor fan speed out of control Fan motor or driver fault Check fan motor, capacitor, and driver IC
E4 Room temperature sensor fault T1 thermistor open or short circuit Check T1 sensor resistance, replace if out of range
E5 Evaporator coil sensor fault T2 thermistor open or short circuit Check T2 sensor resistance, replace if needed
E6 Outdoor coil sensor fault T3 thermistor open or short circuit Check outdoor coil sensor and wiring
E8 Indoor unit address duplicate Multiple indoor units with same address Reset indoor unit addresses to unique values
EC Refrigerant leak detection Refrigerant leak sensor triggered Check for leaks, repair and recharge
F1 Outdoor ambient sensor fault T4 thermistor open or short circuit Check outdoor ambient sensor and wiring
F2 Condenser coil sensor fault T3 thermistor open or short circuit Check condenser coil sensor, replace if faulty
F3 Discharge temperature sensor fault T5 thermistor open or short circuit Check compressor discharge sensor
F4 Outdoor EEPROM parameter error Outdoor unit EEPROM data corrupted Reset power; if persists, replace outdoor PCB
F5 Outdoor unit overload Compressor or system overload condition Check refrigerant charge, airflow, voltage
H1 Defrost mode active Normal defrost operation in heat mode Normal operation, wait for defrost to complete
H3 Compressor overload protection Compressor overcurrent detected Check compressor, refrigerant charge, voltage
H6 No feedback from compressor Inverter compressor not running Check compressor wiring, inverter board
P0 IPM module protection Inverter power module fault Check IPM module, DC bus voltage, compressor
P1 Over/under voltage protection Power supply voltage out of range Check voltage at outdoor unit terminals
P2 Compressor top temperature protection Compressor discharge overheating Check superheat, refrigerant charge, airflow
P4 Inverter compressor drive error Inverter drive board fault Check inverter board and compressor wiring
P5 Outdoor DC fan motor fault Fan motor speed feedback error Check DC fan motor and wiring
P6 Outdoor unit overheating Control box temperature too high Check ventilation around outdoor unit

Fujitsu General

Japan • 27 error codes

View all Fujitsu General codes →
Code Description Cause Action
E:EE Communication error between indoor and outdoor Signal wiring fault Check communication wiring between units
E:01 Communication error (indoor PCB) Indoor control board fault Check indoor PCB, reset power
E:02 Communication error (outdoor PCB) Outdoor control board fault Check outdoor PCB, signal wiring
E:03 Remote controller communication error Remote signal not received Check remote controller and receiver
E:04 Indoor/outdoor mismatch Incompatible indoor and outdoor units Verify unit compatibility and capacity
E:06 Indoor fan motor error Fan motor locked or abnormal speed Check fan motor, blade, and wiring
E:07 Outdoor fan motor error Outdoor fan motor fault Check outdoor fan motor and drive circuit
E:08 Compressor overcurrent Compressor drawing excess current Check compressor, refrigerant charge, voltage
E:09 Electronic expansion valve error EEV driver or valve fault Check EEV wiring and operation
E:0A Compressor overcurrent at startup Locked rotor or high starting current Check compressor, starting circuit
E:0C Compressor current sensor fault CT sensor failure Check current transformer and wiring
E:0d Compressor position error Inverter cannot detect rotor position Check compressor and inverter board
E:11 Room temperature sensor error Thermistor open or short Check room temperature sensor
E:12 Indoor coil temperature sensor error Evaporator thermistor fault Check coil temperature sensor
E:13 Outdoor coil temperature sensor error Condenser thermistor fault Check outdoor coil sensor
E:14 Outdoor ambient sensor error Outdoor temperature thermistor fault Check outdoor ambient sensor
E:15 Compressor discharge sensor error Discharge thermistor fault Check discharge temperature sensor
E:16 Heat sink temperature sensor error IPM heat sink thermistor fault Check heat sink sensor on inverter
E:20 Compressor overload (high discharge temp) Compressor overheating Check superheat, refrigerant charge, airflow
E:21 IPM overheat protection Inverter module overheating Check airflow around outdoor unit
E:23 Freeze protection activated Evaporator coil freezing Check airflow, filter, refrigerant charge
E:24 High pressure protection System high pressure exceeded limit Check condenser, fan, refrigerant charge
E:25 Low pressure protection System low pressure below limit Check for leaks, refrigerant charge
E:28 DC voltage abnormal Inverter DC bus voltage fault Check power supply, rectifier circuit
E:31 Power module protection IPM module fault Check inverter module and compressor
E:33 DC bus voltage high DC voltage exceeds limit Check power supply voltage stability
E:53 Drain pump or float switch error Condensate drainage blocked Clean drain line, check float switch and pump

Trane

USA • 20 error codes

View all Trane codes →
Code Description Cause Action
E0 EEPROM parameter error Unit EEPROM data corrupted Reset power; replace PCB if persists
E1 Indoor/outdoor communication error Communication line disconnected Check signal wiring between units
E2 Zero crossing detection error Power supply frequency abnormal Check power supply quality
E3 Fan speed out of control Indoor fan motor abnormal Check fan motor, capacitor, driver
E4 Room temperature sensor fault T1 thermistor open or short Check and replace room sensor
E5 Evaporator coil sensor fault T2 thermistor open or short Check and replace coil sensor
E6 Condenser coil sensor fault Outdoor coil thermistor fault Check outdoor coil temperature sensor
E109 Communication timeout during startup Indoor-outdoor communication failed at startup Verify all wiring and power connections
E201 Indoor/outdoor tracking communication error Indoor unit powered off or wire break Check indoor power and daisy-chain wiring
E320 OLP sensor open or short Compressor top sensor or circuit board defective Check OLP sensor, replace PCB if needed
F1 Outdoor ambient sensor fault Outdoor temperature sensor failure Check outdoor ambient thermistor
F2 Condenser temperature sensor fault Condenser coil thermistor failure Check condenser sensor resistance
F3 Discharge temperature sensor fault Compressor discharge thermistor failure Check discharge temperature sensor
H1 Defrost mode Normal defrost operation Normal, wait 5-10 minutes to complete
H3 Compressor overload protection Overcurrent or overheating Check compressor and refrigerant charge
P0 IPM module protection Inverter module fault Check IPM module and compressor
P1 Over/under voltage protection Supply voltage out of range Check power supply voltage at unit
P2 Compressor top temperature high Compressor discharge overheating Check superheat, charge, clean condenser
P4 Inverter compressor drive error Drive board failure Check inverter drive board
P5 DC fan motor fault Outdoor fan motor feedback error Check DC fan motor wiring and bearings

York

USA • 20 error codes

View all York codes →
Code Description Cause Action
E0 EEPROM malfunction EEPROM data error Reset power; replace PCB if persists
E1 Indoor/outdoor communication error Communication line fault Check signal wiring and connectors
E2 Zero crossing signal error Power supply issue Check power supply voltage and frequency
E3 Indoor fan speed error Fan motor abnormal Check fan motor and driver circuit
E4 Room temperature sensor open/short T1 sensor fault Check and replace room sensor
E5 Indoor coil sensor open/short T2 sensor fault Check and replace coil sensor
E6 Outdoor coil sensor fault Outdoor thermistor failure Check outdoor coil temperature sensor
E7 Outdoor discharge sensor fault Discharge thermistor open or short Check compressor discharge sensor
E8 Outdoor ambient sensor fault Outdoor temperature sensor failure Check outdoor ambient thermistor
EC Refrigerant leak detected Leak sensor triggered Check for leaks, repair and recharge
F1 Condenser high temperature protection Condenser coil overheating Clean condenser, check fan operation
F2 Evaporator freeze protection Evaporator coil freezing Check airflow, filter, refrigerant charge
F3 Discharge temperature protection High discharge temperature Check superheat and refrigerant charge
F4 Compressor overload protection Compressor overcurrent Check compressor and power supply
H1 Defrost in progress Normal defrost cycle Normal operation, wait for completion
H5 IPM module protection Inverter module fault Check IPM and compressor
P0 IPM overcurrent protection Inverter overcurrent Check compressor and inverter board
P1 High/low voltage protection Supply voltage abnormal Check voltage at outdoor unit
P2 Compressor overheating protection Compressor top temperature high Check superheat, charge, airflow
P4 Compressor drive error Inverter drive fault Check inverter board, compressor wiring

Midea

China • 22 error codes

View all Midea codes →
Code Description Cause Action
E0 EEPROM parameter error Indoor EEPROM data corrupted Reset power; replace PCB if persists
E1 Indoor/outdoor communication error Signal wiring disconnected Check communication wiring between units
E2 Zero crossing error Power supply frequency abnormal Check power supply quality
E3 Indoor fan speed error Fan motor speed out of control Check fan motor and drive circuit
E4 Room temperature sensor fault T1 sensor open or short Check room temperature sensor
E5 Evaporator temperature sensor fault T2 sensor open or short Check evaporator coil sensor
E6 Outdoor temperature sensor fault T3 sensor open or short Check outdoor coil sensor
E8 Duplex communication error Address conflict on communication bus Reset unit addresses
E9 Expansion valve fault EEV driver or valve failure Check EEV coil and wiring
EC Refrigerant leak detection Leak sensor activated Leak test, repair, and recharge system
F0 Outdoor EEPROM error Outdoor unit EEPROM fault Reset power; replace outdoor PCB if needed
F1 Outdoor ambient sensor fault T4 thermistor failure Check outdoor ambient sensor
F2 Condenser coil sensor fault Condenser thermistor failure Check condenser sensor
F3 Discharge temperature sensor fault T5 thermistor failure Check compressor discharge sensor
F4 Suction temperature sensor fault Suction line thermistor failure Check suction line sensor
P0 IPM module protection Inverter module overcurrent Check IPM module and compressor
P1 Over/under voltage protection Supply voltage out of range Check power supply voltage
P2 Compressor top temperature protection Compressor overheating Check superheat, charge, airflow
P3 High current protection System drawing excess current Check compressor and wiring
P4 Inverter drive error Drive board fault Check inverter board and compressor wiring
P5 DC fan motor fault Outdoor fan feedback error Check DC fan motor and wiring
P6 Heat sink temperature high Inverter heat sink overheating Check outdoor unit ventilation

Haier

China • 19 error codes

View all Haier codes →
Code Description Cause Action
E0 EEPROM parameter error EEPROM data corrupted Reset power; replace board if persists
E1 Indoor/outdoor communication error Communication line fault Check signal wiring and connectors
E2 Zero crossing error Power supply issue Check power supply stability
E3 Fan speed error Indoor fan speed abnormal Check fan motor and circuit
E4 Room temperature sensor fault T1 sensor open/short Check room sensor
E5 Evaporator sensor fault T2 sensor open/short Check evaporator sensor
E6 Outdoor sensor fault Outdoor thermistor failure Check outdoor coil sensor
E7 Humidity sensor fault Humidity sensor failure Check and replace humidity sensor
E8 Address error Unit address conflict Check and reset unit addresses
F1 Ambient temperature sensor fault Outdoor ambient sensor failure Check outdoor ambient sensor
F2 Condenser sensor fault Condenser thermistor failure Check condenser sensor
F3 Discharge sensor fault Discharge thermistor failure Check discharge temperature sensor
F4 Suction sensor fault Suction line sensor failure Check suction temperature sensor
P0 IPM protection Inverter module fault Check IPM module and compressor
P1 Voltage protection Supply voltage abnormal Check power supply voltage
P2 Compressor overheating Compressor top temperature high Check charge, superheat, airflow
P3 High current protection System overcurrent Check compressor and wiring
P4 Inverter drive error Drive board fault Check inverter drive board
P5 Fan motor fault Outdoor DC fan error Check outdoor fan motor

Toshiba

Japan • 22 error codes

View all Toshiba codes →
Code Description Cause Action
E01 Indoor PCB failure Indoor control board fault Replace indoor PCB
E02 Indoor/outdoor communication error Communication line disconnected Check signal wiring
E03 Remote controller communication error Remote signal fault Check remote and receiver
E04 Indoor fan motor error Fan motor locked or abnormal Check fan motor and wiring
E05 Indoor thermistor fault Room temperature sensor failure Check room sensor resistance
E06 Indoor coil sensor fault Evaporator thermistor failure Check coil temperature sensor
E07 Drain sensor/pump fault Drainage system error Check drain line and float switch
E09 Indoor EEPROM error EEPROM data corrupted Reset power; replace PCB if needed
E10 Multi-indoor capacity error Indoor capacity exceeds outdoor Verify unit capacity matching
E15 Outdoor PCB fault Outdoor control board failure Replace outdoor PCB
E16 Compressor overcurrent Compressor drawing excess current Check compressor, charge, voltage
E17 Outdoor fan motor fault Fan motor error Check outdoor fan motor and wiring
E18 Outdoor coil sensor fault Condenser thermistor failure Check outdoor coil sensor
E19 Outdoor ambient sensor fault Outdoor temperature sensor failure Check outdoor ambient sensor
E20 Discharge temperature sensor fault Discharge thermistor failure Check discharge temperature sensor
E21 High pressure protection System high pressure exceeded Check condenser, fan, charge
E22 Compressor overheating Compressor discharge temperature high Check superheat, charge, airflow
E23 Low pressure protection System low pressure detected Check for leaks, verify charge
E24 Inverter overcurrent IPM module overcurrent Check inverter module and compressor
E27 Outdoor EEPROM error Outdoor EEPROM corrupted Reset power; replace outdoor PCB
E28 DC voltage abnormal Inverter DC bus fault Check power supply, rectifier
E31 Heat sink temperature high Inverter overheating Check outdoor unit ventilation

Hisense

China • 20 error codes

View all Hisense codes →
Code Description Cause Action
E0 EEPROM error EEPROM data fault Reset power; replace PCB if persists
E1 Indoor/outdoor communication error Signal wiring fault Check communication wiring
E2 Zero crossing error Power supply issue Check power supply quality
E3 Fan speed error Indoor fan abnormal Check fan motor and circuit
E4 Room temperature sensor fault T1 sensor open/short Check room temperature sensor
E5 Evaporator sensor fault T2 sensor open/short Check evaporator sensor
E6 Condenser sensor fault Outdoor coil sensor fault Check condenser sensor
E8 Duplex communication error Address conflict Reset unit addresses
EC Refrigerant leak detected Leak sensor triggered Check for leaks, repair, recharge
F0 Outdoor EEPROM error Outdoor EEPROM fault Reset; replace outdoor PCB if needed
F1 Outdoor ambient sensor fault T4 thermistor failure Check outdoor ambient sensor
F2 Condenser sensor fault Condenser thermistor failure Check condenser temperature sensor
F3 Discharge sensor fault Discharge thermistor failure Check discharge temperature sensor
F4 Suction sensor fault Suction thermistor failure Check suction line sensor
P0 IPM module protection Inverter overcurrent Check IPM module and compressor
P1 Voltage protection Voltage out of range Check power supply voltage
P2 Compressor overheating Compressor discharge temp high Check superheat, charge, airflow
P3 Overcurrent protection System drawing excess current Check compressor and wiring
P4 Inverter drive error Drive board fault Check inverter drive board
P5 DC fan motor fault Fan motor feedback error Check outdoor DC fan motor

Lennox

USA • 32 error codes

View all Lennox codes →
Code Description Cause Action
E1 High pressure protection Discharge pressure too high, condenser blockage or overcharge Check condenser coil, clean if dirty, verify refrigerant charge and outdoor fan operation
E2 Anti-freezing protection Evaporator coil temperature too low, low airflow or low charge Check air filter, indoor fan, refrigerant charge, and expansion valve
E3 Low pressure protection Suction pressure too low, refrigerant leak or restriction Check for leaks, verify charge, inspect filter drier and expansion valve
E4 High discharge temperature protection Compressor discharge temperature excessive Check refrigerant charge, condenser airflow, and compressor valves
E5 Whole unit overcurrent protection System drawing excess current Check power supply voltage, compressor windings, and wiring connections
E6 Indoor/outdoor communication error Communication wire fault between indoor and outdoor units Check communication wiring, connectors, and PCB boards on both units
E7 Running mode conflict Multiple indoor units requesting conflicting modes (heat vs cool) Set all indoor units to same mode, check mode settings via remote
E8 Overload protection Compressor overload due to high pressure or mechanical issue Check condenser, refrigerant charge, compressor, and ambient conditions
E9 Indoor unit full water error Condensate drain pan full, float switch triggered Clean drain line, check drain pump, clear blockage in condensate piping
EU IPM temperature protection / frequency limited Inverter power module overheating Check outdoor unit airflow, clean heat sink, verify fan operation
F0 System charge shortage or blockage Low refrigerant or restriction in refrigerant circuit Check for leaks, recharge system, inspect filter drier and capillary tube
F1 Return air temperature sensor fault Room temperature thermistor open or short circuit Check sensor wiring, measure resistance, replace thermistor if out of spec
F2 Evaporator temperature sensor fault Indoor coil thermistor open or short circuit Check sensor connection, measure resistance, replace if faulty
F3 Outdoor ambient temperature sensor fault Outdoor ambient thermistor open or short circuit Inspect sensor wiring at outdoor unit, replace thermistor
F4 Condenser coil temperature sensor fault Outdoor coil mid-tube thermistor open or short circuit Check sensor attached to condenser coil, replace if needed
F5 Discharge temperature sensor fault Compressor discharge thermistor open or short circuit Inspect sensor on discharge line, replace if faulty
H1 Defrosting in progress Normal defrost cycle active in heat mode No action needed, unit will resume heating after defrost completes
H3 Compressor overheating protection Compressor body temperature too high Check refrigerant charge, airflow, and compressor for mechanical failure
H5 IPM current protection Inverter power module overcurrent detected Check compressor windings, wiring, and inverter board
H6 Compressor motor stalling Compressor rotor locked or unable to start Check compressor, starting circuit, refrigerant pressures, and power supply
H7 Compressor desynchronizing Inverter compressor lost synchronization Check compressor winding resistance, inverter board, and power supply voltage
HC PFC protection Power factor correction circuit fault Check PFC module on outdoor PCB, input voltage, and capacitors
P1 High pressure switch open High pressure switch tripped due to excessive pressure Check condenser, outdoor fan, refrigerant charge, reset switch after cooling
P2 Low pressure switch open Low pressure switch tripped due to low suction pressure Check for refrigerant leaks, verify charge, inspect expansion valve
P3 Compressor current overload Outdoor compressor drawing excessive current Check compressor windings, voltage, and mechanical condition
P4 High compressor discharge temperature Discharge line temperature exceeds limit Check superheat, refrigerant charge, compressor valves
P5 Over phase current protection Phase current exceeds safe limit Check power supply, compressor, and inverter board
PH DC bus over-voltage protection DC bus voltage too high in inverter circuit Check input voltage, rectifier, and DC bus capacitors
PL DC bus under-voltage protection DC bus voltage too low in inverter circuit Check input voltage, power supply wiring, and rectifier circuit
LC Compressor startup failure Compressor failed to start within time limit Check compressor windings, power supply, refrigerant pressures
LD Compressor phase loss/reversal Phase sequence incorrect or phase missing (3-phase units) Check 3-phase wiring, swap two phases if reversed
L3 Outdoor fan motor error Outdoor fan motor 1 failure or speed abnormal Check fan motor, wiring, capacitor, and fan blade for obstruction

Bosch

Germany • 29 error codes

View all Bosch codes →
Code Description Cause Action
E0 Indoor unit EEPROM parameter error Indoor PCB EEPROM data corrupted or missing Power cycle the unit, replace indoor PCB if error persists
E1 Indoor/outdoor communication error Communication wire fault between indoor and outdoor units Check communication wiring, polarity, connectors, and both PCBs
E2 Zero-crossing signal detection error AC power zero-crossing circuit failure on indoor PCB Check power supply, replace indoor PCB if error continues
E3 Indoor fan speed out of control Indoor fan motor not running at correct speed Check fan motor, wiring, capacitor, and indoor PCB fan driver
E4 Room temperature sensor T1 fault Indoor room thermistor open or short circuit Check sensor wiring, measure resistance, replace thermistor if faulty
E5 Evaporator coil temperature sensor T2 fault Indoor coil thermistor open or short circuit Inspect sensor on evaporator coil, replace if resistance out of spec
E6 Indoor/outdoor unit communication fault Serial communication failure between units Check communication cable, verify correct wiring, inspect PCB connectors
EC Refrigerant leakage detection Built-in refrigerant leak sensor triggered Perform leak test with electronic detector, repair leak, recharge system
F0 Overload current protection System drawing excessive current beyond rated limit Check compressor, power supply voltage, and wiring connections
F1 Outdoor ambient temperature sensor T4 fault Outdoor ambient thermistor open or short circuit Check sensor wiring on outdoor unit, replace thermistor if needed
F2 Condenser coil temperature sensor T3 fault Condenser coil thermistor open or short circuit Inspect sensor on condenser coil, check connector, replace if faulty
F3 Discharge temperature sensor T5 fault Compressor discharge thermistor open or short circuit Check sensor on discharge line, replace if resistance out of range
F4 Outdoor unit EEPROM parameter error Outdoor PCB EEPROM data corrupted or missing Power cycle outdoor unit, replace outdoor PCB if error persists
F5 Outdoor fan speed out of control Outdoor fan motor not running at expected speed Check fan motor, blade obstruction, wiring, and outdoor PCB
F6 T2b sensor error Indoor coil outlet pipe temperature sensor fault Check T2b sensor wiring and connector, replace if faulty
P0 Inverter module (IPM) malfunction IPM overcurrent or overtemperature protection Check compressor windings, inverter board, heat sink, and wiring
P1 Over-voltage or under-voltage protection Input voltage or DC bus voltage out of range Check incoming voltage with multimeter, inspect rectifier and capacitors
P2 Compressor top high temperature protection Compressor shell temperature exceeds safe limit (OLP) Check refrigerant charge, superheat, condenser airflow, compressor valves
P3 Low ambient temperature cut-off Outdoor temperature below minimum operating threshold Unit cannot operate in extreme cold; check ambient sensor for accuracy
P4 High compressor discharge temperature protection Discharge line temperature exceeds safe limit Check superheat, refrigerant charge, and condenser coil cleanliness
P5 Condenser coil temperature protection in cooling Condenser coil temperature too high during cooling mode Clean condenser coil, check outdoor fan motor, verify charge
P6 Evaporator overheating protection in cooling Evaporator coil temperature too high in cooling mode Check indoor airflow, filter, fan motor, and refrigerant charge
P7 Overheating protection in heating mode Condenser (indoor coil in heating) temperature too high Check indoor airflow, air filter, and fan motor operation
P8 DC fan motor hurricane protection Outdoor DC fan motor reverse rotation detected from strong wind Check fan motor and blade, verify no extreme wind condition
E7 Outdoor DC fan motor fault DC fan motor failure or speed signal lost Check fan motor wiring, hall sensor, replace motor if faulty
E8 Compressor discharge sensor unseated T5 sensor not properly attached to discharge line Reattach discharge sensor securely to pipe, use thermal paste and insulation
E9 Outdoor EEPROM fault Outdoor unit EEPROM chip failure Replace outdoor control board
CF Anti-cold wind mode Normal startup delay to prevent cold air in heating mode No action needed, system will begin heating once coil warms up
dF Defrost mode active Normal defrost cycle running in heating mode No action needed, unit will resume heating after defrost completes

Rheem

USA • 28 error codes

View all Rheem codes →
Code Description Cause Action
E1 Indoor/outdoor communication error Communication wire fault or PCB failure between units Check communication wiring, connectors, and control boards on both units
E2 Room temperature sensor failure Indoor room thermistor open or short circuit Check sensor wiring and resistance, replace thermistor if faulty
E3 Evaporator coil sensor failure Indoor coil thermistor open or short circuit Inspect sensor connection on evaporator, replace if out of spec
E4 Outdoor coil sensor abnormality Outdoor unit condenser coil thermistor failure Check outdoor coil sensor wiring, measure resistance, replace sensor
E5 Over-voltage or under-voltage protection Input power supply voltage out of acceptable range Check incoming voltage with multimeter, verify power supply stability
E6 Evaporator temperature sensor open circuit Indoor evaporator thermistor disconnected or broken Inspect sensor wiring, check connector, replace thermistor
E7 Indoor/outdoor unit miscommunication Serial communication failure between units Check communication cable, verify polarity, inspect PCB connectors
E8 Overheating protection Compressor or system temperature exceeds safe limit Check refrigerant charge, condenser airflow, compressor condition
EC Refrigerant leak detection Refrigerant leak sensor triggered or low charge detected Perform leak test, repair leak, recharge system to nameplate spec
E0 EEPROM parameter error Indoor or outdoor unit EEPROM data corrupted Power cycle the unit, replace main PCB if error persists
F1 Outdoor ambient temperature sensor fault Outdoor ambient thermistor open or short circuit Check sensor wiring on outdoor unit, replace thermistor
F2 Condenser coil temperature sensor fault Condenser coil thermistor (T3) open or short circuit Inspect sensor on condenser coil, replace if resistance out of spec
F3 Discharge temperature sensor fault Compressor discharge thermistor (T5) open or short circuit Check sensor on compressor discharge line, replace if needed
F4 Outdoor unit EEPROM error Outdoor PCB EEPROM data corrupted or missing Power cycle outdoor unit, replace outdoor PCB if error persists
F5 Outdoor fan speed out of control Outdoor fan motor not running at expected speed Check fan motor, wiring, and fan blade for obstruction
P0 Inverter module (IPM) protection IPM overcurrent or overheat protection triggered Check compressor windings, inverter board, and heat sink cooling
P1 Over-voltage / under-voltage protection DC bus voltage out of normal operating range Check input voltage, rectifier circuit, DC bus capacitors
P2 Compressor top high temperature protection Compressor shell temperature exceeds safe limit Check refrigerant charge, suction superheat, and compressor valves
P3 Outdoor high/low pressure protection Refrigerant pressure exceeds high or low pressure limit Check refrigerant charge, condenser/evaporator, and expansion valve
P4 Compressor drive error Inverter compressor drive circuit malfunction Check inverter board, compressor winding insulation, and wiring
P5 Condenser coil high temperature protection Condenser coil temperature too high in cooling mode Clean condenser coil, check outdoor fan, verify refrigerant charge
DF Defrost mode active Normal defrost cycle running in heating mode No action needed, wait for defrost cycle to complete
H1 Defrost protection Outdoor coil frosted, triggering defrost Normal in heating mode; if frequent, check outdoor coil sensor and refrigerant
L4 Locked rotor condition Compressor rotor mechanically locked Check compressor, starting components, and refrigerant pressures
02 High pressure fault High pressure switch tripped or pressure too high Check condenser, outdoor fan, refrigerant overcharge, non-condensables
21 Low pressure control open Low pressure switch tripped or loss of charge Check for leaks, verify refrigerant charge, inspect expansion device
83 Condenser coil temperature fault Condenser sensor reading abnormal Check sensor placement, measure resistance, replace if out of range
84 Outdoor ambient temperature fault Outdoor temp sensor reading out of range Check sensor placement, ensure not near heat source, replace if faulty

TCL

China • 26 error codes

View all TCL codes →
Code Description Cause Action
E0 Indoor/outdoor communication fault Communication wire fault or PCB failure between units Check communication wiring, connectors, and control boards on both units
E1 Room temperature sensor (IRT) fault Indoor room thermistor open or short circuit Check sensor wiring and connector, measure resistance, replace if faulty
E2 Indoor coil temperature sensor (IPT) fault Indoor pipe/coil thermistor open or short circuit Inspect sensor on evaporator coil, replace if resistance out of spec
E3 Outdoor coil temperature sensor (OPT) fault Outdoor pipe/coil thermistor open or short circuit Check sensor on condenser coil at outdoor unit, replace if needed
E4 System abnormality General system fault detected by control board Power cycle the unit, check all sensors and wiring, inspect for refrigerant issues
E5 Model configuration mismatch Indoor and outdoor unit model types do not match Verify correct indoor/outdoor unit pairing, check DIP switch settings
E6 Indoor fan motor fault Indoor fan motor failure or speed signal lost Check fan motor wiring, capacitor, hall sensor, replace motor if faulty
E7 Outdoor ambient temperature sensor fault Outdoor ambient thermistor open or short circuit Check sensor wiring on outdoor unit, replace thermistor
E8 Discharge temperature sensor fault Compressor discharge thermistor open or short circuit Inspect sensor on discharge line, replace if resistance out of range
E9 Inverter power module (IPM) fault IPM drive module failure or abnormality Check compressor windings, inverter board, and power supply to module
EA Current sensor fault Current transformer (CT) sensor failure on outdoor board Check CT sensor wiring and connection, replace outdoor power board if faulty
EC Outdoor unit communication fault Communication failure within outdoor unit boards Check wiring between outdoor main board and driver board
EE EEPROM fault EEPROM chip on main PCB corrupted or not seated Check EEPROM chip seating, replace indoor or outdoor PCB board
EF Outdoor fan motor fault (DC) Outdoor DC fan motor failure or speed signal abnormal Check fan motor wiring, hall sensor, blade obstruction, replace motor
EH Intake temperature sensor fault Suction/intake air thermistor open or short circuit Inspect sensor wiring, check resistance, replace sensor if faulty
EP Compressor top temperature switch fault Temperature switch on compressor top open or faulty Check switch wiring to CN3 on outdoor board, replace switch if needed
EU Voltage sensor fault Voltage sensing circuit failure on outdoor power board Check voltage sensor circuit, replace outdoor power source board
P0 IPM protection (hardware) Hardware-level overcurrent in inverter power module Check compressor insulation, wiring, and inverter board components
P1 Over-voltage / under-voltage protection Input power supply voltage out of acceptable range Check incoming voltage with multimeter, verify power supply stability
P2 Overcurrent protection Compressor or system drawing excessive current Check compressor windings, power supply, and refrigerant charge
P4 Exhaust over-temperature protection Compressor discharge temperature exceeds safe limit Check refrigerant charge, superheat, condenser cleanliness
P5 Subcooling protection in cooling mode Subcooling value below minimum in cooling operation Check refrigerant charge, expansion valve, and condenser airflow
P6 Overheating protection in cooling mode Evaporator coil temperature too high during cooling Check indoor airflow, air filter, fan motor, and refrigerant charge
P7 Overheating protection in heating mode Indoor coil temperature too high during heating Check indoor airflow, air filter, fan motor operation
P8 Outdoor over/under-temperature protection Outdoor ambient temperature outside operating range Check outdoor ambient sensor, verify operating conditions are within spec
P9 IPM protection (software) Software-level drive protection in inverter module Check compressor, inverter board, and reset power to clear fault

Troubleshooting Tips

  • Record the exact error code - Some brands use letters, numbers, or both
  • Check for multiple errors - Some systems store error history in service mode
  • Note when the error occurs - Startup, during operation, or after running
  • Check both indoor and outdoor units - Errors may be displayed on either unit
  • Reset after repair - Clear error codes after fixing the issue
  • Some codes are informational - Not all codes indicate a fault (e.g., defrost mode)