MR28-LH
MR Series • Refrigeration Controller
Quick Info
Output Functions
Multi-compressor rack controller with up to 8 compressors
Technical Specifications
Display & Interface
| Display Type | LCD |
| Display Digits | 4 |
| Buttons | 6 |
| LED Indicators | Comp1, Comp2, Comp3, Comp4, Alarm, Network |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 100-240V AC |
| Frequency | 50/60Hz |
| Power Consumption | 8VA |
Sensor Inputs
| Probe Inputs | 4 |
| Probe Type | NTC / 4-20mA pressure |
| Temp Range | -50 to 150°C |
| Accuracy | ±0.3°C |
Relay Outputs
| Relay Outputs | 8 |
| Relay Rating | 8A/250VAC |
Physical
| Panel Size | 96x96 mm |
| Depth | 85 mm |
| IP Rating | IP54 (front) |
| Weight | 320 g |
Operating Conditions
| Operating Temp | -10 to 55°C |
| Storage Temp | -25 to 65°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| 1-2 | Power 230VAC | Input |
brown/blue
|
| 3-4 | Suction Pressure 4-20mA | Input |
red/black
|
| 5-6 | Discharge Pressure 4-20mA | Input |
yellow/black
|
| 7-8 | Oil Pressure | Input |
green/black
|
| 9-10 | Temperature Probe | Input |
orange/white
|
| 11-12 | RS485 A+/B- | Comm |
orange/yellow
|
| 13-14 | Compressor 1 | Output |
black
|
| 15-16 | Compressor 2 | Output |
black
|
| 17-18 | Compressor 3 | Output |
black
|
| 19-20 | Compressor 4 | Output |
black
|
| 21-22 | Unloader/Comp5 | Output |
gray
|
| 23-24 | Unloader/Comp6 | Output |
gray
|
| 25-26 | Condenser Fan | Output |
blue
|
| 27-28 | Alarm | Output |
red
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SP | Pressure Setpoint | 0 to 30 | 4 bar | Suction pressure setpoint |
| dP | Differential | 0.1 to 5 | 0.5 bar | Compressor staging differential |
| ST | Stage Time | 30 to 600 | 120 sec | Minimum time between stages |
| NC | Number of Comp | 1 to 8 | 4 | Number of compressors |
| RL | Rotation Logic | 0=FIFO,1=Runtime | 1 | Compressor rotation method |
| HP | HP Cutout | 10 to 35 | 28 bar | High pressure cutout |
| LP | LP Cutout | -1 to 5 | 0 bar | Low pressure cutout |
Error Codes
Solution: Check condenser and fans
Solution: Check refrigerant charge
Solution: Check oil level and pump
Solution: Check 4-20mA wiring
Solution: Check transducer
Solution: Check motor protection
Frequently Asked Questions
First In First Out - compressors cycle in fixed order
Compressor with lowest runtime starts first for equal wear
Alternative Models (Cross Reference)
Manufacturer Information
Brand: LAE
Country: Italy