LTR-5CSRE-AG
LTR Series • Refrigeration Controller
Quick Info
Output Functions
Advanced refrigeration controller with RS485 Modbus communication
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 3 |
| Buttons | 4 |
| LED Indicators | Compressor, Defrost, Fan, Alarm, Comm |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 100-240V AC |
| Frequency | 50/60Hz |
| Power Consumption | 4VA |
Sensor Inputs
| Probe Inputs | 3 |
| Probe Type | NTC / PTC |
| Temp Range | -50 to 150°C |
| Accuracy | ±0.5°C |
Relay Outputs
| Relay Outputs | 4 |
| Relay Rating | 8A/250VAC (Comp 16A) |
Physical
| Panel Size | 32x74 mm |
| Depth | 68 mm |
| IP Rating | IP65 (front) |
| Weight | 115 g |
Operating Conditions
| Operating Temp | -10 to 55°C |
| Storage Temp | -25 to 65°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| 1 | Power L | Input |
brown
|
| 2 | Power N | Input |
blue
|
| 3 | Probe 1 | Input |
yellow
|
| 4 | Probe 1 | Input |
white
|
| 5 | Probe 2 | Input |
green
|
| 6 | Probe 2 | Input |
white
|
| 7 | Probe 3 | Input |
orange
|
| 8 | Probe 3 | Input |
white
|
| 9 | RS485 A+ | Comm |
orange
|
| 10 | RS485 B- | Comm |
yellow
|
| 11 | Comp COM | Output |
black
|
| 12 | Comp NO | Output |
black
|
| 13 | Defrost COM | Output |
red
|
| 14 | Defrost NO | Output |
red
|
| 15 | Fan COM | Output |
blue
|
| 16 | Fan NO | Output |
blue
|
| 17 | Alarm COM | Output |
gray
|
| 18 | Alarm NO | Output |
gray
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SP | Setpoint | -50 to 99 | -18 °C | Temperature setpoint |
| HY | Differential | 0.1 to 20 | 2 °C | Switching differential |
| dT | Defrost Type | 0=Off,1=Elec,2=Gas | 1 | Defrost method |
| dI | Defrost Interval | 0 to 99 | 8 hr | Defrost interval |
| dL | Defrost Duration | 0 to 255 | 30 min | Max defrost time |
| dE | Defrost End | -50 to 50 | 8 °C | End defrost temperature |
| Fd | Fan Delay | 0 to 30 | 3 min | Fan delay after defrost |
| FA | Fan Mode | 0-3 | 1 | Fan operation mode |
| Ad | Address | 1 to 247 | 1 | Modbus address |
| bd | Baud Rate | 0=9600,1=19200 | 0 | Communication speed |
Error Codes
Solution: Check room probe wiring
Solution: Check evaporator probe
Solution: Check condenser probe
Solution: Normal operation
Solution: Check refrigeration system
Solution: Check setpoint
Solution: Clean condenser coil
Frequently Asked Questions
Access parameter Ad for address (1-247), bd for baud rate
Optional condenser temperature monitoring for high pressure alarm
Alternative Models (Cross Reference)
Manufacturer Information
Brand: LAE
Country: Italy