Honeywell

UDC2800

UDC Series • Industrial Controller

UDC2800

Quick Info

Type Industrial
Application Process Control
Probe Inputs 2
Relay Outputs 4
Communication RS485 Modbus / Ethernet (option)
Panel Size 1/4 DIN (96x96) mm

Output Functions

R1 Control 1
R2 Control 2
R3 Alarm 1
R4 Alarm 2

Universal digital controller, replacement for UDC2500/3200

Technical Specifications

Display & Interface

Display Type LCD
Display Digits 5
Buttons 6
LED Indicators Output 1, Output 2, Alarm 1, Alarm 2, Auto

Power Supply

Voltage 100-240V AC
Voltage Range 85-264V AC
Frequency 47-63Hz
Power Consumption 15VA

Sensor Inputs

Probe Inputs 2
Probe Type TC / RTD / mA / mV
Temp Range -200 to 1800°C
Accuracy ±0.1%

Relay Outputs

Relay Outputs 4
Relay Rating 3A/250VAC

Physical

Panel Size 1/4 DIN (96x96) mm
Depth 150 mm
IP Rating IP65 (front)
Weight 550 g

Operating Conditions

Operating Temp 0 to 55°C
Storage Temp -40 to 70°C

Wiring Terminals

Terminal Function Type Wire Color
L/N Power AC Input
brown/blue
IN1+/IN1- Input 1 Input
per sensor
IN2+/IN2- Input 2 Input
per sensor
OUT1 Control Output 1 Output
relay
OUT2 Control Output 2 Output
relay/mA
ALM1 Alarm 1 Output
red
ALM2 Alarm 2 Output
red
RETX Retransmit 4-20mA Output
purple
A/B RS485 Modbus Comm
yellow/green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SP1 Setpoint 1 Per input range 100 °C Primary setpoint
SP2 Setpoint 2 Per input range 50 °C Secondary setpoint
Pb Prop Band 0.1 to 999.9 5 °C/% Proportional band
Ti Integral Time 0 to 9999 120 sec Reset time
Td Derivative Time 0 to 9999 30 sec Rate time
AT Auto-Tune 0=Off, 1=On 0 Start auto-tuning
AL1 Alarm 1 SP Per input range 150 °C Alarm 1 setpoint
AL2 Alarm 2 SP Per input range 0 °C Alarm 2 setpoint
RMP Ramp Rate 0 to 999 0 °C/min Setpoint ramp rate

Error Codes

E01 Input 1 open/short

Solution: Check sensor wiring

E02 Input 2 open/short

Solution: Check sensor 2

E10 ADC error

Solution: Internal fault, service required

E20 EEPROM error

Solution: Reset to defaults

AL1 Alarm 1 active

Solution: Check process

AL2 Alarm 2 active

Solution: Check process

Frequently Asked Questions

Alternative Models (Cross Reference)

UDC3500 Omron E5CC Watlow PM6

Manufacturer Information

Brand: Honeywell

Country: USA

Visit Manufacturer Website