UDC2800
UDC Series • Industrial Controller
Quick Info
Output Functions
Universal digital controller, replacement for UDC2500/3200
Technical Specifications
Display & Interface
| Display Type | LCD |
| Display Digits | 5 |
| Buttons | 6 |
| LED Indicators | Output 1, Output 2, Alarm 1, Alarm 2, Auto |
Power Supply
| Voltage | 100-240V AC |
| Voltage Range | 85-264V AC |
| Frequency | 47-63Hz |
| Power Consumption | 15VA |
Sensor Inputs
| Probe Inputs | 2 |
| Probe Type | TC / RTD / mA / mV |
| Temp Range | -200 to 1800°C |
| Accuracy | ±0.1% |
Relay Outputs
| Relay Outputs | 4 |
| Relay Rating | 3A/250VAC |
Physical
| Panel Size | 1/4 DIN (96x96) mm |
| Depth | 150 mm |
| IP Rating | IP65 (front) |
| Weight | 550 g |
Operating Conditions
| Operating Temp | 0 to 55°C |
| Storage Temp | -40 to 70°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L/N | Power AC | Input |
brown/blue
|
| IN1+/IN1- | Input 1 | Input |
per sensor
|
| IN2+/IN2- | Input 2 | Input |
per sensor
|
| OUT1 | Control Output 1 | Output |
relay
|
| OUT2 | Control Output 2 | Output |
relay/mA
|
| ALM1 | Alarm 1 | Output |
red
|
| ALM2 | Alarm 2 | Output |
red
|
| RETX | Retransmit 4-20mA | Output |
purple
|
| A/B | RS485 Modbus | Comm |
yellow/green
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SP1 | Setpoint 1 | Per input range | 100 °C | Primary setpoint |
| SP2 | Setpoint 2 | Per input range | 50 °C | Secondary setpoint |
| Pb | Prop Band | 0.1 to 999.9 | 5 °C/% | Proportional band |
| Ti | Integral Time | 0 to 9999 | 120 sec | Reset time |
| Td | Derivative Time | 0 to 9999 | 30 sec | Rate time |
| AT | Auto-Tune | 0=Off, 1=On | 0 | Start auto-tuning |
| AL1 | Alarm 1 SP | Per input range | 150 °C | Alarm 1 setpoint |
| AL2 | Alarm 2 SP | Per input range | 0 °C | Alarm 2 setpoint |
| RMP | Ramp Rate | 0 to 999 | 0 °C/min | Setpoint ramp rate |
Error Codes
Solution: Check sensor wiring
Solution: Check sensor 2
Solution: Internal fault, service required
Solution: Reset to defaults
Solution: Check process
Solution: Check process
Frequently Asked Questions
UDC2500, UDC3200, UDC3500 with enhanced features
Set AT=1 to start, controller calculates optimal PID
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Honeywell
Country: USA