Honeywell

T6861V2WB

T6800 Series • HVAC Controller

T6861V2WB

Quick Info

Type HVAC
Application FCU
Probe Inputs 1
Relay Outputs 4
Communication Modbus (model dependent)
Panel Size 120x120 wall mm

Output Functions

R1 Fan Low
R2 Fan Med
R3 Fan High
R4 Valve

Fan coil thermostat with modulating valve output

Technical Specifications

Display & Interface

Display Type LCD
Display Digits 3
Buttons 5
LED Indicators Heat, Cool, Fan

Power Supply

Voltage 220-240V AC
Voltage Range 195-264V AC
Frequency 50/60Hz
Power Consumption 5VA

Sensor Inputs

Probe Inputs 1
Probe Type NTC (internal)
Temp Range 0 to 40°C
Accuracy ±0.5°C

Relay Outputs

Relay Outputs 4
Relay Rating 3A/250VAC

Physical

Panel Size 120x120 wall mm
Depth 38 mm
IP Rating IP30
Weight 200 g

Operating Conditions

Operating Temp 0 to 50°C
Storage Temp -20 to 60°C

Wiring Terminals

Terminal Function Type Wire Color
L Power L Input
brown
N Power N Input
blue
FL Fan Low Output
green
FM Fan Med Output
yellow
FH Fan High Output
red
V Valve Output
orange
AO 0-10V Valve Output
purple

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SP Setpoint 10 to 35 22 °C Room temperature setpoint
dT Differential 0.5 to 4 1 °C Control band
Md Mode 0=Auto, 1=Heat, 2=Cool, 3=Fan 0 Operating mode
FS Fan Speed 0=Auto, 1=L, 2=M, 3=H 0 Fan speed selection
VT Valve Type 0=On/Off, 1=Modulating 1 Valve control type
dZ Dead Zone 0 to 5 1 °C Neutral zone

Error Codes

E1 Sensor fault

Solution: Replace thermostat

E3 EEPROM error

Solution: Factory reset

Frequently Asked Questions

Alternative Models (Cross Reference)

T6861H2WB Carel FCR3 Danfoss ERC 214

Manufacturer Information

Brand: Honeywell

Country: USA

Visit Manufacturer Website