Honeywell

T6380A1004

T6300 Series • HVAC Controller

T6380A1004

Quick Info

Type HVAC
Application Fan Coil
Probe Inputs 2
Relay Outputs 6
Communication RS485 (optional)
Panel Size 125x85 wall mm

Output Functions

R1 Fan L
R2 Fan M
R3 Fan H
R4 Heat Valve
R5 Cool Valve
R6 Aux

Digital programmable thermostat for 4-pipe FCU

Technical Specifications

Display & Interface

Display Type LCD
Display Digits 4
Buttons 6
LED Indicators Heat, Cool, Fan, Timer

Power Supply

Voltage 220-240V AC
Voltage Range 195-264V AC
Frequency 50/60Hz
Power Consumption 5VA

Sensor Inputs

Probe Inputs 2
Probe Type NTC (internal + remote)
Temp Range 0 to 40°C
Accuracy ±0.5°C

Relay Outputs

Relay Outputs 6
Relay Rating 3A/250VAC

Physical

Panel Size 125x85 wall mm
Depth 40 mm
IP Rating IP30
Weight 220 g

Operating Conditions

Operating Temp 0 to 50°C
Storage Temp -20 to 60°C

Wiring Terminals

Terminal Function Type Wire Color
L Power L Input
brown
N Power N Input
blue
RP Remote Probe Input
red/white
FL Fan Low Output
green
FM Fan Med Output
yellow
FH Fan High Output
red
HV Heat Valve Output
orange
CV Cool Valve Output
blue
AUX Auxiliary Output
white

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SPH Heating SP 10 to 30 20 °C Heat setpoint
SPC Cooling SP 18 to 35 24 °C Cool setpoint
dT Differential 0.5 to 3 1 °C Control band
Md Mode 0-4 0 0=Auto, 1=Heat, 2=Cool, 3=Fan, 4=Off
FS Fan Speed 0=Auto, 1=L, 2=M, 3=H 0 Fan selection
PR Program Mode 0=Off, 1=5+2, 2=7 day 1 Schedule type
Pb Probe Select 0=Int, 1=Remote, 2=Average 0 Temperature source

Error Codes

E1 Internal sensor error

Solution: Replace unit

E2 Remote sensor error

Solution: Check remote sensor wiring

E5 Clock error

Solution: Reset time

Frequently Asked Questions