Eliwell

IWC 750

IWC Series • Refrigeration Controller

IWC 750

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 2
Relay Outputs 3
Communication RS485 (optional)
Panel Size 32x74 mm

Output Functions

R1 Compressor
R2 Defrost
R3 Fan

Three relay controller for low temperature refrigeration with fan management

Technical Specifications

Display & Interface

Display Type LED
Display Digits 3
Buttons 4
LED Indicators Compressor, Defrost, Fan

Power Supply

Voltage 230V AC
Voltage Range 100-240V AC
Frequency 50/60Hz
Power Consumption 4VA

Sensor Inputs

Probe Inputs 2
Probe Type NTC 10K
Temp Range -50 to 110°C
Accuracy ±0.5°C

Relay Outputs

Relay Outputs 3
Relay Rating 8A/250VAC

Physical

Panel Size 32x74 mm
Depth 60 mm
IP Rating IP65 (front)
Weight 100 g

Operating Conditions

Operating Temp -5 to 55°C
Storage Temp -25 to 70°C

Wiring Terminals

Terminal Function Type Wire Color
1 Power L Input
brown
2 Power N Input
blue
3 Probe 1 (+) Input
red
4 Probe 1 (-) Input
white
5 Probe 2 (+) Input
red
6 Probe 2 (-) Input
white
7 Digital Input Input
gray
8 DI Common Input
gray
9 Relay 1 NO (Comp) Output
black
10 Relay 1 COM Output
black
11 Relay 2 NO (Def) Output
orange
12 Relay 2 COM Output
orange
13 Relay 3 NO (Fan) Output
green
14 Relay 3 COM Output
green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SET Setpoint -50 to 110 -18 °C Temperature setpoint
Hy Differential 0.1 to 25.5 2 °C Switching differential
dFt Defrost Type 0=Off, 1=Elec, 2=Gas 1 Defrost method
dt Defrost Duration 0 to 255 30 min Maximum defrost time
dit Defrost Interval 0 to 24 6 hr Time between defrosts
dSt Defrost End Temp 0 to 50 8 °C Termination temperature
Fdt Fan Delay 0 to 255 2 min Fan delay after defrost
FCO Fan Cutout 0=Off, 1=On 1 Stop fan during defrost

Error Codes

E1 Room probe fault

Solution: Check probe 1 wiring

E2 Evaporator probe fault

Solution: Check probe 2 wiring

HI High temp alarm

Solution: Check refrigeration system

LO Low temp alarm

Solution: Check setpoint

dF Defrost active

Solution: Normal operation

Frequently Asked Questions

Alternative Models (Cross Reference)

Dixell XR60CX Carel IR33 Danfoss EKC 202

Manufacturer Information