Eliwell
IWC 720
IWC Series • Refrigeration Controller
Quick Info
Type
Refrigeration
Application
Cold Room
Probe Inputs
2
Relay Outputs
2
Communication
RS485 (optional)
Panel Size
32x74 mm
Output Functions
R1
Compressor
R2
Defrost
Two relay controller for medium temperature refrigeration
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 3 |
| Buttons | 4 |
| LED Indicators | Compressor, Defrost |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 100-240V AC |
| Frequency | 50/60Hz |
| Power Consumption | 4VA |
Sensor Inputs
| Probe Inputs | 2 |
| Probe Type | NTC 10K |
| Temp Range | -50 to 110°C |
| Accuracy | ±0.5°C |
Relay Outputs
| Relay Outputs | 2 |
| Relay Rating | 8A/250VAC |
Physical
| Panel Size | 32x74 mm |
| Depth | 60 mm |
| IP Rating | IP65 (front) |
| Weight | 95 g |
Operating Conditions
| Operating Temp | -5 to 55°C |
| Storage Temp | -25 to 70°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| 1 | Power L | Input |
brown
|
| 2 | Power N | Input |
blue
|
| 3 | Probe 1 (+) | Input |
red
|
| 4 | Probe 1 (-) | Input |
white
|
| 5 | Probe 2 (+) | Input |
red
|
| 6 | Probe 2 (-) | Input |
white
|
| 7 | Relay 1 NO (Comp) | Output |
black
|
| 8 | Relay 1 COM | Output |
black
|
| 9 | Relay 2 NO (Def) | Output |
orange
|
| 10 | Relay 2 COM | Output |
orange
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SET | Setpoint | -50 to 110 | 4 °C | Temperature setpoint |
| Hy | Differential | 0.1 to 25.5 | 2 °C | Switching differential |
| dFt | Defrost Type | 0=Off, 1=Elec, 2=Gas | 1 | Defrost method |
| dt | Defrost Duration | 0 to 255 | 20 min | Maximum defrost time |
| dit | Defrost Interval | 0 to 24 | 8 hr | Time between defrosts |
| dSt | Defrost End Temp | 0 to 50 | 8 °C | Termination temperature |
Error Codes
E1
Room probe fault
Solution: Check probe 1 wiring
E2
Evaporator probe fault
Solution: Check probe 2 wiring
dF
Defrost active
Solution: Normal operation
Frequently Asked Questions
IWC 750 has 3 relays including fan control, IWC 720 has 2 relays
Alternative Models (Cross Reference)
Dixell XR40CX
Carel PJEZC
Manufacturer Information
Brand: Eliwell
Country: Italy
Parent: Schneider Electric