Eliwell

EWTS Plus 990

EWTS Plus Series • Temperature Controller

EWTS Plus 990

Quick Info

Type Temperature
Application Multi-zone
Probe Inputs 4
Relay Outputs 4
Communication RS485 Modbus RTU
Panel Size 71x29 mm

Output Functions

R1 Heat
R2 Cool
R3 Alarm
R4 Aux

Advanced multi-probe temperature controller with RS485

Technical Specifications

Display & Interface

Display Type LED
Display Digits 4
Buttons 5
LED Indicators Heat, Cool, Alarm, RS485

Power Supply

Voltage 230V AC
Voltage Range 100-240V AC
Frequency 50/60Hz
Power Consumption 5VA

Sensor Inputs

Probe Inputs 4
Probe Type NTC 10K / PTC / PT100
Temp Range -50 to 400°C
Accuracy ±0.3°C

Relay Outputs

Relay Outputs 4
Relay Rating 8A/250VAC (x2), 5A/250VAC (x2)

Physical

Panel Size 71x29 mm
Depth 65 mm
IP Rating IP65 (front)
Weight 120 g

Operating Conditions

Operating Temp -10 to 55°C
Storage Temp -25 to 70°C

Wiring Terminals

Terminal Function Type Wire Color
1 Power L Input
brown
2 Power N Input
blue
3-4 Probe 1 Input
red/white
5-6 Probe 2 Input
red/white
7-8 Probe 3 Input
red/white
9-10 Probe 4 Input
red/white
11-12 Output 1 (Heat) Output
black
13-14 Output 2 (Cool) Output
black
15-16 Output 3 (Alarm) Output
red
17-18 Output 4 (Aux) Output
black
19 RS485 A+ Comm
yellow
20 RS485 B- Comm
green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SP1 Setpoint 1 -50 to 400 25 °C Main setpoint
SP2 Setpoint 2 -50 to 400 30 °C Second setpoint
Hy1 Differential 1 0.1 to 25.5 1 °C Switching differential 1
Hy2 Differential 2 0.1 to 25.5 1 °C Switching differential 2
Pb1 Probe 1 Type 0-3 0 0=NTC, 1=PTC, 2=PT100, 3=PT1000
Pb2 Probe 2 Type 0-3 0 0=NTC, 1=PTC, 2=PT100, 3=PT1000
Pb3 Probe 3 Type 0-3 0 0=NTC, 1=PTC, 2=PT100, 3=PT1000
Pb4 Probe 4 Type 0-3 0 0=NTC, 1=PTC, 2=PT100, 3=PT1000
O1F Output 1 Function 0-5 1 0=Off, 1=Heat, 2=Cool, 3=Alarm, 4=Fan, 5=Aux
O2F Output 2 Function 0-5 2 Output 2 assignment
O3F Output 3 Function 0-5 3 Output 3 assignment
O4F Output 4 Function 0-5 5 Output 4 assignment
Add Modbus Address 1 to 247 1 RS485 address
bAU Baud Rate 0-3 2 0=2400, 1=4800, 2=9600, 3=19200

Error Codes

E1 Probe 1 fault

Solution: Check probe 1 wiring/type

E2 Probe 2 fault

Solution: Check probe 2 wiring/type

E3 Probe 3 fault

Solution: Check probe 3 wiring/type

E4 Probe 4 fault

Solution: Check probe 4 wiring/type

HI High temp alarm

Solution: Temperature above limit

LO Low temp alarm

Solution: Temperature below limit

CnF Comm error

Solution: Check RS485 connection