Eliwell

EWDR 984

EWDR Series • Refrigeration Controller

EWDR 984

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 4
Relay Outputs 6
Communication RS485 Modbus
Panel Size 71x29 mm

Output Functions

R1 Compressor 1
R2 Compressor 2
R3 Defrost
R4 Fan
R5 Alarm
R6 Auxiliary

Rack controller for multi-evaporator cold room systems

Technical Specifications

Display & Interface

Display Type LED
Display Digits 4
Buttons 6
LED Indicators Comp 1, Comp 2, Defrost, Fan, Alarm, Remote

Power Supply

Voltage 230V AC
Voltage Range 100-240V AC
Frequency 50/60Hz
Power Consumption 8VA

Sensor Inputs

Probe Inputs 4
Probe Type NTC 10K / PT1000
Temp Range -50 to 150°C
Accuracy ±0.3°C

Relay Outputs

Relay Outputs 6
Relay Rating 8A/250VAC

Physical

Panel Size 71x29 mm
Depth 74 mm
IP Rating IP65 (front)
Weight 160 g

Operating Conditions

Operating Temp -10 to 55°C
Storage Temp -30 to 70°C

Wiring Terminals

Terminal Function Type Wire Color
L Power L Input
brown
N Power N Input
blue
Pb1 Probe 1 (Room) Input
red/white
Pb2 Probe 2 (Evap) Input
red/white
Pb3 Probe 3 (Discharge) Input
red/white
Pb4 Probe 4 (Auxiliary) Input
red/white
DI1 Digital Input 1 Input
gray
DI2 Digital Input 2 Input
gray
GND Input Common Input
gray
R1 Relay 1 (Comp 1) Output
black
R2 Relay 2 (Comp 2) Output
black
R3 Relay 3 (Defrost) Output
orange
R4 Relay 4 (Fan) Output
green
R5 Relay 5 (Alarm) Output
red
R6 Relay 6 (Aux) Output
yellow
A RS485 A Comm
blue
B RS485 B Comm
yellow

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SET Setpoint -50 to 150 0 °C Main temperature setpoint
SET2 Night Setpoint -50 to 150 -2 °C Energy saving setpoint
Hy Differential 0.1 to 25.5 2 °C Control differential
Hy2 Stage 2 Diff 0.1 to 25.5 4 °C Second compressor differential
dOn Comp Delay 0 to 255 0 min Compressor startup delay
dOF Min Off Time 0 to 255 3 min Minimum compressor off time
CdL Stage Delay 0 to 255 5 min Delay between stages
dFt Defrost Type 0-4 1 Defrost method
dt Defrost Duration 0 to 255 30 min Maximum defrost time
dit Defrost Interval 0 to 48 6 hr Time between defrosts
dSt Defrost End Temp 0 to 50 8 °C Termination temperature

Error Codes

E1 Room probe fault

Solution: Check probe 1 connections

E2 Evaporator probe fault

Solution: Check probe 2 connections

E3 Discharge probe fault

Solution: Check probe 3 connections

E4 Auxiliary probe fault

Solution: Check probe 4 connections

HI High temp alarm

Solution: Check system capacity

LO Low temp alarm

Solution: Check setpoint and defrosts

HP High pressure alarm

Solution: Check condenser and airflow

LP Low pressure alarm

Solution: Check refrigerant charge

Frequently Asked Questions

Alternative Models (Cross Reference)

Dixell XC660D Carel pCO5 Danfoss AKC 115

Manufacturer Information

Brand: Eliwell

Country: Italy

Parent: Schneider Electric

Visit Manufacturer Website