EWDR 984
EWDR Series • Refrigeration Controller
Quick Info
Output Functions
Rack controller for multi-evaporator cold room systems
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 4 |
| Buttons | 6 |
| LED Indicators | Comp 1, Comp 2, Defrost, Fan, Alarm, Remote |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 100-240V AC |
| Frequency | 50/60Hz |
| Power Consumption | 8VA |
Sensor Inputs
| Probe Inputs | 4 |
| Probe Type | NTC 10K / PT1000 |
| Temp Range | -50 to 150°C |
| Accuracy | ±0.3°C |
Relay Outputs
| Relay Outputs | 6 |
| Relay Rating | 8A/250VAC |
Physical
| Panel Size | 71x29 mm |
| Depth | 74 mm |
| IP Rating | IP65 (front) |
| Weight | 160 g |
Operating Conditions
| Operating Temp | -10 to 55°C |
| Storage Temp | -30 to 70°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| Pb1 | Probe 1 (Room) | Input |
red/white
|
| Pb2 | Probe 2 (Evap) | Input |
red/white
|
| Pb3 | Probe 3 (Discharge) | Input |
red/white
|
| Pb4 | Probe 4 (Auxiliary) | Input |
red/white
|
| DI1 | Digital Input 1 | Input |
gray
|
| DI2 | Digital Input 2 | Input |
gray
|
| GND | Input Common | Input |
gray
|
| R1 | Relay 1 (Comp 1) | Output |
black
|
| R2 | Relay 2 (Comp 2) | Output |
black
|
| R3 | Relay 3 (Defrost) | Output |
orange
|
| R4 | Relay 4 (Fan) | Output |
green
|
| R5 | Relay 5 (Alarm) | Output |
red
|
| R6 | Relay 6 (Aux) | Output |
yellow
|
| A | RS485 A | Comm |
blue
|
| B | RS485 B | Comm |
yellow
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SET | Setpoint | -50 to 150 | 0 °C | Main temperature setpoint |
| SET2 | Night Setpoint | -50 to 150 | -2 °C | Energy saving setpoint |
| Hy | Differential | 0.1 to 25.5 | 2 °C | Control differential |
| Hy2 | Stage 2 Diff | 0.1 to 25.5 | 4 °C | Second compressor differential |
| dOn | Comp Delay | 0 to 255 | 0 min | Compressor startup delay |
| dOF | Min Off Time | 0 to 255 | 3 min | Minimum compressor off time |
| CdL | Stage Delay | 0 to 255 | 5 min | Delay between stages |
| dFt | Defrost Type | 0-4 | 1 | Defrost method |
| dt | Defrost Duration | 0 to 255 | 30 min | Maximum defrost time |
| dit | Defrost Interval | 0 to 48 | 6 hr | Time between defrosts |
| dSt | Defrost End Temp | 0 to 50 | 8 °C | Termination temperature |
Error Codes
Solution: Check probe 1 connections
Solution: Check probe 2 connections
Solution: Check probe 3 connections
Solution: Check probe 4 connections
Solution: Check system capacity
Solution: Check setpoint and defrosts
Solution: Check condenser and airflow
Solution: Check refrigerant charge
Frequently Asked Questions
Set Hy2 for second stage differential. Compressor 2 starts when temp exceeds SET+Hy2
Configure SET2 for night setpoint and DI1 for time clock input
Press SET+UP to enter statistics menu
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Eliwell
Country: Italy
Parent: Schneider Electric