Dixell

XR77CX

XR Series • Refrigeration Controller

XR77CX

Quick Info

Type Refrigeration
Application Multi-Compressor
Probe Inputs 4
Relay Outputs 8
Communication RS485 Modbus RTU/TCP
Panel Size 96x96 mm

Output Functions

R1 Comp1
R2 Comp2
R3 Comp3
R4 Comp4
R5 Unload
R6 Fan
R7 Aux
R8 Alarm

Advanced multi-compressor controller with digital scroll support

Technical Specifications

Display & Interface

Display Type LCD
Display Digits 4
Buttons 6
LED Indicators Comp1, Comp2, Comp3, Comp4, Unload, Alarm

Power Supply

Voltage 230V AC
Voltage Range 100-240V AC
Frequency 50/60Hz
Power Consumption 8VA

Sensor Inputs

Probe Inputs 4
Probe Type NTC 10K / PT1000 / 4-20mA
Temp Range -50 to 200°C
Accuracy ±0.2°C

Relay Outputs

Relay Outputs 8
Relay Rating 8A/250VAC (x4), 5A/250VAC (x4)

Physical

Panel Size 96x96 mm
Depth 80 mm
IP Rating IP65 (front)
Weight 280 g

Operating Conditions

Operating Temp -10 to 55°C
Storage Temp -25 to 70°C

Wiring Terminals

Terminal Function Type Wire Color
L/N Power 230VAC Input
brown/blue
Pb1 Suction Pressure Input
4-20mA
Pb2 Discharge Pressure Input
4-20mA
Pb3 Suction Temp Input
NTC/PT1000
Pb4 Oil Temp Input
NTC/PT1000
DI1-4 Comp Status Input
gray
R1-R4 Compressors 1-4 Output
black
R5 Unloader/Digital Scroll Output
black
R6 Condenser Fan Output
black
R7 Auxiliary Output
black
R8 Alarm Output
red
A/B RS485 Comm
yellow/green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SP Pressure Setpoint -1.0 to 50 3.0 bar Target suction pressure
dF Neutral Band 0.1 to 3.0 0.5 bar Dead band
nCP Number of Compressors 1 to 4 4 Installed compressors
UNL Unloader Type 0-3 0 0=None, 1=Mechanical, 2=Digital, 3=VFD
ROt Rotation Mode 0-2 1 0=Fixed, 1=Lead-lag, 2=Runtime balance
ALP Low Pressure Alarm -1.0 to SP 0.5 bar LP alarm threshold
AHP High Pressure Alarm SP to 50 25 bar HP alarm threshold
OIL Oil Return 0 to 60 30 min Oil return cycle time

Error Codes

LP Low pressure alarm

Solution: Check charge, expansion valve

HP High pressure alarm

Solution: Check condenser, ambient

OIL Low oil pressure

Solution: Check oil level, return

OL1-4 Compressor overload

Solution: Check thermal overload

CPF Compressor fault

Solution: Check winding, contactors

Frequently Asked Questions

Alternative Models (Cross Reference)

Danfoss AK-PC 840 Carel pRack pR300 Emerson EC3-X33

Manufacturer Information

Brand: Dixell

Country: Italy

Parent: Emerson Climate Technologies

Visit Manufacturer Website