XR77CX
XR Series • Refrigeration Controller
Quick Info
Output Functions
Advanced multi-compressor controller with digital scroll support
Technical Specifications
Display & Interface
| Display Type | LCD |
| Display Digits | 4 |
| Buttons | 6 |
| LED Indicators | Comp1, Comp2, Comp3, Comp4, Unload, Alarm |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 100-240V AC |
| Frequency | 50/60Hz |
| Power Consumption | 8VA |
Sensor Inputs
| Probe Inputs | 4 |
| Probe Type | NTC 10K / PT1000 / 4-20mA |
| Temp Range | -50 to 200°C |
| Accuracy | ±0.2°C |
Relay Outputs
| Relay Outputs | 8 |
| Relay Rating | 8A/250VAC (x4), 5A/250VAC (x4) |
Physical
| Panel Size | 96x96 mm |
| Depth | 80 mm |
| IP Rating | IP65 (front) |
| Weight | 280 g |
Operating Conditions
| Operating Temp | -10 to 55°C |
| Storage Temp | -25 to 70°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L/N | Power 230VAC | Input |
brown/blue
|
| Pb1 | Suction Pressure | Input |
4-20mA
|
| Pb2 | Discharge Pressure | Input |
4-20mA
|
| Pb3 | Suction Temp | Input |
NTC/PT1000
|
| Pb4 | Oil Temp | Input |
NTC/PT1000
|
| DI1-4 | Comp Status | Input |
gray
|
| R1-R4 | Compressors 1-4 | Output |
black
|
| R5 | Unloader/Digital Scroll | Output |
black
|
| R6 | Condenser Fan | Output |
black
|
| R7 | Auxiliary | Output |
black
|
| R8 | Alarm | Output |
red
|
| A/B | RS485 | Comm |
yellow/green
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SP | Pressure Setpoint | -1.0 to 50 | 3.0 bar | Target suction pressure |
| dF | Neutral Band | 0.1 to 3.0 | 0.5 bar | Dead band |
| nCP | Number of Compressors | 1 to 4 | 4 | Installed compressors |
| UNL | Unloader Type | 0-3 | 0 | 0=None, 1=Mechanical, 2=Digital, 3=VFD |
| ROt | Rotation Mode | 0-2 | 1 | 0=Fixed, 1=Lead-lag, 2=Runtime balance |
| ALP | Low Pressure Alarm | -1.0 to SP | 0.5 bar | LP alarm threshold |
| AHP | High Pressure Alarm | SP to 50 | 25 bar | HP alarm threshold |
| OIL | Oil Return | 0 to 60 | 30 min | Oil return cycle time |
Error Codes
Solution: Check charge, expansion valve
Solution: Check condenser, ambient
Solution: Check oil level, return
Solution: Check thermal overload
Solution: Check winding, contactors
Frequently Asked Questions
Yes, set UNL=2 for digital scroll unloading
Set ROt=2, system will rotate based on total hours
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Dixell
Country: Italy
Parent: Emerson Climate Technologies