XR75CX
XR Series • Refrigeration Controller
Quick Info
Output Functions
Four-relay controller with light control for display cases
Technical Specifications
Display & Interface
| Display Type | LED |
| Display Digits | 4 |
| Buttons | 4 |
| LED Indicators | Compressor, Defrost, Fan, Light |
Power Supply
| Voltage | 230V AC |
| Voltage Range | 110-230V AC |
| Frequency | 50/60Hz |
| Power Consumption | 5VA |
Sensor Inputs
| Probe Inputs | 3 |
| Probe Type | NTC |
| Temp Range | -50 to 110°C |
| Accuracy | ±0.5°C |
Relay Outputs
| Relay Outputs | 4 |
| Relay Rating | 8A/250VAC |
Physical
| Panel Size | 32x74 mm |
| Depth | 65 mm |
| IP Rating | IP65 (front) |
| Weight | 115 g |
Operating Conditions
| Operating Temp | 0 to 55°C |
| Storage Temp | -25 to 60°C |
Wiring Terminals
| Terminal | Function | Type | Wire Color |
|---|---|---|---|
| L | Power L | Input |
brown
|
| N | Power N | Input |
blue
|
| Pb1 | Room Probe | Input |
red/white
|
| Pb2 | Evap Probe | Input |
red/white
|
| Pb3 | Aux Probe | Input |
red/white
|
| DI | Door Switch | Input |
gray
|
| R1 | Compressor | Output |
black
|
| R2 | Defrost | Output |
orange
|
| R3 | Fan | Output |
green
|
| R4 | Light | Output |
yellow
|
| A | RS485 A | Comm |
blue
|
| B | RS485 B | Comm |
yellow
|
Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.
Parameter Settings
| Code | Parameter | Range | Default | Description |
|---|---|---|---|---|
| SEt | Setpoint | -50 to 110 | 2 °C | Temperature setpoint |
| Hy | Differential | 0.1 to 25.5 | 2 °C | Switching differential |
| dt | Defrost Type | 0-3 | 1 | Defrost method |
| dP | Defrost Duration | 0 to 99 | 30 min | Maximum defrost time |
| dE | Defrost End Temp | 0 to 50 | 8 °C | Termination temperature |
| Fd | Fan Delay | 0 to 15 | 2 min | Fan restart delay |
| LOn | Light On Time | 00:00-23:59 | 07:00 | Light on schedule |
| LOF | Light Off Time | 00:00-23:59 | 22:00 | Light off schedule |
Error Codes
Solution: Check probe 1
Solution: Check probe 2
Solution: Check probe 3
Solution: Normal operation
Frequently Asked Questions
Set LOn for on time and LOF for off time in 24-hour format
Alternative Models (Cross Reference)
Manufacturer Information
Brand: Dixell
Country: Italy
Parent: Emerson Climate Technologies