Dixell

XR70CX

XR Series • Refrigeration Controller

XR70CX

Quick Info

Type Refrigeration
Application Cold Room
Probe Inputs 2
Relay Outputs 3
Communication RS485 (optional)
Panel Size 32x74 mm

Output Functions

R1 Compressor
R2 Defrost
R3 Fan

Advanced controller with real-time clock for scheduled defrosts

Technical Specifications

Display & Interface

Display Type LED
Display Digits 4
Buttons 4
LED Indicators Compressor, Defrost, Fan, Clock

Power Supply

Voltage 230V AC
Voltage Range 110-230V AC
Frequency 50/60Hz
Power Consumption 4VA

Sensor Inputs

Probe Inputs 2
Probe Type NTC
Temp Range -50 to 110°C
Accuracy ±0.5°C

Relay Outputs

Relay Outputs 3
Relay Rating 8A/250VAC

Physical

Panel Size 32x74 mm
Depth 59 mm
IP Rating IP65 (front)
Weight 105 g

Operating Conditions

Operating Temp 0 to 55°C
Storage Temp -25 to 60°C

Wiring Terminals

Terminal Function Type Wire Color
1 Power L Input
brown
2 Power N Input
blue
3 Probe 1 (+) Input
red
4 Probe 1 (-) Input
white
5 Probe 2 (+) Input
red
6 Probe 2 (-) Input
white
7 Digital Input Input
gray
8 DI Common Input
gray
9 Relay 1 (Comp) Output
black
10 Relay 1 COM Output
black
11 Relay 2 (Def) Output
orange
12 Relay 2 COM Output
orange
13 Relay 3 (Fan) Output
green
14 Relay 3 COM Output
green

Important: Always disconnect power before wiring. Verify terminal numbers with the actual controller label before connecting.

Parameter Settings

Code Parameter Range Default Description
SEt Setpoint -50 to 110 -18 °C Temperature setpoint
Hy Differential 0.1 to 25.5 2 °C Switching differential
dt Defrost Type 0=Off, 1=Elec, 2=Gas 1 Defrost method
dP Defrost Duration 0 to 99 30 min Maximum defrost time
dE Defrost End Temp 0 to 50 8 °C Termination temperature
td1 Defrost Time 1 00:00-23:59 06:00 First scheduled defrost
td2 Defrost Time 2 00:00-23:59 12:00 Second scheduled defrost
td3 Defrost Time 3 00:00-23:59 18:00 Third scheduled defrost
td4 Defrost Time 4 00:00-23:59 00:00 Fourth scheduled defrost
Fd Fan Delay 0 to 15 2 min Fan restart delay

Error Codes

E1 Room probe fault

Solution: Check probe 1

E2 Evaporator probe fault

Solution: Check probe 2

rtC RTC error

Solution: Set clock or replace battery

dF Defrost active

Solution: Normal operation

Frequently Asked Questions

Alternative Models (Cross Reference)

Eliwell ID Plus 974 Carel IR33+ Danfoss EKC 202

Manufacturer Information

Brand: Dixell

Country: Italy

Parent: Emerson Climate Technologies

Visit Manufacturer Website